The System Reset key resets the system and any detectors. A Reset key is located on the PANEL keypad
(illustrated in Figure 4-1). If the System Reset keys are pressed, the control panel will:
✓
Clear the status LEDs
✓
Turn off the Notification Appliance Circuits
✓
Reset all zones by temporarily removing power
✓
Silence the onboard piezo sounder
✓
Restore all system relays to normal
✓
Temporarily remove power from the resettable power output Terminals
Any alarm, supervisory or fault condition that exists after a system reset will resound the system,
reactivating normal system activity. Any zones and sounds that were disabled before the reset will remain
disabled after the reset, the panel running mode will remain the same after the reset..
4.2 Status LEDs
AC Power LED
A green LED that remains on while the AC power supply is within correct limits. A yellow LED blinks under
Battery powered condition. It turns on steady when Mute key is pressed. If this indicator fails to light under
normal conditions, service the system immediately.
Battery LED
A green LED that remains on while the Battery power supply is within correct limits. A yellow LED that
blinks is to indicate a low battery or no battery condition on the PANEL. It turns on steady when Mute key is
pressed. If this indicator fails to light under normal conditions, service the system immediately.
Mute LED
A yellow LED that turns on to indicate that an Alarm or Fault condition exists in the system, but piezo
sounder have been silenced.
Silence LED
A yellow LED that turns on to indicate that an Alarm condition exists in the system, but Notification
Appliance Circuits have been silenced.
Fire Alarm LED
A red LED that turn on when a system fire alarm condition is detected.
Fault LED
A yellow LED that turn on to indicate that a system fault or abnormal condition exists and that the fire alarm
system may be inoperative. It turns on steady when a signal Silence or Mute key is pressed.
Supervisory LED
A red LED that turn on to indicate the need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems that connected in Supervisory Terminal.
Activate LED
A red LED that flashes when enter the directly activate mode. In this mode, the Notification Appliance
Circuits (Sound1-Sound 4 Output) can be activated directly by manual. A red LED that turn on to indicate any
of sound1 to sound 4 has been activated.
Zone Disabled LED
A yellow LED that turn on to indicate that one or more alarm zones have been disabled. The disabled zone(s)
fault LED will also be on. When enter program mode, a flash LED indicates the program features.
Sound Disabled LED
A yellow LED that turn on to indicate that one or more Notification Appliance Circuits (Sound1-Sound 4
Output) have been disabled. The disabled Sound(s) yellow LED will also be on. When enter program mode, a
Page 31 of 36
Содержание HP101U
Страница 6: ...Notes ...
Страница 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Страница 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Страница 11: ...Page 11 of 36 ...
Страница 12: ...The functions of terminal Page 12 of 36 ...
Страница 13: ...Page 13 of 36 ...
Страница 16: ...Page 16 of 36 ...
Страница 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Страница 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Страница 24: ...Page 24 of 36 ...