PowerCube 5000
User Manual (SmartLi 100Ah)
7 Routine Maintenance
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
117
Maintenance
Interval
Expected
Result
Measure
Every quarter
Cleanliness
Clean the battery exterior using dry cotton cloth. Exercise caution when
cleaning a battery because its voltage is high.
Connection
Check the bolt at every terminal. If any bolt is loose, tighten it.
Every year
Voltage
Measure and record the busbar voltage and the positive and negative
voltages of the SmartLi. If the voltages are different, check for cable
faults and rectify them.
In the first year, collect real-time data when discharging is about to
complete at least once every six months.
From the second year, check the capacity quarterly.