Unit Size
Namplate
Voltage
Compressor
RLA
Compressor
LRA
Fan Motor
FLA
Max
Fuse Size
(Amps)
HRP 30
208/ 230 - 1
4.5 /4.3
25
0.68
15
HRP 40
208/ 230 - 1
5.7 / 5.4
27
0.68
15
HRP 60
208/ 230 - 1
8.5 / 8.1
47
0.68
15
HRP 80
208/ 230 - 1
11.7 / 11.0
56
2.7
20
NOTES:
1.
Minimum circuit ampacity are for non electric heat units.
2.
Maximum fuse size should be HACR type circuit breaker C/B & wiring to C/B
by others.
3.
Compressor and fan motors are permanent split capacitor type, all single phase.
A vertical stacking heat pump provides the essential benefits of a centralized system but gives the
individual choice of heating or cooling. Additionally, the occupant may select heating, cooling,
or may shut off the unit without affecting conditions maintained in other spaces.
General Design Steps
Electrical Data – HTS Signature Series : High Rise Heat Pumps
During hot weather with most or all units cooling, heat removed from the air is transfer to the water
loop. A water tower rejects the excess heat outdoors to maintain a maximum water temperature of
approximately 95
o
F