63
Figure 27
10. Press and hold
ENTER
for 4 seconds until you see the screen to log in the access code.
11. Use the
and
arrow keys to move the blinking zero to the left and right. Next, use the
▲
and
▼
arrow keys on to log in the access code of 925. Press
ENTER
to access the
System Setting Program
Navigation
menu. Once the code is confirmed, you can set the
System Settings
. Use
and
to
navigate through the
System Setting Program
.
12. Press
3 times to scroll to Function 4 - “WARM WEATHER OFF”. This is the warm weather
shutdown. This function determines the outdoor temperature that will turn off the hydronic heating module
and operate the appliance only as a water heater for the warmer weather. To adjust this value, press
ENTER
and the factory default of 68°F starts to blink. Use
▲
and
▼
to adjust this value to your system
needs. To store the new value press
ENTER
.
13. Next, press
once to scroll to Function 5 - “MIN OUTDOOR TEMP”. This function is the first step to
setting the outdoor reset curve. Enter your system’s minimum outdoor temperature value. To adjust the
value, press
ENTER
and the factory default of 5 °F starts to blink. Use
▲
and
▼
to adjust to your
designed temperature. To store the new value press
ENTER
.
Содержание Versa Hydro PHE130-119
Страница 23: ...23 Figure 5 Figure 6 ...
Страница 24: ...24 Figure 7 ...
Страница 25: ...25 F HYDRONIC PIPING Figure 8 ...
Страница 26: ...26 Figure 9 ...
Страница 27: ...27 Figure 10 ...
Страница 28: ...28 Figure 11 ...
Страница 29: ...29 Figure 12 ...
Страница 32: ...32 F INTERNAL WIRING Figure 14 Internal connection diagram ...
Страница 38: ...38 Figure 17 ...
Страница 48: ...48 Figure 25 ...
Страница 76: ...76 Figure 29 ...
Страница 77: ...77 Figure 30 ...
Страница 78: ...78 Figure 31 LP 314 G ...
Страница 79: ...79 Figure 32 ...
Страница 81: ...81 ...
Страница 82: ...82 ...
Страница 83: ...83 MAINTENANCE NOTES ...