7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
115
The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism.
The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.
7.3.4 Physical Ports
shows the physical ports on the NetCol5000-A in-row smart cooling product.
Table 7-12
Physical port description
Item
Specifications
Refrigerant liquid pipe
Copper pipe; outer diameter: 5/8 in.; pressure resistance ≥ 4.5
MPa; welded
Refrigerant gas pipe
Copper pipe; outer diameter: 3/4 in.; pressure resistance ≥ 4.5
MPa; welded
Humidifier water inlet
pipe
Reserved port: BSPP 1/2 in.; thread connection
Top drainpipe
Reserved port: BSPP 1/2 in.; thread connection
Bottom drainpipe
Reserved port: copper pipe with an outer diameter of 5/8 in.;
you are advised to use a hose with an inner diameter of 14 mm
for connection.
7.3.5 Technical Specifications
respectively show the main technical specifications of the
NetCol5000-A in-row smart cooling product.
Table 7-13
General specifications
Item
Specifications
Cooling mode
Air cooled
Refrigerant
R410A
Cooling capacity
35 kW
Air volume
6000 m
3
/h
Air supply mode
Horizontal air supply
Certification
REACH, RoHS, CE, WEEE, China Energy Conservation
Certification, and IEC
Cooling capacity test conditions: dry bulb temperature at air return vent: 37°C; relative