![HTP EL-110 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/htp/el-110/el-110_installation-manual_2179388046.webp)
46
L. VENTING THROUGH AN EXISTING SYSTEM
This boiler may be vented through an existing unused vent system. The inner diameter of the existing vent system
is utilized for the combustion air source. Two methods have been approved for such venting: Concentric Venting
Through an Existing System and Venting as a Chase.
Do not install the boiler into a common existing vent with any other appliance. This will cause flue gas spillage or
boiler malfunction, resulting in substantial property damage, severe personal injury, or death.
Contractors must check state and local codes before installing through an existing vent opening. State and local
codes always take precedence over manufacturer’s instructions. Failure to check state and local codes before
installing through an existing opening could result in property damage and add significantly to installation costs.
1. CONCENTRIC VENTING THROUGH AN EXISTING SYSTEM
NOTE:
The following instructions refer only to venting through an existing vent system, and not to venting with
HTP’s concentric vent kits (2” Part # KGVAT0501CVT, 3" Part # KGAVT0601CVT). Refer to Concentric Vent Kit
installation manual (Part # LP-166) for further concentric venting information and instructions.
Concentric venting through an existing system must run vertically through the roof. See Table 11 for proper
minimum vent sizing. Use only the approved venting materials specified in Table 10 for piping the system. All
instructions listed in Part 5 - Venting, Sections A
– G apply. See Figures 18-1 and 18-2 for venting
demonstrations.
The upper and lower vent terminations as well as all joints in the venting system must be properly sealed to
ensure that all combustion air is drawn properly and exhaust does not leak from the system. Failure to properly
seal the venting system will result in property damage, severe personal injury, or death.
Содержание EL-110
Страница 15: ...15 Figure 3 ...
Страница 61: ...61 Figure 29 ...
Страница 62: ...62 Figure 30 ...
Страница 87: ...87 Figure 33 ...
Страница 88: ...88 Figure 34 ...
Страница 89: ...89 Figure 35 LP 293 A NOTE Parts listed on the following page ...
Страница 94: ...94 ...
Страница 95: ...95 ...
Страница 96: ...96 MAINTENANCE NOTES ...