39
13 Installing Batteries
13.1 Installation Requirements
•
Before powering on the cabinet, do not connect the batteries and power module; otherwise, the batteries will
discharge to the power module, affecting the battery service life.
•
Record the last charging time (The last time charged at __) and required next charging time (Refresh Charging
No Later than __) marked in the package container to ensure timely charging. If the batteries are stored
overtime without any recharging, the batteries will bulge and their capacity will decrease, resulting in a shorter
service life.
•
Unpack the packaged batteries only after they arrive at the installation site. Install batteries grouped in the
package container. Do not use together batteries of different types, specifications, capacities, and batches in a
group.
•
Before powering on the batteries, perform the pre-installation check.
Install the batteries according to the field installation environment:
•
If the cabinet is powered on within the day when it is installed, place the batteries into the battery compartment
and connect them.
•
If the cabinet is not powered on within the day when it is installed, store the batteries in an appropriate
environment (battery storage environment: temperature 5°C-45°C and relative humidity ≤ 90% RH) for proper
maintenance and management. Otherwise, the batteries will have unrecoverable damages. If the cabinet is not
planned to be powered on for a short period (1-2 months), it is recommended that the batteries be stored in the
warehouse for subsequent maintenance and management.
Package container of
the batteries
Содержание ETP4860
Страница 1: ...HUAWEI TECHNOLOGIES CO LTD F01T100 ETP4860 Quick Installation Guide Issue 01 Date 2019 09 30 ...
Страница 33: ...30 11 Routing Cables 11 5 Diagram of Cable Connections Between the RPS and MDF RPS Power Supply ...
Страница 61: ...22 FAQs for Installation 58 ...
Страница 62: ...23 FAQs for Installation 59 ...