FusionModule2000 Smart Modular Data Center
Product Description
5 Power Supply and Distribution System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
13
Figure 5-4
Layout of smart module A (batteries deployed outside the module, 2N scenario)
Table 5-1
Power distribution specifications
Item
Specifications
Integrated
UPS(50kVA,125kVA)
25 kW power modules are configured: 48 routes for IT
power distribution and 8 routes for smart cooling
product power distribution
The 50 k VA and 125 k VA racks respectively provide
the single-route MCCB and dual-route ATS input.
Supports maximum 50 kW or 125 kW IT loads.
Supports maximum (2+1) or (5+1) 25 kW modules.
Integrated
UPS(60kVA,125kVA)
30 kW power modules are configured: 48 routes for IT
power distribution and 8 routes for smart cooling
product power distribution
The 60 k VA and 125 k VA racks respectively provide
the single-route MCCB and dual-route ATS input.
Supports maximum 60 kW or 125 kW IT loads.
Supports maximum (2+1) 30 kW modules or (5+1) 25
kW modules.
Smart Module B
For smart module B, the UPS is deployed outside the module. Power supply and distribution
supports the integrated PDF, precision PDF, and new main way (NMW).