IMP57
EN - 11
6. MASTER INSTRUMENT SETTINGS
Operating Instruction are given according to
Table 1 - Instrument Type
definition.
6.1.
OPERATING INSTRUMENT FOR “TYPE 1” INSTRUMENT
6.1.1. Instrument Settings
Select
LOOP
rotary switch position.
Select one of the following connection by means
F1
button.
"
P-P
", "
P-N
", "
P-PE
"
available among the functions "P-P", "P-N", "P-PE", " R
A
", "
".
Press
F2
to Enable the "High Resolution Measurement
Z2
" working mode.
correspondently the
Z2
symbol will be displayed in the lower part of the
display.
When
Z2
working mode is enabled it's possible to select one of the
following measurement mode by means the
F1
button.
“
P-N
"
The instrument execute the High Resolution Phase-Neutral
impedance measurement and calculate the Prospective Short
circuit Current Calculation selected.
“
P-P
" The instrument execute the High Resolution Phase-Phase
impedance measurement and calculate the Prospective Short
circuit Current Calculation selected.
“
P-PE
"
The instrument execute the High Resolution Phase-ground
impedance measurement and calculate the Prospective Short
circuit Current Calculation selected.
The
F3
button allows the selection of Prospective Short Circuit current
calculation according to paragraph 6.1.2.
By pressing the
F4
button the instrument will show the IMP57 Serial Number,
the Firmware release and the calibration date. Press ESC to quit this screen.
Press
F2
button to quit High Resolution Measurement mode
Z2
.