PART 1 – GENERAL SAFETY INFORMATION
A. PRECAUTIONS
INDOOR INSTALLATION
Clearance to combustible materials: 0” top, bottom, sides and back. Unit must have room for service: 24” front and 12” sides are
minimum recommended service clearances. (A combustible door or removable panel is acceptable front clearance.) This water heater
has been approved for closet installation, and installation on combustible flooring. Do not install this water heater directly on carpeting.
Use only Category IV vent systems.
OUTDOOR INSTALLATION
Clearance to combustible materials: 0” top, bottom, sides and back. Special attention should be paid to ensure that T&P valve
discharge and drainage from the condensate line will not adversely affect the surrounding area or pose a hazard in freezing conditions.
This water heater has a condensate disposal system that may freeze if exposed to sustained temperatures below 32
o
F. Precautions
should be taken to protect the condensate trap and drain lines from sustained freezing conditions. Failure to take precautions could
result in property damage, severe personal injury, or death.
INSTALLER
–
Read all instructions in this manual before installing. Perform steps in the order given.
USER
–
This manual is for use only by a qualified heating installer/service technician. Have this heater serviced/inspected by a
qualified service technician annually.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE AND HAVE THIS HEATER SERVICED/INSPECTED ANNUALLY
CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.
If the heater is exposed to the following, do not operate until all corrective steps have been made by a qualified service technician:
1. FIRE
2. DAMAGE
3. WATER
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN SUBMERGED IN WATER.
Immediately call a qualified service
technician. The water heater MUST BE replaced if it has been submerged. Attempting to operate a water heater that has been
submerged could create numerous harmful conditions, such as a potential gas leakage causing a fire and/or explosion, or the release
of mold, bacteria, or other harmful particulates into the air. Operating a previously submerged water heater could result in property
damage, severe personal injury, or death.
NOTE:
Water heater damage due to flood or submersion is considered an Act of God, and IS NOT covered under product warranty.
Altering any HTP, Inc. water heater with parts not manufactured and/or approved by HTP, Inc. WILL INSTANTLY VOID the water
heater warranty and could result in property damage, serious personal injury, or death.
This water heater has been designed to heat potable water ONLY. Using this water heater to heat non-potable fluid WILL VOID product
warranty, and could result in property damage, personal injury, or death.
B. IMPROPER COMBUSTION
Do not obstruct the flow of combustion and ventilating air. Adequate air is necessary for safe operation. Failure to keep the exhaust
vent and intake pipe clear of ice, snow, or other debris could result in property damage, serious personal injury, or death.
C. GAS
Should overheating or gas supply fail to shut off, turn off the manual gas control valve to the water heater.
Содержание phoenix plus PHP199-119
Страница 32: ...32 LP 454 REV 1 6 15 Figure 15...
Страница 37: ...37 LP 454 REV 1 6 15 C INTERNAL WIRING DIAGRAM Figure 21 Stage 1 Wiring Diagram...
Страница 38: ...38 LP 454 REV 1 6 15 Figure 22 Stage 2 Wiring Diagram Not Applicable to 199kBTU Models...
Страница 39: ...39 LP 454 REV 1 6 15 Figure 23 LP 179 L...
Страница 48: ...48 LP 454 REV 1 6 15 Figure 26 LP 454 W...
Страница 49: ...49 LP 454 REV 1 6 15 Figure 27 LP 454 Y...
Страница 50: ...50 LP 454 REV 1 6 15 Figure 28 LP 454 X...
Страница 53: ...53 LP 454 REV 1 6 15...
Страница 54: ...54 LP 454 REV 1 6 15...
Страница 55: ...55 LP 454 REV 1 6 15 MAINTENANCE NOTES...