86
Error code
Meaning
Cause
Tilt switch
(Automatic restore)
Vibration occurs hot water and Tilt
switch senses it and error code 42
appears.
Failure event
It occurs when sensing serious shaking during operation then cut off gas valve power in circuit and manual
restore error occurs.
Check point
① Check position of boiler and correctly installed condition.
② Confirm ‘Tilt switch’ is fixed well.
③ Check the availability of normal operation by shorting the 2P
connectors for ‘Tilt switch’.
(1) In case error disappear after shorting
: Replace ‘Tilt switch’
(2) In case error not disappear after shorting
: Check overheating sensor and water temperature sensor
(3) Overheating sensor and water temperature sensor are
inspected but same problem occurs.
: Replace main controller
④ If above issues operates normally, replace main controller.
Chapter 4 Troubleshooting
① Check whether error code disappears after turning OFF and ON the power.
① Check whether error code disappears after turning OFF and ON the
power.
① Check whether error code disappears after turning OFF and ON
LP-528 REV. 8.01.14
Error code
Meaning
Cause
Jumped Wire Disconnected
(Manual reset)
Error Er 42 will appear if wire
is disconnected.
Failure event
Jumped Wire Disconnected
Check point
① Ensure the jumper wire is properly connected on the control board.
② If all things are normal, please replace main controller.
WARNING
Failure to turn the power off to the appliance before repair could result in serious injury or death.
Содержание EFTC-140F
Страница 3: ...1 LP 528 REV 8 01 14 ...
Страница 11: ...9 Domestic Hot Water Mode Space Heating Mode Flow chart Chapter 1 Product Characteristics LP 528 REV 8 01 14 ...
Страница 13: ...11 Operation flow chart Chapter 1 Product Characteristics LP 528 REV 8 01 14 ...
Страница 14: ...12 Operation flow chart Chapter 1 Product Characteristics LP 528 REV 8 01 14 ...
Страница 15: ...13 Wiring Diagram Chapter 1 Product Characteristics LP 528 REV 8 01 14 ...
Страница 16: ...14 Wiring Diagram Chapter 1 Product Characteristics Mixing Valve LP 528 REV 8 01 14 ...
Страница 41: ...39 Installer Setting Mode Control panel mode Chapter 3 How to use control panel LP 528 REV 8 01 14 ...
Страница 42: ...40 Chapter 3 How to use control panel LP 528 REV 8 01 14 ...
Страница 67: ...65 Chapter 4 Troubleshooting 1 Flame Detection LP 528 REV 8 01 14 ...
Страница 69: ...67 4 Storage DHW OP CH Overheat Exhaust Overheat Sensor Chapter 4 Troubleshooting LP 528 REV 8 01 14 ...
Страница 70: ...68 Error code Chapter 4 Troubleshooting LP 528 REV 8 01 14 ...
Страница 71: ...69 Chapter 4 Troubleshooting LP 528 REV 8 01 14 ...
Страница 72: ...70 Chapter 4 Troubleshooting LP 528 REV 8 01 14 ...
Страница 106: ...104 1 Cabinet Replacement Parts Chapter 7 Repair Part Diagram LP 528 REV 8 01 14 ...
Страница 107: ...105 Chapter 7 Repair Part Diagram LP 528 REV 8 01 14 ...
Страница 108: ...106 2 Combustion System Replacement Parts Chapter 6 Repair Parts Diagram LP 528 REV 8 01 14 ...
Страница 109: ...107 Chapter 7 Repair Part Diagram LP 528 REV 8 01 14 ...
Страница 110: ...108 Memo LP 528 REV 8 01 14 ...
Страница 111: ...109 Memo LP 528 REV 8 01 14 ...
Страница 112: ...110 Memo LP 528 REV 8 01 14 ...