HTS HRP 30 C 2 Скачать руководство пользователя страница 17

Troubleshooting

Water drips from conditioner:

1.

 

 Check for dirty filter.

2.

 

 Check to see if condensate drain runs uphill.

3.

 

 See if blower motor is up to speed.

4.

 

 Check for loose or mispositioned blower.

5.

 

 Are drains properly trapped?

Noisy unit operation:

1.

 

Check for fan wheel hitting the housing. Adjust for clearance.

2.

 

Check for bent fan wheel. Replace if damaged. Check for loose fan wheel on shaft. Tighten.

3.

 

Make sure compressor is floating free on its isolator mounts.

4.

 

Check for tubing touching compressor or other surface. Readjust tubing by bending slightly.

5.

 

Check screws on all panels. Tighten.

6.

 

Check for chattering or humming in the contactor relays due to low voltage or a defective holding coil.
Replace component.

7.

 

Check water balance to unit for proper water flow rate.

Start-up

1. 

Open all valves to full open position and turn on power to the conditioner.

2. 

Set thermostat for FAN ONLY operation by selecting OFF at the system switch and ON at the fan

switch. If  AUTO fan operation were selected, the fan would cycle with the compressor. Check for proper
air delivery.

3. 

Set thermostat to COOL. If the thermostat is an automatic changeover type, simply set the cooling

temperature to the coolest position. On manual changeover types additionally select COOL at the system
switch. Again, many conditioners have time delays which protect the compressor against short cycling.
After a few minutes of operation, check the discharge grilles for cool air delivery. Measure the temperature
difference between entering and leaving water. It should be approximately 1 1/2

 

times greater than the

heating mode temperature difference. For example, if the cooling temperature difference is 15 degrees, the
heating temperature difference should have been at ten degrees. Without automatic flow control valves,
target a cooling temperature difference of 10° to 14°F (5° to 8°C). Adjust the combination shutoff/balancing
valve in the return line to a water flow rate which will result in the 10° to 14° (5° to 8°C) difference.

4. 

Set thermostat to HEAT. If thermostat is the automatic changeover type, set system switch to the

AUTO position and depress the heat setting to the warmest selection. Some conditioners have built-in time
delays which prevent the compressor from immediately starting. With most control schemes, the fan will
start immediately.  After a few minutes of compressor operation, check for warm air delivery at discharge
grille. If this is a "cold building" start-up, leave unit running until return air to the unit is at least 65°F
(18°C).  Measure the temperature difference between entering and leaving air and entering and leaving
water. With entering water of 60° to 80°F (16° to 27°C), leaving water should be 6° to 12°F (3.3° to 6.6°C)
cooler, and the air temperature rise through the machine should not exceed 35°F (19°C). If the air
temperature rise exceeds 35°F (19°C), then the water flow rate is probably inadequate. If the water
temperature difference is less than 6 degrees, the water flow rate is excessive. If the water temperature
difference exceeds 12°F (6.6°C), then the water flow rate is inadequate.

5.

 Check the elevation and cleanliness of the condensate line. If the air is too dry for sufficient

dehumidification, slowly pour enough water into the condensate pan to ensure proper drainage.

6.

 

If the conditioner does not operate, check the following points:

a.  

Is supply voltage to the machine compatible?

b.  

Is thermostat type appropriate?

c.  

Is thermostat wiring correct?

Содержание HRP 30 C 2

Страница 1: ...SEPT 2001 INSTALLATION AND MAINTENANCE Visit us on the web at w w w www htseng com...

Страница 2: ...he carrier within 48 hours to establish your claim and request their inspection and report Our Warranty Claims Department should then be contacted All cartons are marked with UP arrows and should be t...

Страница 3: ...tor will find it beneficial to confer with piping sheet metal ceiling and electrical foremen together before installing any conditioners Chassis It is recommended that a piece of rubber or neoprene pa...

Страница 4: ...phosphate is recommended as a cleaning agent during flushing However many localities prohibit the introduction of phosphates into their sewage systems The current recommendation is to contact your lo...

Страница 5: ...ermostat is the automatic changeover type set system switch to the AUTO position and depress the heat setting to the warmest selection Some conditioners have built in time delays which prevent the com...

Страница 6: ...wing Number 101 Engineer Project Revision Sept 2001 NOTES Temporary riser supports provided contractor to supply riser clamps to support risers in multistory applications Return Air Opening is on the...

Страница 7: ...nit shown Unit Includes hose kits and shut off valves Risers are made with type M copper expanded connections are provided Contractor to provided couples where piping not swagged Optional 2 x 8 Outsid...

Страница 8: ...Engineer Project Revision Sept 2001 NOTES Any combination of discharge arrangements are available Supply Riser is towards the center line of unit All Handings determined looking at return air opening...

Страница 9: ...RETURN AIR PANEL MODEL SIZE A B C D HRP 30 40 36 18 14 32 HRP 60 80 38 20 16 34 Contractor Date Drawing Number 105 Engineer Project Revision Sept 2001 Notes...

Страница 10: ...USTIC RETURN AIR PANEL MODEL SIZE A B C D HRP 30 20 30 5 18 36 HRP 40 20 30 5 18 36 HRP 60 22 32 5 20 36 HRP 80 22 32 5 20 38 Contractor Date Drawing Number 107 Engineer Project Revision Sept 2001 Not...

Страница 11: ...clearance between heat pump return air flange and return air panel Mount Return Air Panel centered in front of Return Air opening For REAR risers allow an additional 5 clearance at back of units Inst...

Страница 12: ...y others Drywall frame is to be mounted such that there is 1 2 maximum clearance between heat pump return air flange and return air panel Mount Return Air Panel centered in front of Return Air opening...

Страница 13: ...Discharge Grille or Ductwork Installing contractor to insulate drywall enclosure with acoustical thermal batt insulation Recommended Opening Width Opening Width Opening Width Opening Width Back Discha...

Страница 14: ...provided contractor to supply clamps for multistory applications Supply riser towards center line of unit Riser couplings are not provided expanded connections are provided RISER SLEEVING SIZES AND L...

Страница 15: ...ck capacitor 2 Wires may be loose or broken Replace or tighten 3 The high pressure may have tripped due to a fouled or plugged condenser b lack of or no condenser water c too warm condenser water d no...

Страница 16: ...k all relays relaying and contacts 3 Check run capacitor 4 Check high pressure switch 5 Check low temperature switch 6 See if reversing valve has not fully shifted to either side Insufficient cooling...

Страница 17: ...ing Adjust for clearance 2 Check for bent fan wheel Replace if damaged Check for loose fan wheel on shaft Tighten 3 Make sure compressor is floating free on its isolator mounts 4 Check for tubing touc...

Страница 18: ...be seen through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned...

Страница 19: ...bient Air 50 o F 10o C 50 o F 10o C Normal Ambient Air 80 o F 27o C 70 o F 21o C Max Ambient air 110 o F 38o C 85 o F 29o C Min Entering Air 50 o F 10o C 50 o F 10o C Normal Entering Air db wb 80 67 o...

Страница 20: ...HRP 60 208 230 1 8 5 8 1 47 0 68 15 HRP 80 208 230 1 11 7 11 0 56 2 7 20 NOTES 1 Minimum circuit ampacity are for non electric heat units 2 Maximum fuse size should be HACR type circuit breaker C B w...

Страница 21: ...HRP Wiring Diagram...

Страница 22: ...ill be made at the Company s expense provided that the refrigerating circuit is delivered without shipping damage transportation prepaid to the factory or to a factory designated repair station at the...

Страница 23: ...For Parts and Service Call HTS Engineering Ltd 115 Norfinch Drive North York Ontario Tel 416 661 3400 1 800 850 0567 Fax 416 661 0100 SEPT 2001 I M 1 0...

Отзывы: