After selecting one relay, relay configuration window appears with its last saved
parameter value.
First configuration is relay name. It is only used for relay identification and will not be
shown on the display. To change it, highlight it will arrow keys and press 0 key. On screen
keyboard will be shown at the top right corner of the display. Working with it is exactly same
as described in changing panel name section.
Second configuration is which events will trigger the relay. There are 4 fixed events,
‘Fire’, ‘Fault, ‘Evacuate’ and ‘Pre Alarm’. To make the relay triggers or does not trigger on
one event, highlight it with arrow key and press 0 key. If X symbol appears in front of the
event, this means that the relay will trigger on this event. If X symbol does not appear in
front of the event, this means that the relay will not trigger on this event. For the relays and all
outputs, selection of more than one event is accepted.
Third configuration is the silence state of the relay. This means that if the relay will return
its contacts to NC State when Silence Alarm key is pressed or will keep its contacts to NO
state even if Silence Alarm key is pressed. To change it, highlight it with arrow keys and
press 0 key. If X symbol appears in front of it, this means that the relay will stop with silence
alarm state. If X symbol does not appear in front of the event, this means that the relay will
not stop with silence alarm state.
Fourth configuration is disabled state of the relay. This means that if the relay will be
function or not regardless of the current panel state. To change it, highlight it with arrow keys
and press 0 key. If X symbol appears in front of it, this means that the relay will be disabled
and not working. If X symbol does not appear in front of it, this means that the relay will be
working normally. If disabled is active, after saving, general disabled LED will be on.
Fifth configuration is zone number. Zone for on board relays is fixed to zone 0 and cannot
be changed.
Sixth configuration is delay value. It is used to postpone the relay trigger to a defined
amount. The number represents number of half minutes of delay. For example, if value is 3,
so the delay value is 1.5 minutes. If value is 12, so the delay value is 6 minutes. Minimum
value is 0 which means that no delay for this relay and it will trigger directly when at least