Maintenance
Area
Maintenance
Item
Operation
Expected Result Troubleshootin
g
Indicator
-
The indicator on
the power
module is steady
green.
Check the
output voltage
and determine
whether the
power module
is faulty. If the
power module
is faulty, replace
it.
Fan
-
No abnormal
noise is
generated.
If abnormal
noise is
generated, clean
the fan.
Operating
environment
-
● Ambient
temperature:
–20°C to
+65°C
● Humidity:
0%–95% RH
(non-
condensing)
If the
temperature or
humidity is
abnormal, check
the smart
cooling product
status.
Monitoring
module indicator
-
The monitoring
module indicator
is steady green
or blinking
green.
If the indicator
is off or any
abnormal
condition
occurs, see
to rectify the
fault.
Network interface
indicator
-
The green
indicator is
steady on, and
the yellow
indicator is
blinking.
If the indicator
status is
abnormal, check
the network
cable
connection.