62
LP-171 Rev. 3.3.15
To adjust, press either
{S1}
(Decrease Value) or
{S2}
(Increase Value) Ranges 5°F to 30°F. Press
{S3}
again and you will see the
Indirect Setting de and an alternative value of 119 (
with Vision Systems option
). To adjust, press either
{S1}
(Decrease Value) or
{S2}
(Increase Value).
The final adjustment in this mode is the Fahrenheit to Celsius measurement. Press
{S3}
again and you will see t and alternating value
of F. To change value, press
{S1}
or
{S2}
to choose the correct measurement.
C. STATUS MENU
Installers are also able to check the current status of heater parameters by pressing
{S4}
for 3 seconds. Once activated, the display will
show
|d1|
alternating value of the actual outlet temperature. Actual values are displayed for each function. To view the next value, press
{S4}
to go to the next displayed value. Listed below are the values which can be displayed. These values cannot be changed. To exit
this menu, simply press
{S3}
to resume normal operation.
Function
Value
d1
— Actual Temperature from outlet sensor
d2
— Actual Temperature from inlet sensor
d3
— If using a standard mechanical control, the control will display
|1|
for closed
|0|
for open. If the sensor is connected to the
SuperStor Indirect Fired Water Heater it will measure the actual temperature (Vision option).
Function
Value
d4
— Not used
d5
— Actual Temperature from the outdoor sensor (Vision option).
d6
— Actual Fan speed multiplied by 10 (Example: If fan speed displayed is
|410|
RPM x 10 = 4100 actual fan speed)
d7
— Actual Ionization current read from Flame Rectification probe
d8
— Actual Status of the Central Heating Circulator Off =
|0|
, On =
|1|
. (Vision option.)
d9
— Actual Status of the Indirect Fired Circulator Off =
|0|
, On =
|1|
. (Vision option.)
d10
— Actual Status bus communication
|co|
= connected,
|no|
= not connected
d11
— Central Heating Set Point
d12
— Power On Hours in units
d13
— Total Central Heat Hours
d14
— Total Indirect/dhw Hours
d15
— Passed Ignition Attempts
D. TEST MODE
This function is intended to simplify the gas valve adjustment if needed. Listed below are the recommended limits on each heater and
the combustion settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation
based on the heater central heating set point. The user will be allowed to increase or decrease the fan speed by pressing in either
{S1}
or
{S2}
.
To activate Test mode, press
{S2}
and
{S3}
together for 1 second. Once activated, you will see
{Ser}
in the display and the actual fan
speed. The measurement of the combustion levels should always be taken at the highest and lowest fan speed. After 10 minutes, the
Test mode stops automatically. To exit Test mode, press
{S1}
and
{S2}
together for 1 second.
COMBUSTION SETTINGS ON ALL MODELS
Natural Gas
Propane LP
Fan Speed
Low
Ignition
High
Low
Ignition
High
Carbon Monoxide PPM
5
– 50
60
– 100
< 150
5
– 50
60 - 140
< 150
Carbon Dioxide (CO
2
)
8 - 10%
8 ½
– 10 ½%
8 ½ - 10 ½%
9 - 10 ½%
9 - 11%
Table 9
FAN SPEEDS
HEATER
HIGH
LOW
IGNITION
MC-50
3300
1250
3000
MC-80
4250
1200
4250
MC-99
4700
1500
3000
MC-120
5500
1500
3000
Table 10
PART 13 – START-UP PROCEDURES WITH VISION 1 OPTION
The Vision I option allows the user to have one temperature for central heating and another temperature for the SuperStor Ultra Indirect
Fired Water Heater. This enables the user to increase the temperature supplied to the indirect water heater by prioritizing flow at a
higher temperature than may be needed for the central heating circuits (this will require two separate circulators). Once the indirect
Содержание MC120
Страница 21: ...21 LP 171 Rev 3 3 15 M PIPING DETAILS Figure 5 ...
Страница 53: ...53 LP 171 Rev 3 3 15 Figure 30 ...
Страница 71: ...71 LP 171 Rev 3 3 15 Figure 34 ...
Страница 72: ...72 LP 171 Rev 3 3 15 Figure 35 ...
Страница 73: ...73 LP 171 Rev 3 3 15 Figure 36 ...
Страница 76: ...76 LP 171 Rev 3 3 15 ...
Страница 77: ...77 LP 171 Rev 3 3 15 ...
Страница 78: ...78 LP 171 Rev 3 3 15 MAINTENANCE NOTES ...