FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
129
7.5.2 Technical Specifications
Figure 7-15
Dimensions of the NetCol500 outdoor unit
Table 7-23
Technical specifications of the NetCol500 outdoor unit 1
Product
Model
NetCol500-A0
26SC11E0
NetCol500-A0
265S11E0
NetCol500-A0
365C11E0/Net
Col500-A0365
S11E0
NetCol500-A0
725C11E0
Power system 220–240 V AC,
L/N/PE, 50 Hz
380–480 V AC, 3 Ph/N/PE, 50 Hz/60 Hz (for a unit
with a low-temperature component, the power system
is 380–415 V AC, 3 Ph/N/PE, 50 Hz/60 Hz)
Voltage
tolerance
Rated voltage ±10%
b
Frequency
tolerance
Rated frequency ±3 Hz
Maximum
outdoor unit
current (A)
3.3
2.5
2.5
4.5
Air volume
of fans (m
3
/h)
8000
12000
12000
26000
Number of
fans
1
1
1
2
Liquid pipe
outer
diameter
5/8 in. (15.88
mm)
5/8 in. (15.88
mm)
5/8 in. (15.88
mm)
5/8 in. (15.88
mm)
Gas pipe
outer
3/4 in. (19.05
mm)
3/4 in. (19.05
mm)
7/8 in. (22.22
mm)
7/8 in. (22.22
mm)