16
LP-454 REV. 1.6.15
COLD WEATHER HANDLING
– If the heater has been stored in a very cold location (BELOW 0
o
F) before installation, handle with care
until the plastic components come to room temperature.
Remove all sides of the shipping crate to allow the heater to be moved into its installation location.
PERFORMANCE SPECIFICATIONS FOR PHOENIX PLUS MODELS
MODEL
GALLON CAPACITY
BTU/HR INPUT
TEMPERATURE RISE IN DEGREES FAHRENHEIT
40
50
60
70
80
90
100
110
120
130
140
PHP199-119
PHP199-119D
119
199,000
GPH
579
463
386
331
289
257
232
211
193
178
165
GPM
9.6
7.7
6.4
5.5
4.8
4.3
3.9
3.5
3.2
3.0
2.8
PHP260-119
260,000
GPH
756
605
504
432
378
336
303
275
252
233
216
GPM
12.6
10.1
8.4
7.2
6.3
5.6
5.0
4.6
4.2
3.9
3.6
PHP320-119
320,000
GPH
931
745
621
532
465
414
372
339
310
286
266
GPM
15.5
12.4
10.3
8.9
7.8
6.9
6.2
5.6
5.2
4.8
4.4
PHP399-119
399,000
GPH
1161
929
774
663
580
516
464
422
387
357
332
GPM
19.3
15.5
12.9
11.1
9.7
8.6
7.7
7.0
6.4
6.0
5.5
Table 2
– Phoenix Plus Performance – 95% Thermal Efficiency Used for Calculations
PERFORMANCE EQUATIONS
Rated Input x .95
GPM = Temp Rise (
o
F) x 500
GPH = GPM x 60
PART 4 – HEATER PIPING
Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage, serious injury, or death.
A. GENERAL PIPING INFORMATION
Use two wrenches when tightening water piping at heater. Use one wrench to prevent the heater return or supply line from turning.
Failure to prevent piping connections from turning could cause damage to heater components.
DO NOT pipe this water heater with black iron, galvanized steel, steel, or lead pipe. Doing so will result in premature product failure and
property damage, and WILL VOID the product warranty.
The heater control module uses temperature sensors to provide both high limit protection and modulating temperature control. The
control module also provides low water protection by sensing the water level in the tank. Some codes/jurisdictions may require
additional external controls.
Never use dielectric unions or galvanized steel fittings when connecting to a stainless steel storage tank or heater. Use only copper or
brass fittings. Teflon thread sealant must be used on all connections.
Содержание phoenix plus PHP199-119
Страница 32: ...32 LP 454 REV 1 6 15 Figure 15...
Страница 37: ...37 LP 454 REV 1 6 15 C INTERNAL WIRING DIAGRAM Figure 21 Stage 1 Wiring Diagram...
Страница 38: ...38 LP 454 REV 1 6 15 Figure 22 Stage 2 Wiring Diagram Not Applicable to 199kBTU Models...
Страница 39: ...39 LP 454 REV 1 6 15 Figure 23 LP 179 L...
Страница 48: ...48 LP 454 REV 1 6 15 Figure 26 LP 454 W...
Страница 49: ...49 LP 454 REV 1 6 15 Figure 27 LP 454 Y...
Страница 50: ...50 LP 454 REV 1 6 15 Figure 28 LP 454 X...
Страница 53: ...53 LP 454 REV 1 6 15...
Страница 54: ...54 LP 454 REV 1 6 15...
Страница 55: ...55 LP 454 REV 1 6 15 MAINTENANCE NOTES...