HST HP101 Скачать руководство пользователя страница 6

                                                                 

protection   against   telephone   line   failure,   backup   radio   transmission   systems   are
recommended.

The most common cause of fire alarm malfunction is insufficient maintenance. To
keep the entire fire alarm system in excellent working order, ongoing maintenance is
required   as   the   manufacturer’s   recommendations,   and   UL  and   NFPA  72  shall   be
followed. Environments with large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement should be arranged through the
local manufacturer’s representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be performed by authorized
professional   fire   alarm   installers   only.  Adequate   written   records   of   all   inspection
should be kept.

1.4 Installation Precautions

WARNING 

– 

Several different sources of power can be connected to the fire alarm

control   panel.   Disconnect   all   sources   of   power   before   servicing   the   control   unit.
Associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this manual is read and
understood fully.

CAUTION

 

– 

System Reacceptance Testing Requirements. To ensure proper system

operation,   this   product   must   be   tested   in   accordance   with   NFPA   72   after   any
programming operation or change in site specific software. Re-acceptance testing is
required after any change, addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or wiring.   All components,
circuits, system operations, or software functions known to be affected by a change
must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation
verified.

This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F
and at a relative humidity up to 93 ±2%RH (non-condensing) at 32 ±2° C/90 ±3° F.
However,   the   useful   life   of   the   system's   standby   batteries   and   the   electronic
components may be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all peripherals be installed in an
environment with a nominal room temperature of 15-27°C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer
to   the   manual   specifications   section   for   maximum   allowable   I.R.   drop   from   the
specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be

- 6 -

Содержание HP101

Страница 1: ... Fire Alarm Control Panel 4 16 Zones User Installation Manual IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice ...

Страница 2: ...E 7 2 2 MOUNTING THE ENCLOSURE 8 2 3 AC POWER CONNECTION 9 2 4 BATTERY INSTALLATION 9 2 5 ZONE INSTALLATION 10 2 6 NAC SOUNDER OUTPUT CIRCUIT INSTALLATION 10 2 7 RELAY OUTPUTS 10 2 8 RINGING THE ALARMS REMOTELY 11 2 9 SIGNALING FIRE TO ANOTHER PANEL 11 2 10 CONNECT TO REPEATER 12 2 11 MAIN PCB BOARD 12 2 12 INNER DOOR LABEL WIRING DIAGRAM 13 3 CONTROL PANEL OPERATION 14 4 LED INDICATORS 15 5 FAULT...

Страница 3: ...e following key features 4 8 or 16 conventional input zones 2 notification appliance circuits NAC Sounder with built in synchronization for ANSI 3 41and Gentex The panel comes with a 3 amp power supply Dedicated alarm and trouble relays 1 RS485 can be able to connect repeaters Housed in a 383mm W x 295mm H x 87mm D metal enclosure Enclosure supports two 12V 7Ah backup batteries 1 2 Electrical Spec...

Страница 4: ... might not function for a diversity of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a building A second floor detector for example may not sense a first floor or basement fire Particles or combustion or smok...

Страница 5: ...y to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any warning device may fail to alert people with a disability or those who have recently consumed drugs alcohol or medication Please note that Strobes can under certain circumstances cause seizures ...

Страница 6: ...ments To ensure proper system operation this product must be tested in accordance with NFPA 72 after any programming operation or change in site specific software Re acceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions know...

Страница 7: ...ndling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by a...

Страница 8: ...sonnel and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order 2 2 Mounting The Enclosure Install the enclosure as follows 1 Carefully unpack the system components and inspect for any damage due to shipping 2 Mount the enclosure in a clean dry vibration free area where extreme temperatures are not encountered The location s...

Страница 9: ...binet via a knock out hole Attach the brown live wire from the source to the terminal labeled L terminal Attach the blue neutral wire from the source to the terminal labeled N terminal Attach the ground wire from the source to the terminal labeled E terminal Figure 2 2 AC power wiring connection 2 4 Battery Installation The batteries are placed at the bottom of the enclosure The panel is fully pro...

Страница 10: ...it Installation The control panel has 2 built in output notification appliance circuits NAC Figure 2 5 shows output circuit 1 wired as a class B NAC output Observe the polarity of the wiring and the placement of the 10K end of line EOL resistor located at the very end of the class B wiring Figure 2 5 Sounder bell wiring connection 2 7 Relay Outputs Each panel has 2 forms C relays the relays are de...

Страница 11: ...s shown below when panel B closes its auxiliary contacts panel A will go into fire If the zone on panel A is set to non latching it will automatically reset when panel B opens its auxiliary contacts If both panels need to signal fire to each other simply duplicate the circuit substituting panel A for panel B and vice versa 11 Sense Zone Sense Zone Panel A 510R Resistor 4K7 EOL AUXILIARY CONTACTS C...

Страница 12: ...rm control panel can connect 64 repeaters in the same RS485 communication wires The default setting for RS485 JP1 jump is set to position 2 which EOF of RS485 is zero ohm For the end repeater of RS485 the jump JP1 should set to position 1 which the EOF of RS485 is 120 ohm 2 11 Main PCB Board 12 ...

Страница 13: ... e P e r m 2 8 V t e r m i n a l t h e a l a r m s d e v i c e s o n t h e N A C w i l l s o u n d B a t t e r y S i z e 2 x 1 2 V R e q u i r e d Z o n e 1 1 6 c i r c u i t s M a x i m u m N u m b e r o f D e t e c t o r s p e r Z o n e i s 3 0 s m o k e d e t e c t o r m a n u l c a l l p o i n t h e a t d e t e c t o r s m o k e d e t e c t o r E O L R e s is t o r 4 7 K m a x 3 0 d e v i c e ...

Страница 14: ... button Silencing the fault alarm and sounder If a fire or fault is detected the panel will automatically activate the alarm circuits To silence the alarms press the Silence button once In the alarm silenced condition press the Silence button once the sounder will be reset Using the disable function The panel allows the user to selectively disable the sense zones and the alarm zones To enter disab...

Страница 15: ...ry power condition is low or completely gone the Fault indicator comes on and the Battery LED become yellow Alarm Red LED This Indicator is lit when an alarm condition exists in the system initiated by smoke detectors heat detectors sprinkler flow switches manual pull stations manual call points or other initiating devices Along with the indicator on the panel notification appliances such as horns...

Страница 16: ...one wiring Short circuit on the sense zone wiring Detector head removal Check all detectors and call points on the sense zone indicated Check wiring is as in example diagrams and ensure the end of line monitor is a 4K7 resistor or an active end of line device Fault LED and Sounder NAC zone fault LED flashing buzzer sounding Faults monitored are Open circuit on the Sounder NAC zone wiring Short cir...

Страница 17: ...Ensure batteries are connected correctly and battery leads are secure Note Date Time Zone Event Action Required Date Completed Initials 17 ...

Отзывы: