IMP57
EN - 35
9. TECHNICAL SPECIFICATIONS
9.1. TECHNICAL
FEATURES
Accuracy is indicated as [% of r number of digits]. It refers to the following
atmospheric conditions: a temperature of 23°C ± 5°C with a relative humidity < 60%HR.
IMPEDANCE
MEASUREMENT
Range Resolution Accuracy
0.1
199.9m
(*) 0.1m
(5% r 1m
)
200
1999m
1m
(*) Max test current 202A
RESISTANCE AND REACTANCE MEASUREMENT
(for Type 1 and Type 3 instr. only – see table
1 pag. 8)
Range Resolution Accuracy
0.1
199.9m
(*) 0.1m
(10% r 2m
)
200
1999m
1m
(*) Max test current 202A
PROSPECTIVE SHORT CIRCUIT CURRENT
Range Resolution Accuracy
0
1999A
1A
related to Z accuracy and relationship of
paragraph 6.1.2 and 6.2.2 and 6.3.2 and
6.4.2
2.0
9.9kA
0.1kA
10
1999kA
1kA
VOLTAGE
Range (50Hz
5%)
Resolution Accuracy
190
460V
1V
(1.0
2digit)
FREQUENCY
Range Resolution Accuracy
47.5 – 52.5Hz
0.1Hz
0.2Hz
9.1.1. Safety Guidelines:
IMP57 comply with:
EN 61010, EN61557
Insulation:
Class 2, Double Insulation
Pollution
degree:
2
max
altitude:
2000m
Overvoltage category:
CAT III 240V (to ground)
CAT III 415V (between inputs P1, C1, P2, C2)
9.1.2. Safety standards
The instrument complies with CEI 64.8 612.6.3, EN61557-3, EN60909-0, VDE 0413
9.1.3. General Characteristics
Dimensions:
340mm (L) x 300mm (W) mm x 150mm (H)
Weigh:
approx.4100g (without accessories)
Power Supply
Nominal
Voltage:
220
415V (between P1 and P2)
Frequency:
50Hz
5%
Содержание IMP57
Страница 1: ...Copyright HT ITALIA 2013 Version EN 3 00 04 01 2013 ENGLISH User s manual...
Страница 2: ......