August-2015
Page 14
LCD backlight is on by default. In case of no updates on LCD (except date & time), LCD
backlight will be turned off after 10 minutes. LCD backlight can be turned on again with any
change on LCD.
5.1.
Access levels
HST-HP201-2 has 3 access levels for different panel operations from panel users.
Access level 1 is the least secure level and has no protected password. It is the default
level after power on and it has the ability to see different fire and fault information at the main
screen and it can silence panel buzzer.
Access level 2 is the medium secure level and it is protected by password. Added to
access level 1 permissions, at fire or fault conditions, it has the ability to silence the trigged
alarms, re-sound the silenced alarm, and perform fire reset. Also it can trigger Evacuate key
on the panel.
Access level 2 users can also access panel programming & configuration menus through
Menu key on the panel. Users can only see all panel configuration data but they cannot make
any changes to it.
Access level 3 is the highest secure level and is protected by password. Added to access
level 1 & 2 permissions, it has the ability to change any panel configuration data and it has
access to 4
th
sub menu which contains advanced panel operations.
To make changes to any panel configuration data, with level 3 access, enable key must be
turned on to proceed saving any changes.
Access level 2 & 3 passwords and enable key must only be known and kept to the
identified persons who have the permissions to perform different panel functions.