FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
117
Item
NetCol500-A060
NetCol500-A120
Operating temperature
range
-20°C to 45°C (With a
low-temperature
component -40°C to 45°C)
-20°C to 45°C (With a
low-temperature component -40°C
to 45°C)
Fan speed range
10%–100%
10%–100%
Number of fans
1
2
Dimensions H1 (H2) x
W1 (W2) x D (mm)
52273539: 1107 (677) x
1356 (1217) x 1094
52273539-005: 1107 (655)
x 1356 (1217) x 1094
52273539-006: 1156 (725)
x 1356 (1217) x 1094
52273755-002: 1107 (655) x 1356
(1217) x 2189
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Protection level
IPX5
Altitude
0–4000 m. If the altitude exceeds 1000 m, the cooling
performance is derated. For detailed derating data, contact
Huawei technical support.
Certification
RoHS, REACH, WEEE
Outdoor unit installation environments are classified as follows based on the harshness:
Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live.
Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%.
Class C (harsh environment): refers to sea environments or outdoor land environments with simple
shielding measures near pollution sources.
Class D (marine environment): environments that are within 500 m from the coast.
NetCol500-A0605S outdoor unit must not be installed in Class D environments, and other outdoor
units must not be installed in Class C or Class D environments.
7.4 NetCol5000-A050 Smart Cooling Product
This section describes the components, operating environment, and technical specifications of
the NetCol5000-A050 In-row Air Cooled Smart Cooling Product (46 kW smart cooling
product for short).