background image

Installation Precautions

Adherence  to the  following will  aid  in  problem-
free installation with long-term reliability:

WARNING  

- Several different sources of power can be

connected to the fire alarm control panel. Disconnect all

sources   of   power   before   servicing.     Control   unit   and

associated   equipment   may   be   damaged   by   removing

and/or   inserting   cards,   modules,   or   interconnecting

cables   while   the   unit   is   energized.   Do   not   attempt   to

install, service, or operate this unit until this manual is

read and understood.

CAUTION

  -   System   Reacceptance  Test   after   Software

Changes.     To   ensure   proper   system   operation,   this

product   must   be   tested   in   accordance   with   NFPA  72

Chapter 7 after any programming operation or change in

site-specific soft- ware.  Reacceptance testing is required

after   any   change,   addition   or   deletion   of   system

components,   or   after   any   modification,   repair   or

adjustment to system hardware or wiring.

All components, circuits, system operations, or software

functions   known   to   be   affected   by   a   change   must   be

100% tested. In addition, to ensure that other operations

are not inadvertently affected, at least 10% of initiating

devices that are not directly affected by the change, up to

a   maximum   of   50   de-   vices,   must   also   be   tested   and

proper system operation verified.

This system

  meets NFPA requirements for operation at

0-49° C/32-120° F and at a relative humidity of 85% RH

(non- condensing) at 30° C/86° F.   However, the useful

life of the system's standby batteries and the electronic

components   may   be   adversely   affected   by   extreme

temperature   ranges   and   humidity.   Therefore,   it   is

recommended   that   this   system   and   all   peripherals   be

installed   in   an   environment   with   a   nominal   room

temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate

 for all initiating and

indicating   device   loops.     Most   devices   cannot   tolerate

more   than   a   10%   I.R.   drop   from   the   specified   device

voltage.

Like all solid state electronic devices,

 this system may

operate erratically or can be damaged when subjected to

lightning-induced   transients.     Although   no   system   is

completely   immune   from   lightning   transients   and

interferences, proper grounding will reduce susceptibility.

Overhead or outside aerial wiring is not recommended,

due   to   an   increased   susceptibility   to   nearby   lightning

strikes.  Consult with the Technical Services Department

if any problems are anticipated or encountered.

Disconnect AC power and batteries

  prior to removing

or inserting circuit boards.  Failure to do so can damage

circuits.

Remove all electronic assemblies

  prior to any drilling,

filing,   reaming,   or   punching   of   the   enclosure.     When

possible, make all cable entries from the sides or rear.

Before   making   modifications,   verify   that   they   will   not

interfere   with   battery,   transformer,   and   printed   circuit

board location.

Do not tighten screw terminals

 more than 9 in-lbs.

Over-tightening   may   damage   threads,   resulting   in

reduced   terminal   contact   pressure   and   difficulty   with

screw terminal removal.

Though   designed   to   last   many   years

,   system

components can fail at any time.   This system contains

static-sensitive components.  Always ground yourself with

a proper wrist strap before handling any circuits so that

static charges are re- moved from the body.  Use static-

suppressive  packaging  to  protect  electronic assemblies

removed from the unit.

Follow   the   instructions

  in   the   installation,   operating,

and programming manuals.   These instructions must be

followed   to   avoid   damage   to   the   control   panel   and

associated   equipment.     FACP   operation   and   reliability

depend upon proper installation by authorized personnel.

FCC Warning

WARNING:   This   equipment   generates,   uses,   and   can

radiate radio frequency energy and if not installed and

used   in   accordance   with   the   instruction   manual,   may

cause interference to radio communications.  It has been

tested   and   found   to  comply   with  the   limits   for  class  A

computing  device  pursuant  to Subpart  B  of Part  15  of

FCC   Rules,   which   is   designed   to   provide   reasonable

Содержание HP101U

Страница 1: ...ventional Fire Alarm Control Panel Installation And Operation Manual NOTICE All information documentation and specifications contained in this manual are subject to change without prior notice by the manufacturer ...

Страница 2: ...himneys may inhibit particle or smoke flow Smoke particles may become cold stratify and not reach the ceiling or upper walls where detectors are located Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to ala...

Страница 3: ... for a specified time and only if the batteries have been properly maintained and replaced regularly Equipment used in the system may not be technically compatible with the control It is essential to use only equipment listed for service with your control panel Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disab...

Страница 4: ...device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to lightning induced transients Although no system is completely immune from lightning transients and interferences proper grounding will reduce susceptibility Overhead or outside aerial wiring is not recommended due to an increased susceptibility to nearby lightning strikes ...

Страница 5: ...ments This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Le present appareil numerique n emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage rad...

Страница 6: ...Notes ...

Страница 7: ...5 COMMUNICATION WITH REPEATER PANELS 20 CHAPTER 3 PROGRAMMING INSTRUCTIONS 21 3 1 KEY FUNCTIONS 21 3 2 ENTERING PROGRAM MODE 21 3 3 PROGRAMMING FUNCTIONS 21 3 4 ACTIVATE SOUND OUTPUT BY MANUAL 21 3 5 ZONE DISABLE 22 3 6 SOUND DISABLE 22 3 7 MANUAL AUTOMATIC RUNNING MODE SWITCH 22 3 8 ZONE INPUT MODE SELECTION 22 3 9 EARTH FAULT CHECK SELECTION 22 3 10 EARTH FAULT CHECK SELECTION 22 CHAPTER 4 OPERA...

Страница 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...

Страница 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...

Страница 10: ...ollowing sections Table 1 1 FACP Number of Detection Zones Number of Sounder Outputs Output Delay Settings 8113 4 4 1 N A 8113 8 8 2 N A 8113 16 16 4 N A 1 1 Product Features 4 8 16 Class B Initiating Device Circuits IDCs All zones accept conventional detectors and any normally open contact device Four Class B Notification Appliance Circuits NACs One Form AAlarm Relay One Form A Trouble Relay One ...

Страница 11: ...Page 11 of 36 ...

Страница 12: ...The functions of terminal Page 12 of 36 ...

Страница 13: ...Page 13 of 36 ...

Страница 14: ...r Loop Current is sufficient to ensure operation of two alarmed detectors per zone Standby Current 7 26 mA Three Relays Output Relay contact rating 2 0 amps 30 VDC resistive 2 0 amps 30 VAC resistive Nonresettable 24 VDC Power Maximum ripple voltage 10 mVRMS Operating Voltage nominal 24 volts Total DC current available from this output is up to 500 mA Recommended maximum Standby current is 150 mA ...

Страница 15: ...ult yellow LED Manual red LED Automatic red LED Sound1 to 4 red LED or yellow LED Zone Fire Alarm red LED Zone Fault Alarm yellow LED Ground Fault yellow LED FIGURE 1 3 1 PANEL 4 LEDs and Keypad Page 15 of 36 ...

Страница 16: ...Page 16 of 36 ...

Страница 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...

Страница 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...

Страница 19: ...tput 1000 mA 24 Volt Nonresettable Power Output 1000 mA 24 Volt Battery Charger up to 18 AH batteries EIA 485 Port interfaces to Annunciators and Graphic Annunciators and Remote Relay Module Sounder Notification Appliance Circuits Four Notification Appliance Circuits Relays Three dry relays for system alarm system trouble and supervisory are provided standard Contacts are rated 2 0 amps 30 VDC res...

Страница 20: ...d pre mounted in the cabinet Cabinet The cabinet is red and the backbox measures 14 57 37 cm long X 17 32 44 cm high X 3 94 10cm deep and provides space for two batteries up to 7 Amp Hours Power Module Assembly One 75VA power module is provided standard with the panel Batteries The cabinet provides space for 7 Amp Hour batteries larger batteries up to 18 Amp Hour batteries use the external battery...

Страница 21: ...e number of conductors required for the devices to be installed Sufficient knockouts are provided for wiring convenience Select the appropriate knockout s and pull the required conductors into the box All wiring should be in accordance with the National and or Local codes for fire alarm systems 2 2 Backbox Mounting Open the door Remove the main PC board assembly by unscrewing the four screws in th...

Страница 22: ...cal Code use 14 AWG 2 00 mm2 1 6 mm O D or heavier gauge wire with 600V insulation No other equipment may be connected to this circuit In addition this circuit must be provided with overcurrent protection and may not contain any power disconnect devices A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection Connect the Earth Ground w...

Страница 23: ...f contact is made with sulfuric acid immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention FIGURE 2 3 Typical Operating Power Connections AC Power Input Terminals The AC 90 270V power input wires must connected to AC Power input terminals Live Earth Neutral from left to right And there is one 5A fuse inserted into the terminal Page 23 of 36 ...

Страница 24: ...Page 24 of 36 ...

Страница 25: ... RESETABEL DC24V Terminal Refer to the Device Compatibility Document for a list of compatible smoke detectors It is allowable to mix an assortment of device types i e smoke detectors heat detectors pull stations etc on any zone 2 5 Input Supervisory Appliance Circuits Any switch or push button can be connected in supervisory terminal IN1 IN2 Normal Close NC Alarm In the normal the switch that conn...

Страница 26: ...OUT Circuits The PANEL provides one DC24V positive output OP and one open collector GND output OC when panel in alarm status When the panel alarms the terminal OP would connected with DC24V positive and the terminal OC would connected with GND The maximum current carrying capacity of OP or OC is 1A 24VDC Page 26 of 36 4 Wire Smoke Detector Power 1000 mA 24VDC filtered resettable power for 4 wire s...

Страница 27: ...cabinet All power limited circuit wiring must remain at least 0 25 6 35 mm away from any nonpower limited circuit wiring Furthermore all power limited and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the PANEL is illustrated in Figure 2 3 2 11 RS485 Communication with repeater panels Page 27 of 36 A B 2 4 V...

Страница 28: ... Program Mode from the keypad shuts off the fire protection and causes the all other LED turn off except the relative function programming LED 3 1 Key Functions The function of each key in Program Mode is illustrated below 3 2 Entering Program Mode To enter program mode the Mode key must be pressed and held for more than three seconds time to prevent accidental activation Once in Programming Mode ...

Страница 29: ...utomatically the disabled Zone Yellow LED turns on and the Zone Disable LED turns on 3 7 Manual Automatic running mode switch 1 Press and held Mode key for more than three seconds until the Activate LED blinks 2 Press Up and Down arrow key to select Manual or Automatic LED blinks 2 Press Enter Mode key to set panel running mode In program mode press Cancel Silence key to exit the program mode in a...

Страница 30: ...put will be turned OFF The corresponding Sound LED will be turned OFF The main circuit board signal Silence LED will be turned ON Upon the occurrence of a subsequent event alarm or trouble signal Silence is overridden and the control panel will respond to the new event Mute An Mute key is located on the PANEL keypad refer to Figure 4 1 The Mute key silences the system piezo sounders and changes al...

Страница 31: ...diately Mute LED A yellow LED that turns on to indicate that an Alarm or Fault condition exists in the system but piezo sounder have been silenced Silence LED A yellow LED that turns on to indicate that an Alarm condition exists in the system but Notification Appliance Circuits have been silenced Fire Alarm LED A red LED that turn on when a system fire alarm condition is detected Fault LED A yello...

Страница 32: ...ault LED Yellow LEDs that blink to indicate that a fault or abnormal condition exist on the corresponding zone It turns on steady when Mute key is pressed LEDs on Main PCB board Charger LED A green LED that remains on while the batteries has been charging by AC power Ground Fault LED A yellow LED that remains on while the panel has earth fault System Fault LED A yellow LED that remains on while th...

Страница 33: ...o the waterflow valve and or a tamper switch is to be monitored If the tamper switch has been activated normally open contacts close a supervisory alarm condition will occur When a supervisory condition occurs the control panel will cause the following Turn on the supervisory LED Pulse system piezo sounders second On second Off Turn on supervisory relay 4 3 4 System Supervisory Restoral Response W...

Страница 34: ...quired Standby Time in Hours Current amps X 24 or 60 Hours Alarm Load Required Alarm Time in Hours Current amps X i e 5 min 0 084 hours Add Standby and Alarm Load for Required Ampere Hour Battery Multiply by derating factor of 1 2 X1 2 Note 1 7 Ampere Hour battery can be located in the backbox 2 Batteries larger than 7 Ampere Hour up to 18 Ampere Hour require the External battery box Page 34 of 36...

Страница 35: ... the resettable and nonresettable DC24 output Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified see Table A 2 TABLE A 3 Filtered Load in Alarm 24 VDC of Current Device Type Devices amps Total Current amps Main Circuit Board 1 X 0 138 4 wire Smoke Detector2 X Power Supervision Relay3 X 0 025 Notification Appliances4 X Notifi...

Страница 36: ...t meters WIRE GUAGE Initiating Device Circuit Connects to Initiating Devices Untwisted unshielded wire Do not exceed 100 ohms 10 000 3 000 m 8 000 2 400 m 4 875 1 480 m 3 225 975 m 12 AWG 3 25 mm2 Belden 9583 WPW999 14 AWG 2 00 mm2 Belden 9581 WPW995 16 AWG 1 30 mm2 Belden 9575 WPW991 18 AWG 0 75 mm2 Belden 9574 WPW975 EIA 485 Connects to annunciator modules and relay module Twisted shielded pair ...

Отзывы: