CHAPTER 1:
Product Description
The PANEL is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The
panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other
normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three
standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote
annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also
supervises all wiring, AC voltage and battery level.
This series of panels are basically the same in application and operation, their differences are shown in Table 1-1.
PANEL will be described as the example in the following sections.
Table 1-1
FACP
Number of Detection Zones
Number of Sounder Outputs
Output Delay Settings
8113-4
4
1
N/A
8113-8
8
2
N/A
8113-16
16
4
N/A
1.1 Product Features
4,8,16 Class B Initiating Device Circuits (IDCs)
✓
All zones accept conventional detectors and any normally open contact device
Four Class B Notification Appliance Circuits (NACs)
One Form-A Alarm Relay
One Form-A Trouble Relay
One Form-A Supervisory Relay
3.0 amps of system power
Max 30 conventional detectors in one zone.
Auto/Manual mode setting enable walk test.
Each Zone can be disabled,
Sound output can be disabled.
Manual active sound output enabled.
Able to report short and broken circuit of detection zones.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
Testing and disable functions.
Can connect max 32 repeater panels by RS485 communication port
Dimensions : 14.57" (37 cm) long X 17.32" (44 cm) high X 3.94"(10cm).
Weight: 6.6kg (without battery).
Page 10 of 36
Содержание HP101U
Страница 6: ...Notes ...
Страница 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Страница 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Страница 11: ...Page 11 of 36 ...
Страница 12: ...The functions of terminal Page 12 of 36 ...
Страница 13: ...Page 13 of 36 ...
Страница 16: ...Page 16 of 36 ...
Страница 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Страница 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Страница 24: ...Page 24 of 36 ...