Figure 2.1 -
The dimensions of mounting enclosure
2.3 AC Power Connection
WARNING!
To reduce the risk of electrical shock, make sure that all power has been turned off or
disconnected prior to attempting to connect AC power to the Power Supply.
Apply the AC Power BEFORE connecting the batteries to the Panel!
Provide the Fire Alarm Control Panel with a dedicated AC Circuit rated 10 Amps or
higher. Refer to figure 2.2 for the AC power wiring diagram.
Enter the power cable into the Cabinet via a knock out hole.
Attach the brown (live) wire from the source to the terminal labeled “L” terminal..
Attach the blue (neutral) wire from the source to the terminal labeled “N” terminal.
Attach the ground wire from the source to the terminal labeled “E” terminal..
Figure 2.2 - AC power wiring connection
2.4 Battery Installation
The batteries are placed at the bottom of the enclosure. The panel is fully protected if
the batteries are connected in the wrong polarity. The yellow battery fault LED on the
display circuit board will show steady in such a condition. When the green battery
LED is on steady it shows that the battery condition and connections are normal. See
Figure 2.3 below.