August-2015
Page 13
5.
Panel operation
HST-HP201-2 will not power on if backup batteries is the only power source connected.
Panel must be powered on with its main power.
After power on, power LED is on and LCD displays HST logo while panel is initializing
its hardware modules and it’s saved data.
After initialization, panel displays loops scanning window. Panel scans loops one by one
to identify all connected devices to this loop. If this is the first time to power on the panel, it
will save directly what is identified. If this is not the first time to power on the panel, it will
compare what is identified to what was previously saved in the panel. If mismatch is detected,
panel will display all errors after scan phase is finished. If there is any error in communication
with the loop, loop scan will be aborted and loop communication fault will be trigged after
scanning phase is finished. If one loop is disabled, panel will skip scanning this loop. If all
loops are disabled (which is not a normal behavior), panel will not scan any loop and general
disabled LED will be on. By default, loop 1 is enabled and loop 2 is disabled.
After scanning, panel displays its main window. Date & time are displayed at the upper
left part of the LCD. Logo and panel model are displayed at the upper right part of the LCD.
Panel name and current status are displayed down to date and time information.
First fire and other fire, fault and manual evacuate information are displayed at middle of
LCD. Last row in the LCD is used to display some icons which identify some information
about panel current status.