FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
104
The controller controls the indoor temperature precisely and responds quickly.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
The display panel displays the operating status and duration of the smart cooling product
components in real time.
The fault diagnosis system automatically displays the information about current faults,
which facilitates the maintenance.
The controller provides a variety of external ports including a fast Ethernet (FE) port and
universal serial bus (USB) port that is protected by a security mechanism.
7.2.3 Application Environment
Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.
describe the operating environment, physical ports, installation
requirements, and water quality requirements of the NetCol5000-A.
Environmental Specifications
Table 7-3
Environmental specifications
Item
Specifications
Operating temperature
18–45°C
Operating humidity
20%–80% RH
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non–condensing)
Outdoor temperature
Working with the NetCol500–A032 (including
low–temperature components): –40°C to +45°C
Working with the NetCol500–A036 (including
low–temperature components): –40°C to +55°C
Working with the NetCol500–A036: –20°C to +55°C
Working with the NetCol500-A026SC11E0: –20°C to
+45°C
Working with the NetCol500-A0265S11E0: –20°C to
+55°C
Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40°C to +45°C
Protection level
Indoor unit: IP20
Outdoor unit: IPX5