2
Indoor Unit
1.2
Unit: mm
(1) Water inlet hole
(2) Strong-current cable hole
(3) Water outlet hole
(4) Signal cable hole
(5) Gas pipe stop valve
(6) Liquid pipe stop valve
(Front view)
(Rear view)
(Side view)
(Front view)
(Top view)
Outdoor Unit
1.3
(Front view)
(Top view)
NetCol500-A018
NetCol500-A020
Unit: mm
2
Materials
Delivered
Materials
Hose clamps, cable ties, humidifier water inlet pipe (optional with humidifier), guide
rails, drainpipe connector, OT terminals, cord end terminals
Engineering
Procurement
Refrigerant
pipe
Liquid pipe: Copper pipe with an outer diameter of 3/8 inch (9.52 mm),
pipe wall thickness of 0.75 mm, and operating pressure of greater than
or equal to 4.5 MPa
Gas pipe: Copper pipe with an outer diameter of 5/8 inch (15.88 mm),
pipe wall thickness of 1.0 mm, and operating pressure of greater than
or equal to 4.5 MPa
Thermal insulation foam: thickness ≥ 13 mm
Refrigerant pipe support (see page 4)
Oil trap (see page 4)