HTS HRP 30 C 2 Скачать руководство пользователя страница 4

1.

 

Prior to first operation of any HRP unit, the water circulating system must be cleaned and flushed of all
construction dirt and debris.  The chassis cannot be connected to system when flushing is being
conducted.  Supply and return pipes must be interconnected with factory supplied hoses to properly
flush system. This will prevent the introduction of dirt into the chasis.

 
 

2.

 

Fill system at city water makeup connection with all air vents open. After filling close all air vents
assure that boiler and heat rejector are off but flow is allowed through each. The installer/contractor
should start main circulating pump with pressure reducing makeup valve open. Check vents in sequence
to bleed off any trapped air, assuring circulation through all components of the system.

 
 

3.

 

Shut off circulating pump and open all drains and vents to completely drain the system. Short circuited
supply and return runouts should now be connected to the HRP unit with factory supplied supply and
return hoses. Teflon tape is recommended over pipe dope for pipe thread connections. Use no sealers at
the swivel flare connections of hoses.

 

4.

 

Trisodium phosphate is recommended as a cleaning agent during flushing. However, many localities
prohibit the introduction of phosphates into their sewage systems. The current recommendation is to
contact your local water treatment specialist.

 

5.

 

Refill the system with clean water. Test with litmus paper for acidity, and treat as required to leave the
water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this
time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade
antifreeze.

6.

 

Installing contractor to provide written confirmation that the system was properly flushed and balanced.
An independent flushing & balancing agency must be used.  Once this is complete a proper start can be
completed by HRP start-up contractor.

 
 

7.

 

Set the system heat add setpoint to 70°F (27°C) and the heat rejection setpoint to 85°F (29°C). Supply
power to all motors and start the circulating pumps. After full flow has been established through all
components including the heat rejector (regardless of season) and air vented and loop temperatures
stabilized, each of the HRP units will be ready for check, test and start-up and for air and water
balancing.

8.

 

 

FAILURE TO PERFORM ANY OF THE ABOVE STEPS WILL RESULT IN

TERMINATION OF MANUFACTURES WARRANTY.

System Description

This decentralized, year round heating and cooling system consists of a two pipe closed loop
water circuit, through which non-refrigerated water is circulated continuously throughout the
building. Locating the piping within the building negates the need for piping insulation. A
supplemental central heat source adding heat to the loop at the lower end of the range and
heat rejecter equipment capable of removing heat at the high end of the range maintains the
loop water temperature throughout the year in an approximate range of 65

o

 to 95

o

F (18

o

C to

35

o

C). Filled with water(usually 30% EG), this circuit provides both a sink and a source of

energy.  These systems achieve energy conservation by pumping heat from warm to cold
spaces whenever they coexist anywhere within the building.

General Design Steps

START UP : FLUSHING THE SYSTEM

In moderate weather, units serving the shady side of a building are often heating while those
serving the sunny are in cooling mode.  When approximately one-third of the units in operation
are cooling, they add sufficient heat to the water loop so that neither addition to nor rejection of
heat from the water is required.

Содержание HRP 30 C 2

Страница 1: ...SEPT 2001 INSTALLATION AND MAINTENANCE Visit us on the web at w w w www htseng com...

Страница 2: ...he carrier within 48 hours to establish your claim and request their inspection and report Our Warranty Claims Department should then be contacted All cartons are marked with UP arrows and should be t...

Страница 3: ...tor will find it beneficial to confer with piping sheet metal ceiling and electrical foremen together before installing any conditioners Chassis It is recommended that a piece of rubber or neoprene pa...

Страница 4: ...phosphate is recommended as a cleaning agent during flushing However many localities prohibit the introduction of phosphates into their sewage systems The current recommendation is to contact your lo...

Страница 5: ...ermostat is the automatic changeover type set system switch to the AUTO position and depress the heat setting to the warmest selection Some conditioners have built in time delays which prevent the com...

Страница 6: ...wing Number 101 Engineer Project Revision Sept 2001 NOTES Temporary riser supports provided contractor to supply riser clamps to support risers in multistory applications Return Air Opening is on the...

Страница 7: ...nit shown Unit Includes hose kits and shut off valves Risers are made with type M copper expanded connections are provided Contractor to provided couples where piping not swagged Optional 2 x 8 Outsid...

Страница 8: ...Engineer Project Revision Sept 2001 NOTES Any combination of discharge arrangements are available Supply Riser is towards the center line of unit All Handings determined looking at return air opening...

Страница 9: ...RETURN AIR PANEL MODEL SIZE A B C D HRP 30 40 36 18 14 32 HRP 60 80 38 20 16 34 Contractor Date Drawing Number 105 Engineer Project Revision Sept 2001 Notes...

Страница 10: ...USTIC RETURN AIR PANEL MODEL SIZE A B C D HRP 30 20 30 5 18 36 HRP 40 20 30 5 18 36 HRP 60 22 32 5 20 36 HRP 80 22 32 5 20 38 Contractor Date Drawing Number 107 Engineer Project Revision Sept 2001 Not...

Страница 11: ...clearance between heat pump return air flange and return air panel Mount Return Air Panel centered in front of Return Air opening For REAR risers allow an additional 5 clearance at back of units Inst...

Страница 12: ...y others Drywall frame is to be mounted such that there is 1 2 maximum clearance between heat pump return air flange and return air panel Mount Return Air Panel centered in front of Return Air opening...

Страница 13: ...Discharge Grille or Ductwork Installing contractor to insulate drywall enclosure with acoustical thermal batt insulation Recommended Opening Width Opening Width Opening Width Opening Width Back Discha...

Страница 14: ...provided contractor to supply clamps for multistory applications Supply riser towards center line of unit Riser couplings are not provided expanded connections are provided RISER SLEEVING SIZES AND L...

Страница 15: ...ck capacitor 2 Wires may be loose or broken Replace or tighten 3 The high pressure may have tripped due to a fouled or plugged condenser b lack of or no condenser water c too warm condenser water d no...

Страница 16: ...k all relays relaying and contacts 3 Check run capacitor 4 Check high pressure switch 5 Check low temperature switch 6 See if reversing valve has not fully shifted to either side Insufficient cooling...

Страница 17: ...ing Adjust for clearance 2 Check for bent fan wheel Replace if damaged Check for loose fan wheel on shaft Tighten 3 Make sure compressor is floating free on its isolator mounts 4 Check for tubing touc...

Страница 18: ...be seen through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned...

Страница 19: ...bient Air 50 o F 10o C 50 o F 10o C Normal Ambient Air 80 o F 27o C 70 o F 21o C Max Ambient air 110 o F 38o C 85 o F 29o C Min Entering Air 50 o F 10o C 50 o F 10o C Normal Entering Air db wb 80 67 o...

Страница 20: ...HRP 60 208 230 1 8 5 8 1 47 0 68 15 HRP 80 208 230 1 11 7 11 0 56 2 7 20 NOTES 1 Minimum circuit ampacity are for non electric heat units 2 Maximum fuse size should be HACR type circuit breaker C B w...

Страница 21: ...HRP Wiring Diagram...

Страница 22: ...ill be made at the Company s expense provided that the refrigerating circuit is delivered without shipping damage transportation prepaid to the factory or to a factory designated repair station at the...

Страница 23: ...For Parts and Service Call HTS Engineering Ltd 115 Norfinch Drive North York Ontario Tel 416 661 3400 1 800 850 0567 Fax 416 661 0100 SEPT 2001 I M 1 0...

Отзывы: