PowerCube 5000
User Manual (SmartLi 100Ah)
B Alarm List for the Lithium Battery Cabinet
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
162
Alarm ID
(Alarm
ID-Alarm
Cause ID)
Alarm Name
Alarm
Severity
Fault Cause
Troubleshooting
0031-2
Battery
overtemperature
protection
Critical
The battery temperature is
too high.
Take measures to reduce the
ambient temperature.
0616-1
Battery
undertemperatur
e protection
Critical
The charger temperature is
too low.
Take measures to increase the
ambient temperature.
0032-4
Battery
overvoltage
protection
Critical
The battery string is
abnormal.
The battery control unit is
abnormal.
1.
Check the battery voltage.
2.
Replace the battery control
unit.
0617-3
Battery
undervoltage
protection
Critical
The battery string
overdischarges, module
voltage is less than the
setting value of module
battery LVD voltage.
Check the input source, and
charge batteries in a timely
manner.
0621-1
Battery
overcurrent
protection
Critical
The charger of the battery
control unit is faulty.
Replace the battery control
unit.
0621-2
Battery
overcurrent
protection
Critical
1.
The load exceeds the
upper threshold.
2.
The battery control unit
is damaged.
1.
Check whether the load of
power cabinet exceeds the
battery configuration.
2.
Replace the battery control
unit.
0630-2
Abnormal
intra-battery
cabinet parallel
cable
Critical
The RS485 communications
cable in the rack is faulty.
1.
Check that the
communications cables
inside the battery cabinet
are properly connected.
2.
Replace the
communications cable
between the battery
control unit and the battery
modules.
3.
Replace the battery control
unit.
0653-1
Intra-battery
cabinet parallel
cable alarm
Minor
1.
.The communications
cable of the battery
module is disconnected.
2.
The battery module is
faulty.
1.
Check that the RS485
communications cable is
properly connected.
2.
Replace the faulty battery
module.
0629-2
Abnormal
inter-battery
cabinet parallel
cable
Critical
1.
The inter-rack parallel
cable is not properly
connected.
2.
The 1# battery control
unit is faulty or the
1.
Check whether the
inter-rack parallel cable is
loose.
2.
Replace the inter-rack
parallel cable.