41
LP-454 REV. 1.6.15
Nominal Iron
Pipe Size (In.)
Internal
Dia. (In.)
Length of Pipe (Feet)
BTU’s
Per Hour
x
1,000
10
20
30
40
50
60
70
80
90
100
125
150
175
200
¾
.824
278
190
152
130
115
105
96
90
84
79
72
64
59
55
1
1.049
520
350
285
245
215
195
180
170
160
150
130
120
110
100
1 ¼
1.380
1,050
730
590
500
440
400
370
350
320
305
275
250
225
210
1 ½
1.610
1,600
1,100
890
760
670
610
560
530
490
460
410
380
350
320
Table 8
– Source – ANSI Z223.1
It is recommended that a soapy solution be used to detect leaks. Bubbles will
appear on the pipe to indicate a leak is present. The gas piping must be sized for
proper flow and length of pipe to avoid excessive pressure drop. Both the gas
meter and the gas regulator must be properly sized for the total gas load. If you
experience a pressure drop greater than 1" WC, the meter, regulator or gas line
is undersized or in need of service. You can attach a manometer to the incoming
gas drip leg by removing the cap. The gas pressure must remain between 3.5"
WC and 14" WC during stand-by (static) mode and while in operating (dynamic)
mode at full output.
If an in-line regulator is used, it must be a minimum of 10 feet from the
heater. It is very important that the gas line is properly purged by the gas
supplier or utility. Failure to properly purge the lines or improper line sizing
will result in ignition failure.
This problem is especially noticeable in NEW LP
installations and also in empty tank situations. This can also occur when a utility
company shuts off service to an area to provide maintenance to their lines. The
gas valve must not be replaced with a conventional gas valve under any
circumstances. As an additional safety feature, the gas valve in this water heater
has a flanged connection to the swirl plate and blower.
C. GAS VALVE
Figure 25
– Gas Valve
Содержание phoenix plus PHP199-119
Страница 32: ...32 LP 454 REV 1 6 15 Figure 15...
Страница 37: ...37 LP 454 REV 1 6 15 C INTERNAL WIRING DIAGRAM Figure 21 Stage 1 Wiring Diagram...
Страница 38: ...38 LP 454 REV 1 6 15 Figure 22 Stage 2 Wiring Diagram Not Applicable to 199kBTU Models...
Страница 39: ...39 LP 454 REV 1 6 15 Figure 23 LP 179 L...
Страница 48: ...48 LP 454 REV 1 6 15 Figure 26 LP 454 W...
Страница 49: ...49 LP 454 REV 1 6 15 Figure 27 LP 454 Y...
Страница 50: ...50 LP 454 REV 1 6 15 Figure 28 LP 454 X...
Страница 53: ...53 LP 454 REV 1 6 15...
Страница 54: ...54 LP 454 REV 1 6 15...
Страница 55: ...55 LP 454 REV 1 6 15 MAINTENANCE NOTES...