2
Copyright © Huawei Technologies Co., Ltd. 2019 All rights reserved.
2 Installation environment requirements
Environment
Requirements for selecting the installation site
• Install the cabinet in a place free from high temperature, heavy dust, harmful gas, inflammable
or explosive material, electromagnetic interference (such as a large radar station, launching
tower, or transformer substation), unstable voltage, great shock (for example, near a railway).
• Ensure that the cabinet is installed at a place at least 500 meters away from the pollution
source, highways, and the seashore. Do not install the cabinet at erosion-prone areas such as
downwind direction of chemical plants, gas stations, foul ditches, fur factories.
• The installation site should be away from trees or other plants to reduce the possibility of air
intake vent blockage and ensure normal operation of the equipment.
• If the installation site is prone to snow accumulation, you are advised to increase the
installation foundation height to prevent the cabinet door from being blocked by snow.
• If the installation site is prone to snow accumulation, you are advised to increase the
installation foundation height to prevent water from entering the cabinet.
• To prevent the cabinet noise from affecting residents, it is recommended that the distance
between the installation site and households be greater than 10 m.
• Select a suitable place for the cabinet according to the telecom network plan and telecom
device requirements considering the hydrology, geology, earthquake, electric power, and traffic
conditions.
Requirements for the conditions outside the cabinet:
•Temperature: –33
°
C to +50
°
C or
–33
°
C to +45
°
C with solar radiation
•Relative humidity : 8%–100%
•Temperature change rate: ≤ 0.5
°
C/minute
•Atmospheric pressure: 70–106 kPa
•Solar radiation: ≤ 1120 W/m2
•Wind speed: ≤ 45 m/s
Содержание ETP4860
Страница 1: ...HUAWEI TECHNOLOGIES CO LTD F01T100 ETP4860 Quick Installation Guide Issue 01 Date 2019 09 30 ...
Страница 33: ...30 11 Routing Cables 11 5 Diagram of Cable Connections Between the RPS and MDF RPS Power Supply ...
Страница 61: ...22 FAQs for Installation 58 ...