SmartACU2000D Smart Array Controller
User Manual (with No PID Module)
2 Overview
Issue 01 (2020-02-14)
Copyright © Huawei Technologies Co., Ltd.
15
No.
Name
Specifications
Quantity
2
Position for the 24 V DC
power module (U02)
AC input: 100–240 V, 50 Hz/60 Hz
DC output: 12 V DC, 60 W (maximum); 24 V
DC, 30 W (maximum)
NOTE
If an external 24–28 V DC input is used, the DC
output voltage ranges from 21.5 V to 25.2 V.
The 24 V DC power module is optional. Its
installation position is reserved in the cabinet.
1
3
AC input terminal of the 24
V power module (JX02)
220 V/2P
1
4
Single-phase surge protective
device (SPD) (F03)
Uc=385 V AC, 20 kA/40 kA, 8/20 μs, 4P
1
5
Three-phase SPD 1 (F01)
U
c
= 680 V AC; 20 kA/40 kA; 8/20 μs; 1P
4
6
Three-phase SPD 2 (F02)
U
c
= 680 V AC; 20 kA/40 kA; 8/20 μs; 1P
4
7
Position for the Ethernet
switch (SWITCH)
-
1
8
SmartMBUS CCO (MBUS
CCO)
SmartMBUS CCO01A
1
9
SmartLogger3000
(SmartLogger)
SmartLogger3000
1
10
Fiber adapter (OFA01: TX1
RX1; OFA02: TX2 RX2)
2LC/PC-2LC/PC-4
2
11
Position for the SPD of the
power over Ethernet (PoE)
module
-
1
12
Position for the PoE module
(POE)
-
1
13
ATB (Access Terminal Box)
-
1
14
Single-phase input switch
(QF03)
32 A/2P
1
15
Three-phase input switch 2
(FU02)
25 A/3P
1
16
Three-phase input switch 1
(FU01)
25 A/3P
1
17
RS485 communications
terminal (JX01)
12P; supports the wires with a cross-sectional area
ranging from 1 mm
2
to 2.5 mm
2
(or 18–14 AWG)
1
18
Position for the
SmartModule1000A01
(SmartModule)
-
1
19
Protective earthing (PE) bar
-
1