background image

FusionModule2000 Smart Modular Data Center 
Product Description 

8 Intelligent Module Management System 

 

Issue 06 (2020-05-21) 

Copyright © Huawei Technologies Co., Ltd. 

172 

 

Figure 8-29

 

Multi-functional sensor 

 

(1) Address DIP switch 

(2) BLINK button 

(3) TEST button 

(4) RF_Z indicator 

(5) RUN indicator 

(6) ALM indicator 

 

Specifications 

Table 8-38

 

Multi-functional sensor technical specifications 

Item 

Specifications 

Temperature 
monitoring 

–40°C to 70°C. Precision ≤ ±0.5 °C (0-50 °C). 

Humidity 
monitoring 

0 to 100% RH. Precision ≤ ±5% RH (25°C, 20%–80% RH). 

Smoke 
monitoring 

Complies with Ul217. The smoke sensor generates an alarm when 
testing 3.2% weak dust for each foot. 

POE port 

One POE port that complies with IEEE802.3 at. 

RS485 port 

Reserves one RS485 port. 

DI input 

One DI input port, 12 V DC power input. 

BLINK button 

Wireless communication: 

 

If the sensor is not connected to the network, after you hold down 
the button for 2s to 3s, the sensor connects to the network in RF_Z 
mode. 

 

If the sensor is connected to network, after you hold down the button 
for 2s to 3s, the RUN indicator blinks. 

 

Hold down the button for more than 6s to clear network parameters. 

Test button 

Supports the smoke sensor test. 

Содержание FusionModule2000 V500R003C10

Страница 1: ...FusionModule2000 Smart Modular Data Center V500R003C10 Product Description Issue 06 Date 2020 05 21 HUAWEI TECHNOLOGIES CO LTD ...

Страница 2: ...tomer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to c...

Страница 3: ...s The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoided will result in death or serious injury Indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury Indicates a hazard with a low level of risk which if not avoided could result in minor or modera...

Страница 4: ...ontains all updates made in previous issues Issue 06 2020 05 21 Added section Integrated UPS 60 kVA 125 kVA Added section NetCol5000 A035 Smart Cooling Product Updated section Server Issue 05 2020 01 21 Updated the UIM20A expansion Module Issue 04 2019 12 04 Updated the USB description Issue 03 2019 11 05 Updated section Optional eLight Issue 02 2019 08 30 Updated the server model Issue 01 2019 06...

Страница 5: ... 1 Power Supply and Distribution System for Smart Module A 16 5 1 2 Power Supply and Distribution System for Smart Module B 19 5 2 System Hardware 25 5 2 1 Integrated UPS 50 kVA 125 kVA 25 5 2 1 1 Product Structure 25 5 2 1 2 Power Module 29 5 2 1 3 Bypass Module 30 5 2 1 4 Control Module 31 5 2 1 4 1 Overview 31 5 2 1 4 2 ECM 31 5 2 1 4 3 Dry Contact Card 33 5 2 1 4 4 Monitoring Interface Card 34...

Страница 6: ...ccessories 79 6 1 1 Network Cabinet 79 6 1 2 IT Cabinet 80 6 1 3 Top Sealing Plate 82 6 1 4 Cabinet Bottom Sealing Plate 83 6 1 5 Cabinet Enclosure Plate 84 6 1 6 Cable Management Devices 85 6 1 7 Optional Adjustable Base 88 6 2 Aisle and Mechanical Parts 89 6 2 1 Skylight 89 6 2 2 Aisle End Door 91 6 2 2 1 Sliding Door 91 6 2 2 2 Revolving Door 91 6 2 2 3 Electric Sliding Door 93 6 2 3 M shaped C...

Страница 7: ...l Specifications 125 7 5 NetCol500 Outdoor Unit 126 7 5 1 Product Composition 127 7 5 2 Technical Specifications 129 7 5 3 Optional Low Temperature Component 131 7 5 4 Optional Sunshade 133 7 6 Water Cooling Module 134 8 Intelligent Module Management System 136 8 1 System Overview 136 8 2 System Functions 137 8 2 1 Monitoring 137 8 2 2 App View 137 8 2 3 Alarm 143 8 2 4 History Query 143 8 2 5 Lin...

Страница 8: ... with a Keypad 179 8 3 8 4 Fingerprint and Card Reader 180 8 3 8 5 Card Reader with a Keypad 182 8 3 8 6 Magnetic Lock 183 8 3 8 7 Optional Cabinet Access Control System 184 8 3 9 Video Surveillance System 185 8 3 9 1 IP Camera 185 8 3 9 2 VCN510 187 8 3 9 3 VCN520 188 8 3 9 4 VCN540 189 8 3 10 Lighting System 190 8 3 10 1 AC Actuator 191 8 3 10 2 Aisle Light 600 mm long 193 8 3 11 Optional eLight...

Страница 9: ...ment Furthermore the Huawei smart module uses the i3 intelligent management system to comprehensively improve the reliability and energy efficiency of power supply and cooling systems The management system significantly improves operation and maintenance O M efficiency by alarm convergence and locating automatic fault isolation and automated asset management The FusionModule2000 uses an air cooled...

Страница 10: ...pment room and improve the security of the equipment room The intelligent lighting system helps save energy When a person comes into the aisle lights turn on automatically when the person leaves the aisle the lights turn off automatically i3 Intelligent Management iPower The entire link status of the power supply and distribution system is displayed in real time and alarms are intelligently conver...

Страница 11: ...tarts after power failure recovery and this effectively prevents a sharp increase in the aisle temperature due to the long restart time of the smart cooling product Innovative intelligent refrigerant leakage detection prevents cooling capacity decrease or smart cooling product breakdown iManage Room level 3D visualized management and precise alarm locating considerably improve O M efficiency Aisle...

Страница 12: ...awei Technologies Co Ltd 4 3 Product Description 3 1 Solution Overview Smart module structures can be classified into the single row 1200 mm wide aisle containment and dual row 1200 mm wide aisle containment Table 3 1 Smart module structures Scenario Illustration Single row aisle containment Dual row aisle containment ...

Страница 13: ... overhead piping With a raised floor NOTE Typically overhead cabling and underfloor over head piping bottom cabling and underfloor over head piping 3 2 Single Row 1200 mm Wide Aisle Containment The single row 1200 mm wide aisle containment can be a cold or hot aisle containment that involves the following components IT cabinet network cabinet PDF smart cooling product battery cabinet skylight end ...

Страница 14: ...2 Control skylight 3 Flat or rotating skylight 4 Alarm beacon 5 Cable trough 6 Access control device 7 PAD 8 Cabinet 3 3 Dual Row 1200 mm Wide Aisle Containment The dual row 1200 mm wide aisle containment can be a cold or hot aisle containment that involves the following components IT cabinet network cabinet PDF smart cooling product battery cabinet skylight end door and cable trough A cold aisle ...

Страница 15: ... Description Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 7 Figure 3 2 Components of the dual row 1200 mm wide cold aisle containment 1 End door 2 Control skylight 3 Flat or rotating skylight 4 Alarm beacon 5 Cable trough 6 Access control device 7 PAD 8 Cabinet ...

Страница 16: ...nd mechanical parts Smart module A batteries deployed outside the module Integrated UPS smart cooling product cabinet aisle and mechanical parts Battery Smart module B integrated PDF Integrated power distribution frame PDF smart cooling product cabinet aisle and mechanical parts UPS and battery Smart module B precision PDF Precision PDF smart cooling product cabinet aisle and mechanical parts UPS ...

Страница 17: ...020 05 21 Copyright Huawei Technologies Co Ltd 9 Table 4 2 Scenario illustrations Smart Module Scenario Illustration Smart module A batteries deployed inside the module Smart module A batteries deployed outside the module Smart module B integrated PDF Smart module B precision PDF Smart module B NMW ...

Страница 18: ...e 06 2020 05 21 Copyright Huawei Technologies Co Ltd 10 Devices inside and outside the smart module can be deployed in one room or two rooms If deployed in one room the smart module adopts the hot aisle containment design to ensure that the ambient temperature for batteries meets requirements ...

Страница 19: ...istribution System 5 1 System Overview Smart modules are classified into smart module A and smart module B by different power supply and distribution systems Smart Module A For smart module A the integrated UPS is deployed inside the module and batteries can be deployed inside or outside the module Figure 5 1 Layout of smart moduleA batteries deployed inside the module N 1 scenario ...

Страница 20: ...Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 12 Figure 5 2 Layout of smart moduleA batteries deployed inside the module 2N scenario Figure 5 3 Layout of smart moduleA batteries deployed outside the module N 1 scenario ...

Страница 21: ...125 k VA racks respectively provide the single route MCCB and dual route ATS input Supports maximum 50 kW or 125 kW IT loads Supports maximum 2 1 or 5 1 25 kW modules Integrated UPS 60kVA 125kVA 30 kW power modules are configured 48 routes for IT power distribution and 8 routes for smart cooling product power distribution The 60 k VA and 125 k VA racks respectively provide the single route MCCB an...

Страница 22: ...ption 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 14 Figure 5 5 Layout of smart module B integrated PDF precision PDF N 1 scenario Figure 5 6 Layout of smart module B integrated PDF precision PDF 2N scenario ...

Страница 23: ...ifications Item Specifications Integrated PDF 160 A 250 A power input IT input circuit breaker and smart cooling product input circuit breaker 48 routes for IT power distribution 8 routes for smart cooling product power distribution and 1 route for lighting power distribution supports 95 kW 148 5 kW IT loads Precision PDF 160 A 250 A 400 A power input supports maximum 144 routes for IT power distr...

Страница 24: ...es Co Ltd 16 5 1 1 Power Supply and Distribution System for Smart Module A For smart module A the power supply and distribution system diagrams are the same regardless of whether battery cabinets are deployed inside or outside the module N 1 Power Supply and Distribution System Diagram Figure 5 9 N 1 power supply and distribution system diagram ATS ...

Страница 25: ...000 Smart Modular Data Center Product Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 17 Figure 5 10 N 1 power supply and distribution system diagram MCCB ...

Страница 26: ...a Center Product Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 18 2N Power Supply and Distribution System Diagram Figure 5 11 2N power supply and distribution system diagram ...

Страница 27: ...pply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 19 5 1 2 Power Supply and Distribution System for Smart Module B N 1 Power Supply and Distribution System Diagram Figure 5 12 N 1 power supply and distribution system diagram integrated PDF ...

Страница 28: ...Smart Modular Data Center Product Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 20 Figure 5 13 N 1 power supply and distribution system diagram precision PDF ...

Страница 29: ...Smart Modular Data Center Product Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 21 Figure 5 14 N 1 power supply and distribution system diagram new main way ...

Страница 30: ...duct Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 22 2N Power Supply and Distribution System Diagram Figure 5 15 2N isolation power supply and distribution system diagram integrated PDF ...

Страница 31: ...Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 23 Figure 5 16 2N non isolation power supply and distribution system diagram 1 integrated PDF Figure 5 17 2N non isolation power supply and distribution system diagram 2 integrated PDF ...

Страница 32: ...Smart Modular Data Center Product Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 24 Figure 5 18 2N power supply and distribution system diagram precision PDF ...

Страница 33: ... 2 1 Integrated UPS 50 kVA 125 kVA 5 2 1 1 Product Structure The appearance of the UPS5000 E 125K HABBS 02311FTD 002 02311FTD 007 is similar to that of the UPS5000 E 50K HABBS 02311FTB 001 02311FTB 009 The appearance of the UPS5000 E 125K HASBS 02311FTE 002 is similar to that of the UPS5000 E 50K HASBS 02311FTC 001 The appearance of the UPS5000 E 125K HASBS 02311FTE 004 02311FTE 006 is similar to ...

Страница 34: ...t view 1 Power input status indicator 2 Input circuit breaker 3 Lighting circuit breaker 4 Power distribution circuit breaker for the smart cooling product 5 IT load circuit breaker 6 UPS input circuit breaker 7 UPS maintenance bypass circuit breaker 8 Control module 9 Bypass module 10 Filler panel 11 Power module 12 Monitor display unit MDU 13 Power distribution monitoring board 14 UPS output cir...

Страница 35: ...ont view 1 Power input status indicator 2 ATS 3 Lighting circuit breaker 4 ATS handle installation slot 5 Power distribution circuit breaker for the smart cooling product 6 IT load circuit breaker 7 UPS input circuit breaker 8 UPS maintenance bypass circuit breaker 9 Control module 10 Bypass module 11 Power module 12 Monitor display unit MDU 13 Power distribution monitoring board 14 UPS output cir...

Страница 36: ... status indicator 2 ATS drive module 3 ATS monitoring module 4 Lighting circuit breaker 5 Power distribution circuit breaker for the smart cooling product 6 IT load circuit breaker 7 UPS input circuit breaker 8 UPS maintenance bypass circuit breaker 9 Control module 10 Bypass module 11 Power module 12 ATS transfer switch 13 ATS handle 14 Monitor display unit MDU 15 Power distribution monitoring bo...

Страница 37: ... 3 Alarm indicator 4 Fault indicator 5 Ready switch 6 Output port 7 Input port Functions The power module consists of a PFC rectifier and inverter The power module performs AC DC or DC DC conversion on the mains and battery inputs and stabilizes the bus voltage The inverter converts DC inputs into AC sine wave outputs Specifications Dimensions H x W x D 86 mm x 442 mm x 620 mm Weight 21 kg Rated o...

Страница 38: ...Figure 5 24 Bypass module 1 Positioning lock 2 Battery cold start button 3 Run indicator 4 Alarm indicator 5 Fault indicator 6 Ready switch 7 Signal port 8 Input and output ports Functions The UPS is set to ECO mode and the bypass voltage is within the specified range The power module is overloaded for a period longer than the maximum allowed period Both the active and standby ECMs are abnormal ...

Страница 39: ...swappable One subrack is reserved above the dry contact card A backfeed protection card or dry contact extended card can be inserted into this subrack Figure 5 25 Signal panel on the control module 1 Ground terminal 2 Parallel port 1 3 BSC port 1 4 Ready switch on ECM 1 5 Indicators for ECM 1 6 Parallel port 2 7 BSC port 2 8 Ready switch on ECM 2 9 Indicators for ECM 2 10 Dry contact card 11 Dry c...

Страница 40: ...each other BSC cables are hot swappable Table 5 4 Indicator description Indicator Color Status Description NORMAL Green Steady on This ECM is the active ECM Blinking at 0 5 Hz This ECM is the standby ECM and it is ready Off This ECM is not ready or the CPLD of this ECM is being upgraded Blinking at 4 Hz The DSP of the ECM is being upgraded or not configured ALM Yellow Steady on The ECM has a minor...

Страница 41: ...sconnected no battery grounding fault Disconnected 0V Port for signal ground GEN Port for detecting diesel generator D G mode Connected D G mode Disconnected non D G mode Disconnected 0V Port for signal ground BCB_OL Port for detecting the BCB box Grounded BCB box connected Disconnected BCB box not connected Grounded BCB_STA Port for monitoring the battery switch Connected battery switch ON Discon...

Страница 42: ...onnected SWITCH STATUS_ 0V Port for signal ground SWITCH STATUS_ BP Port for monitoring the bypass input circuit breaker Connected circuit breaker ON Disconnected circuit breaker OFF Connected SWITCH STATUS_ 0V Port for signal ground SPD Port for monitoring the input AC surge protective device SPD Connected SPD enabled Disconnected SPD disabled Connected 0V Port for signal ground The dry contact i...

Страница 43: ...nclude the ambient temperature and humidity sensor port FE port battery temperature monitoring port and network management port MDU functions include monitoring of the UPS allowing users to set parameters command delivery information reports and UPS key information and parameters displayed on the LCD Figure 5 28 Monitoring interface card The maximum voltage and current of ports DO_1 to DO_4 are 30...

Страница 44: ...ons port 1 COM1 Supported protocol Modbus RTU Connects to an ambient temperature and humidity sensor over two wires Southbound communications port 2 COM2 Supported protocol Modbus RTU Connects to a southbound device Network port FE Supported protocols Modbus TCP HTTPS and SNMP Connects to the network port on a PC Northbound communications port RS485 Supported protocol Modbus RTU Connects to a nort...

Страница 45: ... 2020 05 21 Copyright Huawei Technologies Co Ltd 37 Figure 5 30 Wiring method 2 Figure 5 31 and Table 5 7 describe the COM1 pin definitions Figure 5 31 COM1 pins Table 5 7 COM1 pin definition Pin Description 1 GND 2 N A 3 RS485 4 RS485 5 N A 6 12V_PORT Figure 5 32 and Table 5 8 describe the COM2 pin definitions ...

Страница 46: ...ribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 38 Figure 5 32 COM2 pins Table 5 8 COM2 pin definition Pin Description 1 RS485 2 RS485 3 N A 4 RS485 5 RS485 6 GND 7 CANH0 8 CANL0 Figure 5 33 and Table 5 9 describe the RS485 pin definitions Figure 5 33 RS485 pins ...

Страница 47: ... N A If cables are prepared onsite follow the three methods below Connect pin 1 and pin 2 Pin 1 connects to RS485 and pin 2 connects to RS485 Connect pin 4 and pin 5 Pin 4 connects to RS485 and pin 5 connects to RS485 Connect pins 1 2 4 and 5 Twist cables to pin 1 and pin 4 into one cable and then connect it to RS485 Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485 5 2 1...

Страница 48: ...cator on the MDU panel is yellow when the bypass supplies power in non ECO mode Figure 5 35 MDU ports Table 5 11 Description of MDU ports No Port Name Description 1 MUS05A DB26 Connects to the MDU and monitoring interface card 2 FE Network port 3 CAN Reserved 4 RS485_1 Reserved 5 USB Host After installing the WiFi module locally connect to the UPS over the Service Expert app Obtain the initial sta...

Страница 49: ...UPS operations parameter setting viewing of running status and alarms and so on Specifications Dimensions H x W x D 175 mm x 264 mm x 40 mm 5 2 1 6 Technical Specification Table 5 12 Physical specifications Item Specifications Cable routing mode Routed in and out from the top Routed in and out from the bottom tail frame configured Protection level IP20 Dimensions H x W x D 2000 mm x 600 mm x 1100 ...

Страница 50: ...Input electrical specifications Item Specifications Input system Three phase four wire and PE Rated input voltage 380 V AC 400 V AC 415 V AC line voltage Input voltage range 80 280 V AC phase voltage At 0 40 C The UPS works at full load when the voltage is 176 280 V AC and is linear derated to 40 load when the voltage is 176 80 V AC Input frequency range 40 70 Hz Input power factor 0 99 full load ...

Страница 51: ...by default 30 44 batteries Table 5 18 Output electrical specifications Item Specifications Output system Three phase four wire and PE Voltage 380 V AC 400 V AC 415 V AC line voltage Output voltage precision 1 balanced load Output power factor 1 Transfer time Uninterruptible transfer 0 ms Interruptible transfer 20 ms Output voltage imbalance Voltage imbalance 3 phase imbalance 120 2 Overload capabi...

Страница 52: ...02312TVW 02312TWB is similar to that of the UPS5000 E 125K HABBS 01 02312TVY 02312TWC The appearance of the UPS5000 E 60K HASBS 02312TVX is similar to that of the UPS5000 E 125K HASBS 01 02312TWA Figure 5 36 UPS5000 E 60K HABBS 02312TVW front view 1 Power input status indicator 2 Input circuit breaker 3 Lighting circuit breaker 4 Power distribution circuit breaker for the smart cooling product 5 I...

Страница 53: ... circuit breaker Figure 5 37 UPS5000 E 125K HASBS 01 02312TWA front view 1 Power input status indicator 2 ATS 3 Lighting circuit breaker 4 ATS handle installation slot 5 Power distribution circuit breaker for the smart cooling product 6 IT load circuit breaker 7 UPS input circuit breaker 8 UPS maintenance bypass circuit breaker 9 Control module 10 Bypass module 11 Power module 12 Monitor display u...

Страница 54: ... 3 Alarm indicator 4 Fault indicator 5 Ready switch 6 Output port 7 Input port Functions The power module consists of a PFC rectifier and inverter The power module performs AC DC or DC DC conversion on the mains and battery inputs and stabilizes the bus voltage The inverter converts DC inputs into AC sine wave outputs Specifications Dimensions H x W x D 86 mm x 442 mm x 620 mm Weight 21 kg Rated o...

Страница 55: ...dicator 4 Alarm indicator 5 Fault indicator 6 Ready switch 7 Signal port 8 Input and output ports Table 5 20 Indicator description Indicator Color Status Description Run indicator Green Steady on The system is working in bypass mode Blinking at long intervals The bypass has no output blinking at 0 2 Hz on for 2 5s and off for 2 5s Blinking at short intervals The bypass is not configured or the DSP...

Страница 56: ...ses If the UPS is set to ECO mode and the bypass voltage is within the specified range the UPS works in bypass mode If the power module overload times out the UPS transfers to bypass mode Both the active and standby ECMs are abnormal The system fails to run properly and transfers to bypass mode A manual operation is performed to transfer to bypass mode Specifications Dimensions H x W x D 130 mm x ...

Страница 57: ... 12 MDU port 13 RS485 port 14 Fast Ethernet FE port 15 COM2 port 16 COM1 port 17 Battery temperature sensor port 18 Optional card subrack cover Ports are protected by a security mechanism 5 2 2 4 2 ECM The control module consists of two ECMs that work in active standby mode Each card provides two ports that is a BSC port in the upper part and a reserved parallel port in the lower part Figure 5 41 ...

Страница 58: ...Hz The software of the ECM is being upgraded or not configured ALM Yellow Steady on The ECM has a minor alarm but it does not need to be replaced Off The ECM has no minor alarm or the software of the ECM is being upgraded FAULT Red Steady on The ECM has a critical alarm Off The ECM has no critical alarm or the software of the ECM is being upgraded 5 2 2 4 3 Dry Contact Card The dry contact card al...

Страница 59: ...ery switch OFF Disconnected BCB_DR V Controls battery circuit breaker trip When the voltage is 12 V the circuit breaker trips 0 V battery switch not tripped 12 V battery switch tripped 0 V BCB_0V Port for signal ground EPO_NO Emergency power off EPO port If the normally open NO port is connected to the EPO_12V port EPO is triggered Disconnected EPO_12V 12 V EPO_NC EPO port If the normally closed N...

Страница 60: ... NC as required When multiple UPSs are paralleled all dry contact signals to be used need to connect to each UPS Single cables require dual insulated twisted cables If the length of a power cable is within 25 50 m its cross sectional area must be 0 5 mm2 to 1 5 mm2 5 2 2 4 4 Monitoring Interface Card Only once being set will dry contact signals take effect Set unused dry contact signals to the unu...

Страница 61: ...larm Minor alarm Bypass mode Battery mode Low batt volt Low battery SOC Abnormal mains Sys maint breaker enable Sys outp breaker enable Maint breaker closed No power supplied Mains supplies power ECO mode Battery test and Batt Volt Below Thres Configure power segment settings based on backup time COM DO_2 NO COM DO_3 NO COM DO_4 NO COM DB26 MDU Provides FE RS485 I2C and CAN signals Battery tempera...

Страница 62: ...ort RS485 Supported protocol Modbus RTU Signal cables must be double insulated twisted cables If the cable length is 25 50 m the cross sectional area must be 0 5 1 5 mm2 RS485 cables and FE cables must be shielded cables Figure 5 44 and Figure 5 45 are recommended wiring methods for DO ports Figure 5 44 Wiring method 1 Figure 5 45 Wiring method 2 Figure 5 46 and Table 5 25 describe the COM1 pin de...

Страница 63: ...and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 55 Figure 5 46 COM1 pins Table 5 25 COM1 pin definition Pin Description 1 GND 2 N A 3 RS485 4 RS485 5 N A 6 12V_PORT Figure 5 47 and Table 5 26 describe the COM2 pin definitions Figure 5 47 COM2 pins ...

Страница 64: ...ht Huawei Technologies Co Ltd 56 Table 5 26 COM2 pin definition Pin Description 1 RS485 2 RS485 3 N A 4 RS485 5 RS485 6 GND 7 CANH0 8 CANL0 Figure 5 48 and Table 5 27 describe the RS485 pin definitions Figure 5 48 RS485 pins Table 5 27 RS485 pin definition Pin Description 1 RS485_T 2 RS485_T 3 N A 4 RS485_R 5 RS485_R 6 GND 7 N A ...

Страница 65: ... and 5 Twist cables to pin 1 and pin 4 into one cable and then connect it to RS485 Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485 5 2 2 5 MDU Appearance Figure 5 49 MDU 1 Status indicator 2 LCD touchscreen Table 5 28 Status indicator Status Color Meaning On Red A critical alarm has been generated and the buzzer sounds continuously Yellow A minor alarm has been generate...

Страница 66: ...ert app Obtain the initial startup password during deployment View or obtain UPS running information during preventive maintenance NOTE Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module To ensure security remove the WiFi module immediately after use Insert the USB flash drive import and export the configuration file export run logs and upgrade softwar...

Страница 67: ...unication Dry contacts Table 5 31 Environmental specifications Item Specifications Operating temperature 0 C to 40 C Storage temperature 40 C to 70 C Relative humidity 5 95 RH non condensing Altitude 0 1000 m When the altitude is greater than 1000 m and less than 4000 m the rated power should be derated For details see the IEC62040 3 Table 5 32 Safety and EMC Item Specifications Safety compliance ...

Страница 68: ...ull load 0 98 half load THDi 3 linear load maximum 3 5 non linear load maximum 5 Table 5 34 Bypass Input electrical specifications Item Specifications Input system Three phase four wire and PE Rated input voltage 380 V AC 400 V AC 415 V AC line voltage Input frequency range 50 60 Hz 6 Hz adjustable with the tolerance of 0 5 6 Hz 2 Hz by default Table 5 35 Battery specifications Item Specifications...

Страница 69: ...default 44 batteries Float charging voltage 2 23 2 3 V cell 2 25 V cell by default 30 44 batteries The UPS supports the SmartLi For details about related parameters see the SmartLi user manual Table 5 36 Output electrical specifications Item Specifications Output system Three phase four wire and PE Voltage 380 V AC 400 V AC 415 V AC line voltage Output voltage precision 1 balanced load Output powe...

Страница 70: ...se is 150 200 overloaded the bypass can keep working for 5 minutes If the bypass single phase or three phase is more than 200 overloaded the bypass can keep working for 1 minute If the load exceeds 1000 the bypass can keep working for 100 ms Derating coefficient of output circuit breakers 40 A circuit breaker 0 75 63 A circuit breaker 0 7 Table 5 37 System electrical specifications Item Specificat...

Страница 71: ...F Table 5 38 Technical specifications of the integrated PDF Item Specifications Engineering features Dimensions H x W x D mm Basic dimensions 2000 x 600 x 1100 2000 x 600 x 1200 Expanded dimensions 2200 including a top frame x 600 x 1200 Weight kg 350 Enclosure protection level IP20 Cable routing Routed in and out from the top or routed in from the bottom and routed out from the top The 1100 mm de...

Страница 72: ...on input mode One 3 pole 160 A MCCB input One 3 pole 250 A MCCB input Two 3 pole 160 A MCCB inputs Two 3 pole 250 A MCCB inputs Smart cooling product power distribution input mode One 3 pole 160 A MCCB input One 3 pole 250 A MCCB input Two 3 pole 160 A MCCB inputs Two 3 pole 250 A MCCB inputs Output switch standard configuration IT power distribution branch a maximum of 48 branches single phase or...

Страница 73: ...ent frequency active power reactive power electric energy power factor and temperature Communications mode Supports the Modbus TCP protocol and Modbus RTU protocol Optional Branch temperature monitoring Certifications CE CCC Table 5 39 Monitoring specifications Item Specifications Power distribution mains input Phase voltage phase current load rate frequency power factor total active power total e...

Страница 74: ...DF Figure 5 52 Precision PDF Table 5 40 Precision PDF technical specifications Item Specifications Dimensions H x W x D mm Basic dimensions 2000 x 600 x 1100 2000 x 600 x 1200 Expanded dimensions 2200 including a top frame x 600 x 1200 Weight kg 400 Rated operating voltage V 380 400 415 Rated insulation voltage V 690 Rated frequency Hz 50 60 Rated operating current A 400 250 160 ...

Страница 75: ...m the top or bottom Certifications CCC CE Environmental friendliness RoHS REACH Table 5 41 Monitoring specifications Item Specifications Power distribution mains input Phase voltage phase current load rate frequency power factor total active power total electric energy total apparent power total reactive power busbar temperature circuit breaker status and surge protection status Power distribution...

Страница 76: ... supports maintenance inside the aisle Easy installation short time to install the new main way Intelligent monitoring and flexible management Easy to network through an FE port to implement teleindication telemetering and teleadjusting Flexible to manage and monitor the power usage effectiveness PUE and maintenance Table 5 43 Technical specifications Item Specifications System type Three phase fo...

Страница 77: ... General Input Unit The general input unit is classified into two types left installed general input unit and right installed general input unit When the personnel are close to the cable tray and face the aisle the left cabinets use the left installed general input unit and the right cabinets use the right installed general input unit Left installed general input unit Cables are routed in from the...

Страница 78: ... port 7 AIDI_2 port Table 5 45 Indicator description Indicator Color Status Description RUN Green Blinking at 0 5 Hz on for 1s and then off for 1s The equipment is running properly ALM Red Steady on There is an alarm Off There is no alarm Blinking at 0 5 Hz on for 1s and then off for 1s The ALM indicator blinks PWR Green Steady on The power supply to the CPU of the monitoring board is normal Off T...

Страница 79: ...d 71 Figure 5 56 Integrated management card 1 PWR indicator 2 PoE port 3 48 V output port Figure 5 57 Port pins Table 5 46 Pin definitions Pin RS485 Port FE Port AIDI Port PoE Port 1 RS485 TRX0 TRX0 _RTN 2 RS485 TRX0 TRX0 _RTN 3 TRX1 GND TRX1 _ 48V 4 RS485 TRX2 TRX2 _RTN 5 RS485 TRX2 TRX2 _RTN 6 TRX1 GND TRX1 _ 48V 7 TRX3 AIDI_1 TRX3 _ 48V 8 TRX3 TRX3 _ 48V ...

Страница 80: ... Unit Figure 5 58 Power distribution unit 1 Load wiring port 2 PWR_1 port 3 FE1 port 4 Monitoring panel 5 Integrated management card 6 FE2 port 7 PWR_2 port 8 Output circuit breaker behind the cover 5 2 6 Smart Cooling Product PDB The smart cooling product PDB supplies power to smart cooling products and aisle lighting in precision PDF or new main way NMW scenarios Figure 5 59 Appearance ...

Страница 81: ... up to four battery cabinets in 2N scenario can be deployed inside the smart module If many batteries are configured they can be deployed outside the smart module If the configured batteries can be placed in four or fewer battery cabinets it is recommended that battery cabinets be deployed inside the smart module smart module A Battery cabinets or racks can also be deployed with UPS batteries outs...

Страница 82: ... Description 5 Power Supply and Distribution System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 74 Figure 5 60 Battery cabinet Figure 5 61 Battery cabinet components 1 BIB battery control I O board 2 iBOX CIM 3 Batteries 4 Circuit breaker ...

Страница 83: ...05 Material High intensity class A carbon cold rolled steel plate and zinc coated steel plate Air channel Front and rear air channels Installation space 42 U Installation mode Installed on a concrete floor or ESD floor Door opening mode The front door is a single door and the rear door is a double one Weight 128 kg excluding batteries Protection level IP20 Shoto and Enersys batteries are supported...

Страница 84: ...ery cabinet and auxiliary battery cabinet are differentiated Battery Specifications Layer from Top to Bottom Main Battery Cabinet Number of Batteries Auxiliary Battery Cabinet Number of Batteries 20 19 18 17 16 20 19 18 17 16 65 Ah 100 Ah Layer 1 5 4 3 2 1 5 4 3 2 1 Layer 2 5 5 5 5 5 5 5 5 5 5 Layer 3 5 5 5 5 5 5 5 5 5 5 Layer 4 5 5 5 5 5 5 5 5 5 5 5 2 8 rPDU Introduction 5 2 8 1 rPDU The rPDU use...

Страница 85: ...g monitoring functions Detect and display the input current Detect and display the total input current Detect and display the input voltage display the voltage and current alternately Provide remote input management Remotely query the input voltage total input current input power and input energy through a serial port Remotely query the PDU status through a serial port The status that can be queri...

Страница 86: ...l connector 3 Main control module 4 Output sockets 5 Hydraulic circuit breaker Table 5 53 Technical specifications of the smart rPDU Item Specifications Function Supports single phase AC 200 240 V power supply twenty 10 A outputs four 16 A outputs Dimensions H x W x D 1866 mm x 60 mm x 48 mm appearance 1 1866 mm x 56 mm x 52 mm appearance 2 Output quantity and system 20 x C13 4 x C19 Monitoring fu...

Страница 87: ...tem Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 79 6 Cabinet Aisle System 6 1 Cabinets and Accessories 6 1 1 Network Cabinet The network cabinet provides the smart module with the space for integrated cabling and the cable management interface Figure 6 1 Network cabinet ...

Страница 88: ...cabinet provides 47 U available space The distance between the front and rear mounting bars can be adjusted by the step of 25 mm Positions behind the cabinet are reserved for installing two rPDUs Installation mode Installed on a concrete floor a base or an ESD floor Door opening mode The front door is a single door and the rear door is a double one Weight of an empty cabinet The weight of an empty...

Страница 89: ...g bars The front and rear doors are locked and can be unlocked only with dedicated keys The cabinet supports a door status sensor and electronic access control The maximum static load of the cabinet is 1800 kg Table 6 2 Cabinet technical specifications Item Technical Specifications External dimensions H x W x D 2000 mm x 600 mm x 1100 mm with castors 2000 mm x 600 mm x 1200 mm with castors 2000 mm...

Страница 90: ...Positions for vertically installing two rPDUs are provided in the rear of the cabinet Installation mode Installed on a concrete floor a base or an ESD floor Door opening mode The front door is a single door and the rear door is a double one Weight of an empty cabinet The weight of an empty cabinet includes the weight of the front and rear doors 2000 mm x 600 mm x 1200 mm 128 kg 2000 mm x 800 mm x ...

Страница 91: ...lates Apply to 300 mm wide smart cooling products 600 mm wide front and rear sealing plates Apply to cabinets that are 600 mm wide and 2000 mm high 800 mm wide front and rear sealing plates Apply to cabinets that are 800 mm wide and 2000 mm high End cabinet Bottom sealing plate assembly Front and rear sealing plates side sealing plate assembled by five components Apply to end cabinets that are 200...

Страница 92: ...Figure 6 4 Bottom sealing plate assembly 1 Side sealing plate 2 Front or rear sealing plate Figure 6 5 600 mm 800 mm wide bottom sealing plate Figure 6 6 300 mm wide bottom sealing plate 6 1 5 Cabinet Enclosure Plate Enclosure plates are used for sealing an aisle They can be 300 mm 600 mm and 800 mm wide and apply only to a single row of cabinets ...

Страница 93: ... 1 6 Cable Management Devices Cables inside cabinets are sorted by cable managers cable rings and cable trays Cable managers route cables horizontally cable rings on the cabinet side route cables vertically and cable trays route cables from the cabinet front to cabinet rear Cable Manager A cable manager is used to manage cables inside a cabinet horizontally Figure 6 8 Cable manager ...

Страница 94: ...482 6 mm x 91 mm 0 56 kg 1 U Cable Ring A cable ring is installed on a side post in the cabinet to secure vertically routed cables Figure 6 9 Cable ring Table 6 5 Cable ring specifications Name Dimensions H x W x D Weight Standard cable ring 55 mm x 48 mm x 188 6 mm 0 163 kg Small cable ring 55 mm x 48 mm x 44 mm 0 096 kg Cable Tray A cable tray is used for forward and backward cabling It uses mou...

Страница 95: ...Product Description 6 Cabinet Aisle System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 87 Figure 6 10 Cable tray Table 6 6 Cable tray specifications Dimensions H x W x D Weight Space Occupied 43 6 mm x 482 6 mm x 250 mm 1 89 kg 1 U ...

Страница 96: ...on positions for cable management devices 1 Cable rack 2 Cable ring 3 Cable tray The installation positions for cable management devices are for reference only Determine the installation positions based on the actual situation 6 1 7 Optional Adjustable Base An adjustable base for the smart module can be 300 mm 600 mm or 800 mm wide The minimum adjustment range is 1 mm ...

Страница 97: ...stable 1000 mm 1100 mm or 1200 mm 800 mm wide IT or network cabinet base Height adjustable 270 mm H 410 mm depth adjustable 1000 mm 1100 mm or 1200 mm Height adjustable 410 mm H 700 mm depth adjustable 1000 mm 1100 mm or 1200 mm 6 2 Aisle and Mechanical Parts 6 2 1 Skylight Skylights are used for sealing an aisle containment Skylights are classified as control skylights rotating skylights and flat...

Страница 98: ...ional sensor and smoke detector If the smart module is longer than 7 m add one control skylight in the middle of the smart module for installing a multi functional sensor or smoke detector Figure 6 13 Flat or rotating skylight 1 Magnetic lock fixing base 2 Glass skylight 3 Skylight connective plate A rotating skylight is designed with an eccentric structure When the trigger is activated a rotating...

Страница 99: ...dent improves equipment efficiency and helps onsite personnel or devices move into or out of the aisle containment 6 2 2 1 Sliding Door Figure 6 14 Sliding door Sliding doors can be opened only sideways and therefore may involve risks during fire extinguishing system acceptance 6 2 2 2 Revolving Door The double revolving door is an outward opening door with an opening angle of 90 degrees It ensure...

Страница 100: ...FusionModule2000 Smart Modular Data Center Product Description 6 Cabinet Aisle System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 92 Figure 6 15 Double revolving door ...

Страница 101: ...cable troughs are categorized into signal cable troughs and power cable troughs which are used to route signal cables and power cables respectively This ensures that weak current cables are separated from strong current cables A cable trough consists of several parts that are clamped together A cable trough is assembled using two brackets one supporting plate and one partition plate used to separa...

Страница 102: ... Supporting plate 3 Partition plate 4 Position for the smart ETH gateway 6 2 4 Optional Mesh cable trough Cabinet cable troughs are categorized into signal cable troughs and power cable troughs which are used to route signal cables and power cables respectively This ensures that weak current cables are separated from strong current cables The length of the cable trough needs to be cut based on the...

Страница 103: ...ional Cable Tray Cable trays are used to route cables across two rows of cabinets in the smart module If two rows of cabinets are deployed route strong current and weak current cables over the control skylight at either end of the rows preferentially If there are more than 24 cabinets install one cable tray on the top of end cabinets for routing power cables as there are many cables to be routed A...

Страница 104: ...can have the same length Table 6 9 Adaptive frame specifications Component Width mm Depth mm Height mm Remarks PDF enclosure frame 600 100 2000 Increases the cabinet depth by 100 mm 300 mm wide smart cooling product enclosure frame 300 100 2000 Increases the cabinet depth by 100 mm 600 mm wide smart cooling product enclosure frame 600 100 2000 300 mm wide top frame 300 1200 200 Increases the cabin...

Страница 105: ...Ground copper bars can be horizontal and vertical Vertical ground copper bars are longer than horizontal ones Ground copper bars are used to ground cabinets Ground copper bars are installed in the battery cabinet or IT cabinet closest to the PDF Figure 6 21 Horizontal ground bar Figure 6 22 Vertical ground bar Figure 6 23 Installation position for a horizontal ground copper bar ...

Страница 106: ...nModule2000 Smart Modular Data Center Product Description 6 Cabinet Aisle System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 98 Figure 6 24 Installation positions for vertical ground copper bars ...

Страница 107: ...to high pressure liquid The high pressure liquid passes through the filter and flow regulating mechanism and then is ejected to the evaporator Then the liquid vaporizes at low pressure and absorbs ambient heat The cross flow fan draws air into the fins in the evaporator to exchange heat and discharges cooled air to the cold aisle The indoor air flows cyclically to decrease the temperature In row s...

Страница 108: ... ranging from 20 to 100 to meet partial load requirements Oil separator It is an oil gas separator that separates lubricant from the exhaust of the compressor and brings back the separated lubricant to the compressor EC fan The EC fan implements stepless speed adjustment Heat exchanger The efficient finned evaporator an important part in the cooling system absorbs heat from indoor air to ensure th...

Страница 109: ...fier The electrode or wet film humidifier can be used to precisely control the equipment room humidity Water pump The water pump provides power for top drainage with a maximum lift of 4 meters 7 2 2 Controller 7 2 2 1 Appearance and Ports Appearance The controller provides a 7 inch true color touchscreen and man machine interfaces for query setting monitoring and maintenance The indicator on the p...

Страница 110: ...g is generated Green No buzzing There is an unacknowledged major alarm Yellow Intermittent buzzing There is an unacknowledged critical alarm Red Constant buzzing Ports Figure 7 3 Controller side ports Table 7 2 Ports No Name Note 1 MUS05A Reserved 2 FE fast Ethernet communications port 3 CAN communications port for the main control board and LCD 4 RS485_1 Reserved 5 USB Host After installing the W...

Страница 111: ...y its status Teamwork control Enables multiple smart cooling products to work cooperatively distributes thermal loads in an optimal way to dramatically reduce power consumption and provides multiple standby smart cooling products to improve the reliability The smart cooling product has the following four remote functions Telemetry supply air temperature return air temperature supply air humidity r...

Страница 112: ...rsal serial bus USB port that is protected by a security mechanism 7 2 3 Application Environment Do not install the smart cooling product near a noise sensitive place such as an office or a conference room Table 7 3 Table 7 7 describe the operating environment physical ports installation requirements and water quality requirements of the NetCol5000 A Environmental Specifications Table 7 3 Environm...

Страница 113: ... 878 0 846 0 815 0 784 0 753 Physical Ports Table 7 5 Physical ports Item Specifications Refrigerant liquid pipe Copper pipe with an outer diameter of 5 8 inch 15 88 mm and thickness of 1 0 mm withstanding a pressure not smaller than 4 5 MPa welding Refrigerant gas pipe Copper pipe with an outer diameter of 3 4 inch 19 05 mm and thickness of 1 0 mm withstanding a pressure not smaller than 4 5 MPa ...

Страница 114: ...ermal insulation foam Liquid pipe 16 mm Gas pipe 19 mm Drainage Drainpipes can withstand a high temperature greater than or equal to 85 C for the smart cooling products configured with electrode humidifiers Power supply Leakage switches are not recommended for the main circuit If leakage switches are required by the customer or local regulations use the residual current circuit breaker RCCB that i...

Страница 115: ...20 a 125 1250 µ S cm Inlet water hardness specificationsb 100 mg L a When σ20 is less than 125 µ S cm the first vapor exhausting duration of the humidifier is long when σ20 greater than 1250 µ S cm the humidifier service life is affected b A water softener needs to be installed if the inlet water hardness exceeds 100 mg L CaCO3 7 2 4 Technical Specifications Table 7 8 and Table 7 9 describe the ge...

Страница 116: ...E2 NetCol5 000 A02 5H412D 2E120E1 NetCol5 000 A02 5H412D 20020E0 NetCol5 000 A02 5H40E0 NetCol5 000 A02 5H412D 2E120E0 NetCol5 000 A02 5H4WE2 NetCol5 000 A02 5H4WE0 Power supply mode Dual power supplies Dual power supplies Single power supply Single power supply Dual power supplies Single power supply Maximum current 20 A 30 A 20 A 30 A 30 A 30 A Power system Supports the 380 415 V 3PH N PE 50 Hz ...

Страница 117: ...02 5H4WE0 function 7 3 NetCol5000 A035 Smart Cooling Product This section describes the components operating environment and technical specifications of the NetCol5000 A035 In row Air Cooled Smart Cooling Product 35 kW smart cooling product for short 7 3 1 Indoor Unit 7 3 1 1 Appearance Figure 7 4 shows the indoor unit of a NetCol5000 A in row smart cooling product Figure 7 4 Appearance Table 7 10...

Страница 118: ...tch 7 Compressor 8 Drainpipe 9 Refrigerant gas pipe 10 Refrigerant liquid pipe 11 Air filter 12 Fan 13 Water pan cover 14 Water pump Compressor The NetCol5000 A uses a variable frequency compressor that features a compact size light weight long service life low noise easy installation as well as high reliability stability and energy efficiency Oil separator It is an oil gas separator which separat...

Страница 119: ...igerant pipes and filters out foreign matter which reduces the component damage probability and improves operating efficiency and reliability of components Sight glass The sight glass allows you to observe the refrigerant flow and the content of gas and liquid for easy maintenance and optimization Electric heater It has multiple protection mechanisms to ensure the secure and stable running of the ...

Страница 120: ...t and surface phosphatization powder coating techniques the outdoor unit adapts to harsh environments with its sound rigidity and anticorrosion performance Pressure preservation is performed on the condenser before delivery and the pipe ports are properly sealed to prevent foreign matter from entry 7 3 3 Controller Appearance The 7 inch display panel with the true color touchscreen provides user i...

Страница 121: ...authorized service engineers are allowed to use the WiFi module To ensure security remove the WiFi module immediately after use Insert the USB flash drive import and export the configuration file export run logs and upgrade software Table 7 11 Indicator and buzzer status description Alarm Status Indicators Buzzer The device is operating properly or a warning alarm occurs Green Silent The buzzer ke...

Страница 122: ...in opposite status such as cooling and heating or humidification and dehumidification in order to save energy You can monitor manage and upgrade one or more smart cooling products using the remote management software provided by Huawei At least 1500 historical alarms can be stored Access logs can be traced back At least 1000 historical login and setting records can be stored The controller can dis...

Страница 123: ...sical port description Item Specifications Refrigerant liquid pipe Copper pipe outer diameter 5 8 in pressure resistance 4 5 MPa welded Refrigerant gas pipe Copper pipe outer diameter 3 4 in pressure resistance 4 5 MPa welded Humidifier water inlet pipe Reserved port BSPP 1 2 in thread connection Top drainpipe Reserved port BSPP 1 2 in thread connection Bottom drainpipe Reserved port copper pipe w...

Страница 124: ... 380 415 V 3PH N PE 50 Hz 60 Hz Voltage If upstream voltage fluctuation exceeds the rated voltage 10 you are advised to add a voltage regulator Otherwise the smart cooling product may generate alarms frequently and fail to work properly Heating Yes No Yes No Humidification Yes No Yes No Pipe routing Bottom pipe routing Top and bottom pipe routing Condensate pump No Yes Water pump lift 4 m a In the...

Страница 125: ...oor unit installation environments are classified as follows based on the harshness Class A controlled environment indoor environments where the ambient temperature and humidity are controlled including rooms where people live Class B uncontrollable environment indoor environments where the ambient temperature and humidity are not controlled or general outdoor environments with simple shielding me...

Страница 126: ...ock 4 Front door 5 Mounting hole 6 Side panel 7 Rear door 8 Anchor Table 7 16 Dimensions Dimensions H x W x D mm Expansion Method Standard dimensions 2000 x 600 x 1200 Expanded dimensions 2200 x 600 x 1200 Install a top frame Components The NetCol5000 A mainly consists of a DC variable frequency compressor EC fan evaporator electronic expansion valve EEV oil separator sight glass filter dryer air ...

Страница 127: ...rential pressure switch Compressor The NetCol5000 A uses a DC variable frequency compressor that features compact size light weight long service life low noise easy installation as well as high reliability stability and energy efficiency The high precision drive automatically adapts to the system pressure fluctuations The drive conducts precision self check Compressor and drive faults can be store...

Страница 128: ...he EEV is equipped with an energy storage unit that prevents slugging due to migration of refrigerant when the smart cooling product is powered off abnormally Oil separator It is an oil gas separator which separates the lubricant brought out due to exhaustion of the compressor and brings back the separated lubricant to the compressor Sight glass It allows you to observe the refrigerant flow and ga...

Страница 129: ...ical ports Table 7 17 Physical ports Item Specifications Indoor unit Refrigerant liquid pipe Outer diameter of 5 8 inch 15 88 mm welding Refrigerant gas pipe Outer diameter of 7 8 inch 22 22 mm welding Humidifier water inlet pipe G 1 2 inch inner screw thread humidifier hose is provided for the smart cooling product G 3 4 inch outer screw thread humidifier hose is not provided for the smart coolin...

Страница 130: ...ply The inlet water pressure should be in the range of 0 1 0 7 MPa A reducing valve must be installed if the inlet water pressure exceeds 0 7 MPa and the temperature should be in the range of 1 C 40 C The water should meet the following requirements Non freezing and nephelometric turbidity units NTU 3 No visible substances 6 5 pH value 8 5 Total hardness in CaCO3 450 mg L Drainage The distance bet...

Страница 131: ...the alarm not confirmed after the alarm generation with the highest severity level Figure 7 11 LCD 1 Indicator 2 USBa Universal Serial Bus reserved 3 12 C 12 V reserved 4 DP display port 5 SW reserved a USB has the following functions After installing the WiFi module locally connect to the smart cooling product over the Service Expert app Obtain the initial startup password during deployment View ...

Страница 132: ... the controller optimally distributes the heat load to reduce power consumption and provides backup to improve reliability When a smart cooling product in the group is faulty the backup smart cooling product starts to operate automatically to improve the reliability of the smart cooling product system Each smart cooling product enters the active mode one by one periodically The number of operating...

Страница 133: ...ays the information of the current fault which facilitates the maintenance The controller provides abundant external ports such as RS485 ports CAN ports FE ports and USB ports that are protected by a security mechanism The smart cooling product supports communications protocols such as Modbus RTU Modbus TCP and SNMP facilitating connection to the network management system The controller intelligen...

Страница 134: ...ply Pipe routing Top and bottom pipe routing Bottom pipe routing Max Current 46 A Condensate pump Yes No Heating function Yes No Yes No Yes No Humidificatio n function Yes No Yes No Yes No Humidifier water inlet hose No No Yes No Yes No Reheating capacity 6kW No 6kW No 6kW No Connection mode of the compressor or filter dryer Welding Thread connection Castor No Yes Humidifying capacity 3kg h No 3kg...

Страница 135: ... Indoor Unit Outdoor Unit Abbreviation 42 kW smart cooling product NetCol500 A0365C11E0 NetCol500 A036 NetCol500 A0365S11E0 NetCol500 A036 NetCol500 A0725C11E0 NetCol500 A072 46 kW smart cooling product NetCol500 A060 NetCol500 A060 NetCol500 A080 NetCol500 A080 NetCol500 A120 NetCol500 A120 7 5 1 Product Composition Appearance Figure 7 12 Appearance 1 ...

Страница 136: ...ture Control System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 128 Figure 7 13 Appearance 2 Components The NetCol500 outdoor unit consists of a condenser electric control box rack and fans Figure 7 14 Components 1 Condenser 2 Electric control box 3 Rack 4 Fans ...

Страница 137: ...0 Net Col500 A0365 S11E0 NetCol500 A0 725C11E0 Power system 220 240 V AC L N PE 50 Hz 380 480 V AC 3 Ph N PE 50 Hz 60 Hz for a unit with a low temperature component the power system is 380 415 V AC 3 Ph N PE 50 Hz 60 Hz Voltage tolerance Rated voltage 10 b Frequency tolerance Rated frequency 3 Hz Maximum outdoor unit current A 3 3 2 5 2 5 4 5 Air volume of fans m3 h 8000 12000 12000 26000 Number o...

Страница 138: ...t user manual Storage temperature C 40 to 70 Storage humidity 5 95 RH non condensing Altitude 0 1000 m normal use above 1000 m derating For derating details see the product overview in the indoor unit user manual b If the upstream voltage may fluctuate outside the voltage tolerance install a voltage stabilizer otherwise the smart cooling product may fail to run properly due to frequent alarms c CE...

Страница 139: ...he coast or outdoor land environments with simple shielding measures within 1 2 km away from a pollution source Class D marine environment environments within 500 m away from the coast The NetCol500 A0365S11E0 NetCol500 A0265S11E0 and NetCol500 A0605S outdoor units must not be installed in class D environments and other outdoor units must not be installed in class C or class D environments 7 5 3 O...

Страница 140: ...Connecting to indoor unit gas pipe A low temperature component is mandatory when the outdoor ambient temperature may drop to 20º C Table 7 25 Low temperature component specifications Item Specifications Heater power supply 220 240 V AC 1 Ph 50 Hz or 60 Hz Heater power supply voltage tolerance Rated voltage 10 Heater power supply frequency tolerance Rated frequency 3 Hz Refrigerant R410A Liquid pip...

Страница 141: ...sure 4 35 MPa 7 5 4 Optional Sunshade When an outdoor unit is used in the T3 working condition 5 C to 55 C install a sunshade if the following three conditions are met The outdoor unit is installed horizontally The ambient temperature exceeds 50 C The outdoor unit is directly exposed to sunlight If the previous three conditions are met but no sunshade is installed the smart cooling product will sh...

Страница 142: ...Composition The NetCol500 water cooling module consists of an electric control box a water valve actuator and a rack The following describes the components and configuration Figure 7 19 Water cooled module components 1 Water valve actuator 2 Water return pipe 3 Water supply pipe 4 Negative temperature coefficient NTC 5 Liquid pipe 6 Electric control box 7 Gas pipe 8 Needle valve 9 Safety valve Fea...

Страница 143: ...o 45 C Humidity range 5 90 RH Storage temperature 40 C to 70 C Storage humidity 5 95 RH non condensing Inlet water temperature range of chilled water 10 C to 37 C Highest operating temperature of the shell pass C 125 Highest operating temperature of the tube pass C 60 IP rating IPX4 Altitude 0 4000 m derated when the altitude is greater than 1000 m Environment Enclosed indoor environment in which ...

Страница 144: ...and humidity sensors water sensors smoke sensors and video surveillance equipment inside the module If a component fault or parameter error is detected alarms are generated in diverse modes such as indicator light email and short message service SMS Historical data and alarm events are recorded and all monitoring information is reported to the management platform The pad app or mobile phone app ca...

Страница 145: ...me alarm signals Smoke monitoring Detects smoke in the smart module and provides real time alarm signals Power distribution monitoring a Detects and collects statistics on the total input phase voltage current frequency power factor electric energy active power apparent power load rate THDv THDi and cabinet interior busbar temperature for the smart module b Detects the current electric energy swit...

Страница 146: ...cally display the power space optional and temperature optional of a single cabinet In addition the resource usage rate of electric energy space and cooling capacity PUE value power consumption ambient temperature and humidity and alarm information of the smart module are displayed on the home screen of the app Figure 8 2 App home screen electric energy Figure 8 3 App home screen temperature ...

Страница 147: ...rPDU are included Users can check the switch status and running status of power supply and distribution devices in a view Figure 8 4 Power supply link view Shows the cooling system of the smart module displays the air inlet temperature air outlet temperature and running parameters of smart cooling products aisle temperature aisle humidity and temperatures optional at the front and rear sides of a ...

Страница 148: ...dule Management System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 140 Figure 8 5 iCooling view Figure 8 6 Running view of a single smart cooling product Displays the resource usage of the electric energy space and cooling capacity of the smart module and each cabinet ...

Страница 149: ...ure 8 7 Power view Displays the real time status and alarms of the aisle temperature and humidity sensor door status sensor water sensor lighting in the plan view Figure 8 8 Environment status view Displays the PUE value of the smart module in a data dashboard allows you to view the historical PUE curve and power consumption of the smart module by day month or year ...

Страница 150: ... on a tablet computer After facial recognition information is added click Facial Enter to start the facial recognition If you do not have facial recognition permission or an error occurs during facial recognition you can use the user name and password login manner After you successfully logs in using facial recognition the system determines whether to open the door based on your access control con...

Страница 151: ...me Performance data statistics You can view historical data of devices to help analyze data or problems Operation log query You can view logs of key operations such as user login parameter modification data export device upgrade and access control events Data export You can export historical data of the ECC800 Pro and certain southbound devices 8 2 5 Linkage Control Supports the linkage logic of a...

Страница 152: ...and one main control module Configuration 2 two power modules and one main control module In configuration 1 install a filler panel in slot 2 In configuration 2 install power modules in slots 1 and 2 Figure 8 11 ECC800 Pro collector in configuration 2 1 Slot 1 power modules 2 Slot 2 power modules 3 Slot 3 main control module Table 8 1 ECC800 Pro environmental specifications Item Specifications Wor...

Страница 153: ...nch cabinet Environmental protection RoHS5 REACH WEEE Figure 8 12 ECC800 Pro rear view 1 53 5V DC_OUT1 2 53 5V DC_OUT2 3 AC_INPUT1 4 AC_INPUT2 Power Ports The ECC800 Pro provides four power ports including two AC input ports AC_INPUT1 and AC_INPUT2 and two DC output ports DC_OUTPUT1 and DC_OUTPUT2 Table 8 3 provides the power port pin definitions Table 8 3 Power port pin definitions Port Type Pin ...

Страница 154: ... 1 USB 2 Status indicator 3 AIDI_1 4 AIDI_2 5 COM1 AIDI_4 6 COM3 12V 7 WAN1 8 LAN1 POE 9 LAN2 POE 10 WAN2 11 COM4 CAN 12 COM2 AIDI_5 13 AIDI_3 14 DO 12V 15 RF_Z 16 WLAN 17 4G 18 SW button Figure 8 14 ECC800 Pro main control module side view 1 SIM card slot 2 Micro SD card slot reserved Specifications Table 8 4 Technical specifications of the ECC800 Pro main control module Item Specifications Power...

Страница 155: ...5 V DC rated voltage 14 5 V DC Supports four RS485 ports with the default communications rate of 9600 bit s COM1 COM3 ports provide 12 V DC power The power supply can be switched on or off and is on by default POE expansion Supports two POE GE ports for expansion of the POE bus and supports network isolation and ring network AIDI expansion RJ45 Output voltage 13 15 V DC rated voltage 14 5 V DC Pro...

Страница 156: ... the site has signal coverage USB Supports USB 2 0 and 5 V 1 A power supply After installing the WiFi module connect the WiFi module to the ECC800 Pro using the app on the mobile phone or tablet computer to view the basic information about the smart module such as layout resources energy efficiency environment and alarms You can insert a USB flash drive to export historical data and configuration ...

Страница 157: ...ides the following communications ports Figure 8 15 shows the pins of the RJ45 port Figure 8 15 RJ45 port pins There are four GE ports that is two WAN ports WAN1 and WAN2 and two LAN ports LAN1 POE and LAN2 POE Table 8 7 GE port pin definitions Item Description Pin sequence Pin 1 GE1 Pin 2 GE1 Pin 3 GE2 Pin 4 GE3 Pin 5 GE3 Pin 6 GE2 Pin 7 GE4 Pin 8 GE4 Indicator Green indicator Linked steady on Ye...

Страница 158: ... Pin 7 DI Pin 8 GND Indicator Green indicator Power output indicator Steady on The 12 V DC output is normal Off No 12 V DC output is provided Table 8 9 COM3 12V port pin definitions Item Description Pin sequence Pin 1 RS485 Pin 2 RS485 Pin 3 12 V DC_OUT Pin 4 RS485 Pin 5 RS485 Pin 6 N A Pin 7 N A Pin 8 GND Indicator Green indicator Power output indicator Steady on The 12 V DC output is normal Off ...

Страница 159: ...Pin 6 and Pin 7 collect sensor data Pin 7 can detect current type sensors 4 20 mA Pin 6 and Pin 7 can detect the output status of passive dry contact type sensors Pin 3 and Pin 7 can detect temperature sensors Table 8 11 AIDI_1 AIDI_2 andAIDI_3 ports pin definitions Item Description Pin sequence Pin 1 Type_1 Pin 2 Type_2 Pin 3 12 V DC Pin 4 Type_3 Pin 5 Type_4 Pin 6 DI Pin 7 DI Pin 8 GND Indicator...

Страница 160: ...n 1 5 V Pin 2 DM Pin 3 DP Pin 4 GND Indicators Table 8 14 Indicators on the ECC800 Pro main control module Indicator Color Name Status Description RUN Green Running status indicator Steady on The power supply is normal the program is being loaded Off The power supply is abnormal Blinking at long intervals The software runs properly the indicator blinks at 0 5 Hz on for 1s and then off for 1s or th...

Страница 161: ...peration Description Indicator Status Wireless network RF_Z 802 15 4 pairing In non wireless network 802 15 4 pairing mode press and hold down the button for 3s to 5s to enter the wireless network pairing mode The RF_Z indicator is blinking at super short intervals In wireless network 802 15 4 pairing mode press and hold down the button for 3s to 5s to exit the pairing mode or the system automatic...

Страница 162: ...he converter application program is being loaded the indicator blinks at 4 Hz on for 0 125s and then off for 0 125s Yellow Alarm indicator Steady on The converter generates a forewarning indicating that power will be limited due to ambient overtemperature or generates a protection shutdown alarm due to ambient overtemperature or undertemperature Power input overvoltage or undervoltage protection R...

Страница 163: ...Color Name Status Description indicator due to output overvoltage The converter delivers no output due to internal faults Off The converter is working properly 8 3 2 UIM20A Expansion Module Figure 8 16 UIM20A expansion module front panel 1 Indicators and button 2 COM1 AI DI_1 COM8 AI DI_8 3 POE Figure 8 17 UIM20A expansion module rear panel 1 DIP switch 2 COM_OUT 3 COM_IN ...

Страница 164: ...ly that is controlled independently The maximum output current is 900 mA when the voltage is 12 V COM1 AIDI_1 and COM2 AIDI_2 form a group COM3 AIDI_3 and COM4 AIDI_4 form a group COM5 AIDI_5 and COM6 AIDI_6 form a group and COM7 AIDI_7 and COM8 AIDI_8 form a group The 12 V DC power supply can be switched on or off and is on by default POE Connects to the ECC800 Pro through the POE port DIP switch...

Страница 165: ...ports COM1 AIDI_1 to COM8 AIDI_8 Table 8 19 Pin assignment for ports COM1 AIDI_1 to COM8 AIDI_8 Item Description Pins Pin1 RS485 Pin2 RS485 Pin3 12V Pin4 RS485 Pin5 RS485 Pin6 D Pin7 D Pin8 GND The following table describes the pin assignments for the COM_IN and COM_OUT ports Table 8 20 Pin assignment for the COM_IN and COM_OUT ports Item Description Pins Pin1 RS485 Pin2 RS485 Pin3 12 V input powe...

Страница 166: ...d or the ECC800 Pro is unsuccessfully registered blinking at short intervals 2 5 Hz on for 0 2s and then off for 0 2s Blinking Blinking at super short intervals for 0 5s and then off for 0 5s last 10s blinking at super short intervals 10 Hz on for 0 05s and then off for 0 05s ALM Steady on A system fault alarm is raised Steady off The system is normal Table 8 22 Blinking description Function Descr...

Страница 167: ... view IPS screen and capacitive five point touch Storage Machine 32 GB Memory 3 GB LPDDR3 extension card microSD a maximum of 256 GB non standard configuration Button Port Touch button power switch and volume button 3 5 mm stereo headphones port Micro SD card port MicroUSB port Camera Rear camera 8 megapixel F2 0 aperture automatic focus Front camera 2 megapixel F2 4 aperture fixed focus Sensor ty...

Страница 168: ...nment unit The rack environment unit collects and controls the environmental data of IT cabinets Figure 8 19 Rack environment unit 1 Ground port 2 48 V DC power input port 3 PoE port 4 COM1 12 V port 5 COM2 12 V port 6 COM3 port 7 COM4 port 8 NTC1 3 ports 9 NTC4 6 ports 10 AI DI_1 port 11 AI DI_2 port 12 12 V_1 port 13 12 V_2 port 14 BLINK button 15 Status indicator Specifications Table 8 25 Techn...

Страница 169: ...t power output AI DI input Two active 12 V DC 200 mA rated AI DI input ports Temperature sensor port Provides two RJ45 ports to connect to six temperature sensors each RJ45 port connecting to three temperature sensors BLINK button Supports the blinking function 8 3 4 2 Smart ETH Gateway A smart ETH gateway allows the extension of the 53 5 V DC power supply and FE communication for the ECC800 Pro a...

Страница 170: ...e communication with the upper computer POE port Four POE ports RJ45 terminal with an indicator 10 100M communications rate complying with IEEE802 3 IEEE802 3u IEEE802 3af at BLINK button If you press the BLINK button the RUN indicator blinks intermittently at super short intervals blinking at super short intervals for 0 5s and then off for 0 5s for 5 seconds Indicators Table 8 27 Indicators on a ...

Страница 171: ...system failure alarm is generated Off No system alarm is generated 8 3 5 WiFi Module The WiFi module provides WiFi signals for equipment such as pads and mobile phones to interact with the host computer Figure 8 21 WiFi module Table 8 28 Technical specifications Item Specifications Wireless standard IEEE 802 11n IEEE 802 11g and IEEE 802 11b Network bandwidth 11n up to 150 Mbps 11g up to 54 Mbps 1...

Страница 172: ... skylight actuator controls the rotating skylight on the aisle containment of the smart module through the alarm linkage information from the fire extinguishing system or the control information from the upper computer The skylight actuator supports E labels and wireless networking 802 15 4 Figure 8 22 Skylight actuator 1 LOCK GND magnetic lock DO output port 2 BUTTON GND window open button DI inp...

Страница 173: ...ocks simultaneously DI input One DI input port for connecting to the window open button BLINK button Hold down the button for less than 1 second to start blinking Hold down the button for 1 5 seconds to search for a network and start networking Hold down the button for more than 10 seconds to clear network parameters Address DIP switch 4 pin address DIP switch E label Supported Indicators Table 8 ...

Страница 174: ...parameters exist or a network is to be created Blinking at long intervals A network is set up and no node access is allowed the indicator blinks at 0 5 Hz on for 1sand then off for 1s Blinking at super short intervals A network is set up and node access is allowed the indicator blinks at 10 Hz on for 0 05s and then off for 0 05s Blinking intermittently at super short intervals The skylight actuato...

Страница 175: ... a water detector and a conversion cable Figure 8 23 WLDS900 water sensor 1 Water detector 2 Conversion cable end A connected to the water detector 3 Conversion cable 4 Conversion cable end B connected to the water detection cable 5 Water detection cable end A connected to the conversion cable 6 Water detection cable Table 8 32 WLDS900 water sensor specifications Item Specification Operating volta...

Страница 176: ...or Figure 8 24 Cabinet temperature sensor Table 8 33 Technical specifications of the cabinet temperature sensor Item Specifications Power 50 mW Single NTC Temperature detection range 10 C to 55 C Temperature detection tolerance 1 C 10 C to 25 C 1 C 25 C to 55 C 0 5 C 25 C Operating temperature 10 C to 55 C Operating humidity 5 95 RH Storage temperature 40 C to 70 C Storage humidity 95 RH non conde...

Страница 177: ... 8 3 7 3 T H Sensor BOM number 02310NBS Figure 8 25 Appearance 1 Status indicator 2 RS485_IN 3 RS485_OUT 4 Address DIP switch The RS485 communications ports of the T H sensor use RJ11 6P6C connectors Figure 8 26 Pins of an RJ11 connector Table 8 34 Pin description of an RJ11 connector Pin Description Pin 1 or Pin 2 GND Pin 3 RS485 Pin 4 RS485 Pin 5 or Pin 6 12V ...

Страница 178: ...pecifications Temperature measuring range 20 C to 70 C Temperature accuracy 1 C Operating temperature 10 C to 55 C Operating voltage 9 16 V DC Storage temperature 40 C to 70 C Output RS485 8 3 7 4 T H Sensor BOM Number 33010516 Figure 8 27 Appearance The T H sensor uses an RJ45 connector Figure 8 28 Pins of an RJ45 connector Table 8 36 Pin description of an RJ45 connector Pin Description Pin1 or P...

Страница 179: ...C to 80 C Temperature accuracy 0 5 C 25 C 1 C full measuring range Operating temperature 20 C to 80 C Operating voltage 9 16 V DC Storage temperature 40 C to 80 C Output RS485 8 3 7 5 Multi Functional Sensor A multi functional sensor integrates the temperature and humidity T H sensor smoke sensor and infrared detection The multi functional sensor can connect to the ECC800 Pro over FE or wireless c...

Страница 180: ...o 100 RH Precision 5 RH 25 C 20 80 RH Smoke monitoring Complies with Ul217 The smoke sensor generates an alarm when testing 3 2 weak dust for each foot POE port One POE port that complies with IEEE802 3 at RS485 port Reserves one RS485 port DI input One DI input port 12 V DC power input BLINK button Wireless communication If the sensor is not connected to the network after you hold down the button...

Страница 181: ...n off for 1s Blinking at short intervals The multi functional sensor fails to register with the ECC800 Pro or the communication fails the indicator blinks at 4 Hz on for 0 125s and then off for 0 125s Blinking The indicator blinks at super short intervals for 0 5s blinking at 10 Hz on for 0 05s and then off for 0 05s and then turns off for 0 5s The cycle lasts for 10s ALM Red Alarm indicator Stead...

Страница 182: ...n a fire occurs or smokes are generated in the micro modular equipment room the alarm beacon generates an audible signal and flashes to inform operators of fire and security risks Figure 8 30 Alarm beacon Table 8 40 Structural specifications of an alarm beacon Item Specifications Dimensions L x W x H 130 mm x 75 mm x 55 mm Installation requirements Installed on a wall Environmental requirements Ro...

Страница 183: ... detecting the card swiping information of the card reader door open button information and fire linkage information It has access right management access event record and alarm record functions Figure 8 31 Access actuator 1 48 V power port 2 POE port 3 RS485 port COM2 4 RS485 port COM1 5 Address DIP switch 6 Status indicator 7 BLINK button 8 WG_2 Wiegand interface 9 WG_1 Wiegand interface 10 AI D...

Страница 184: ...oor status switch RS485 serial port expansion Two RS485 ports one route with the default communications rate of 9600 bit s physical port cascading supported reserved function Wiegand interface Two Wiegand interfaces 12 V DC card reader operating power output two routes of card readers non fingerprint readers can operate at the same time BLINK button Press the button for less than 1 second to start...

Страница 185: ...blinks at 4 Hz on for 0 125s and then off for 0 125s Blinking The indicator blinks at super short intervals for 0 5s blinking at 10 Hz on for 0 05s and then off for 0 05s and then turns off for 0 5s The cycle lasts for 5s ALM Red Alarm indicator Steady on A system failure alarm is generated Off No system alarm is generated RF_Z Green Wireless communication status indicator Steady on No network par...

Страница 186: ...ls The access actuator is searching for a network the indicator blinks at super short intervals for 0 5s and then turns off for 0 5s Communications Ports The access actuator provides one DO port LOCK GND and one DI port GATE COM Table 8 44 lists the LOCK GND GATE COM port pin definitions Table 8 44 LOCK GND GATE COM port pin definitions Item Description LOCK GND control magnetic locks pin sequence...

Страница 187: ...d Item Specifications Dimensions L x W x H 156 mm x 53 mm x 38 mm Rated operating voltage 12 V DC 15 Rated operating current 300 mA 15 Card type supported IC card Authorized storage A maximum of 3000 authorized users with a maximum of 6000 fingerprints Communications mode RS485 and Wiegand communications ports Table 8 46 Access control device operating status Item New Version Standby LED indicator...

Страница 188: ...n white Buzzer sounds The buzzer sounds once Card swiping LED indicator The indicator blinks blue red and blue in order Buzzer sounds The buzzer sounds once 8 3 8 4 Fingerprint and Card Reader Figure 8 33 Fingerprint and card reader 1 Fingerprint reader 2 LED indicator Table 8 47 Fingerprint and card reader Item Specifications Dimensions L x Wx H 156 mm x 53 mm x 38 mm Rated operating voltage 12 V...

Страница 189: ...or is steady blue Fingerprint reader The indicator is off Unauthorized fingerprint collection LED indicator The indicator blinks blue red blue red and blue in order Fingerprint reader The indicator turns on white Buzzer sounds The buzzer sounds three Authorized fingerprint collection LED indicator The indicator blinks blue red and blue in order Fingerprint reader The indicator turns on white Buzze...

Страница 190: ...d reader with a keypad Table 8 49 Specifications of a card reader with a keypad Item Specifications Dimensions L x W x H 114 mm x 63 mm x 25 mm Operating voltage Operating voltage range 10 8 13 2 V DC rated voltage 12 V DC Operating current Static standby current 80 mA dynamic operating current card swiping key pressing 150 mA minimum input current 12 V DC 300 mA Communications mode Wiegand commun...

Страница 191: ...escription 8 Intelligent Module Management System Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 183 8 3 8 6 Magnetic Lock Figure 8 35 Double door magnetic lock Figure 8 36 Single door magnetic lock Figure 8 37 Magnetic lock for a sliding door ...

Страница 192: ...et electronic lock Table 8 50 Cabinet electronic lock specifications Item Specifications Rated input voltage 12 V DC Rated current 200 300 mA Unlock mode Power on to unlock Card type supported IC card Mechanically unlock Supported Features An IC card can be used after being authorized using software An IC card can be authorized for one lock or all locks Door opening information is recorded through...

Страница 193: ... the key The user can set a password A password should only contain three digits If a user forgot the password he can reset it 8 3 9 Video Surveillance System The video surveillance subsystem consists of the cameras and VCN a network video recorder and implements real time monitoring video storage and video playback 8 3 9 1 IP Camera The IPC6325 WD VR IP camera IPC6325 camera for short is a two me...

Страница 194: ...e scan CMOS Lowest illuminance Color 0 01 lux F1 4 AGC ON Black and white 0 004 lux F1 4 AGC ON 0 lux infrared enabled Wide dynamic range 120 dB Focal length 2 8 12 mm manual zoom 4 3x optical zoom Video coding format H 265 H 264 MJPEG Maximum resolution 1920x1080 Power supply PoE 802 3at af 24 V AC 25 24 V DC 25 12 V DC 25 polarity insensitive DC power supply applicable to DC AC adapter and PoE h...

Страница 195: ...ng bandwidth Video playback and download Supports a maximum of eight video playback and download channels or 128 Mbit s video playback and download bandwidth Ingress and egress bandwidth The ingress bandwidth does not exceed 128 Mbit s The egress bandwidth does not exceed 256 Mbit s Table 8 53 Hardware specifications Item Specification Number of disks 2 Whether the hard disk supports hot swap No S...

Страница 196: ...ximum of 32 video access channels or 320 Mbit s video access bandwidth Video forwarding Supports a maximum of 128 video forwarding channels or 320 Mbit s video forwarding bandwidth Video playback and download Supports a maximum of 32 video playback and download channels or 320 Mbit s video playback and download bandwidth Ingress and egress bandwidth The ingress bandwidth does not exceed 320 Mbit s...

Страница 197: ...k ports Power parameters One power module AC power 100 V AC to 240 V AC 50 or 60 Hz Weight in full configuration including disks 10 8 kg Maximum power consumption including hard disks 100 W Dimensions H x W x D 86 1 x 442 x 420 2U excluding panels 86 1 x 442 x 450 2U including panels 8 3 9 4 VCN540 Figure 8 43 Appearance Table 8 56 Performance Specifications Item Specification Device access and vi...

Страница 198: ...d egress bandwidth of the master server do not exceed 256 Mbit s separately Table 8 57 Hardware specifications Item Specification Number of disks 8 Whether the hard disk supports hot swap Yes Supported hard disk type 3 TB 4 TB 6 TB or 8 TB SATA disks CPU type and maximum number of supported CPUs 1 x ARM Cortex A17 Quad core Max 1 4 GHz Memory capacity 2 GB Network port Two GE network ports Power p...

Страница 199: ...formation disabled by default or signals from the light button It also provides a charging port for the pad Figure 8 44 AC actuator 1 AC OUT2 port 2 AC OUT1 port 3 AC IN port 4 Status indicator 5 BLINK button 6 AI DI dry contact 7 COM1 2 RS485 port Specifications Table 8 58 AC actuator technical specifications Item Specifications Power input One AC input 100 240 V AC Power output AC OUT1 two AC ou...

Страница 200: ...teady on The power input is normal Off There is no power input RUN Green Running status indicator Off The power is abnormal or the board program is loading Blinking at long intervals The AC actuator successfully registers with the ECC800 Pro and the software runs properly the indicator blinks at 0 5 Hz on for 1s and then off for 1s Blinking at short intervals The communication is disconnected or t...

Страница 201: ...tly at super short intervals The AC actuator is searching for a network the indicator blinks at super short intervals for 0 5sand then turns off for 0 5s 8 3 10 2 Aisle Light 600 mm long Light emitting diode LED lights are used for lighting in an aisle The lights are installed on the top at the two sides of the aisle Figure 8 45 LED light Table 8 60 LED light technical specifications Item Specific...

Страница 202: ... Huawei Technologies Co Ltd 194 8 3 11 Optional eLight The eLight system consists of the eLight power eLight actuator eLight strip light and cables The eLight strip light is installed in the inverted U shaped light slot in the frame of an automatic sliding door Figure 8 46 Installed eLight strip light Figure 8 47 eLight strip light ...

Страница 203: ... the light is blinking for 3 seconds in red color indicating that the door cannot be opened Associated with the access control for an end door Unassociated alarm severity Blue NOTE When Associated alarm severity in ECC800 Pro WebUI is selected to None Associated alarm severity Mapping between smart module alarm severities and strip light colors Critical alarm red Major alarm orange Minor alarm yel...

Страница 204: ...d voltage of 24 V DC Modbus communications protocol RS485 interface two RJ45 ports Certification CE eLight strip light Rated input voltage 24 V DC Light type RGBW LED strip light in different colors depending on instructions Power RGB fully on under the maximum working condition power P 12 W m Installation mode buckled in a sheet metal light slot Certifications CE and CCC Protection level IP20 Ope...

Страница 205: ...ng Each iBOX can connect to a maximum of eight Hall effect sensors Calculates the SOC and SOH of batteries and battery strings Accurately identifies batteries with lower voltages in a battery string Identifies loose battery terminals and battery terminal overtemperature and controls battery switch tripping Supports WebUI display and northbound communication over FE and RS485 Allows the upstream ma...

Страница 206: ...1 Asset detection strip 2 U space electronic label 3 Main control box Table 8 63 Technical specifications of the smart U space manager Item Specifications Characteristic Applicable to 42 U cabinets Communications port RS485 Modbus RTU Communication Rate 9600 bit s Communication format one start bit eight data bits no parity bit one stop bit Power input 12 V DC 5 RJ45 Rated current and power consum...

Страница 207: ...t comprehensive management functions based on requirements The system can monitor the following equipment Power equipment including in room smart cooling products integrated PDFs UPSs and so on Environment monitoring equipment including water sensor temperature and humidity sensor and so on Video equipment including cameras Access control equipment A standard access management system is integrated...

Страница 208: ...etEco depending on the management scale TaiShan 200 Model 2280 in standard configuration and TaiShan 200 Model 2180 in basic configuration Table 9 1 Server Model Configuration TaiShan 200 Model 2280 in standard configuration 2 x Kunpeng 920 48 core 2 6 GHz 4 x 32 GB memory 2 x 1 2 TB 8 x 1 8 TB drives TaiShan 200 Model 2180 in basic configuration 1 x Kunpeng 920 32 core 2 6 GHz 2 x 32 GB memory 2 ...

Страница 209: ...24 BASE T Ethernet 10 100 1000 ports 4 of which are dual purpose 10 100 1000 or SFP 4 10Gig SFP ports S5720 28X PWR SI 24 BASE T Ethernet 10 100 1000 ports 4 of which are dual purpose 10 100 1000 or SFP 4 10Gig SFP ports S2700 26TP PWR EI 24 BASE TX Ethernet 10 100 ports and 2 BASE T Ethernet 10 100 1000 ports 2 of which are dual purpose 10 100 1000 or SFP S2326TP PWR EI 24 BASE T Ethernet 10 100 ...

Страница 210: ...tection solution and grounding solution Surge Protection Solution SPDs are installed in front of the target equipment The conducting wires to each SPD are short within 0 15 m and straight The SPD wires are copper wires with a minimum cross sectional area of 10 mm2 and the ground cables to SPDs are copper cables with a minimum cross sectional area of 16 mm2 M shaped Grid Grounding Recommended Figur...

Страница 211: ...nding solution for a dual row aisle containment 1 Each cabinet in the smart module connects to the ground grid nearby using ground cables with a minimum cross sectional area of 16 mm2 2 Use 100 mm x 0 3 mm copper foils or 25 mm2 braided copper strips for the equipotential bonding grid and use 30 mm x 3 mm red copper strips for the equipotential bonding bar based on the customer s configurations ...

Страница 212: ...Troughs Cable troughs are installed on the top of cabinets for routing cables There are two types of cable troughs signal cable troughs and power cable troughs If a dual row aisle containment is equipped with one PDF and one network cabinet power cables need to be routed to the other end of the module through the control skylight on the top of the PDF while signal cables need to be routed to the o...

Страница 213: ...able Cable The power cables include power cables to the UPS battery cabinet smart cooling product and rPDU The ground cables include ground cables to the PDU8000 battery cabinet and IT cabinet The monitoring cables include monitoring cables to the smart cooling product UPS and video devices access control alarm cables cables in the network cabinet and various sensor cables Cables to the fire extin...

Страница 214: ...206 12 UPS Derating Coefficients Table 12 1 lists the UPS5000 derating coefficients Coefficients in Table 12 1 are based on the dry air density sea level temperature 15 C of 1 225 kg m3 Table 12 1 UPS5000 derating coefficients Altitude Unit m Derating Coefficient 1000 1 0 1500 0 95 2000 0 91 2500 0 86 3000 0 82 3500 0 78 4000 0 74 4500 0 7 5000 0 67 ...

Страница 215: ...C alternate current ATS Auto Transfer Switch B BCB Battery Circuit Breaker BIB Battery control I O board BIM Battery Interface Module BSPP British Standard Pipe Parallel Thread C CAN Controller Area Network CE ConformitéEuropé enne CFD Computational Fluid Dynamics CIM Communication Interface Module D DC direct current E EC Electronic Commutation ECC Energy Control Center ETH Ethernet ...

Страница 216: ...ata Center IDS integrated data center solution IT Internet Technology L LCD Liquid Crystal Display LED Light Emitting Diode M MTBF mean time between failures MTTR mean time to repair N NTC negative temperature coefficient P PDU Power Distribution Unit PE Protective Earthing PoE Power over Ethernet PUE power usage effectiveness R RCCB Residual Current Circuit Breaker S SD Secure Digital Memory SIM ...

Страница 217: ...A Acronyms and Abbreviations Issue 06 2020 05 21 Copyright Huawei Technologies Co Ltd 209 SNMP Simple Network Management Protocol SPD surge protective device U USB Universal Series Bus UPS uninterruptible power system V VCN Video Cloud Node W WiFi Wireless Fidelity ...

Отзывы: