DO NOT alter any mechanical or electrical features of the equipment
supplied
BE FAMILIAR with the building code, fire prevention code, and/or requirements of
the Authority Having Jurisdiction (AHJ) in the locale of the installation.
! Caution !
Under normal and fault conditions, AC line voltages may be present on any terminal.
Touching any component could be hazardous and result in loss of life. A short circuit
can result in arcing that could cause molten metal injuries to testing personal. To
minimize this possibility, only qualified electrical technicians familiar with electrical
hazards should perform these checkout procedures. Safety glasses should be worn by
such personnel, and instruments used for voltage measurement should be designed for
the purpose and should be in good mechanical and working order.
2.2 Mounting The Enclosure
Install the enclosure as follows:
1. Carefully unpack the system components and inspect for any damage due to
shipping.
2. Mount the enclosure in a clean, dry, vibration-free area where extreme
temperatures are not encountered. The location should be readily accessible
with sufficient room for easy installation and maintenance.
3. Mount the cabinet by using the two mounting holes located in the upper back
of the cabinet. After the panel has been properly located using the mounting
holes, the panel can be secured.
4. Complete all conduit connections to the cabinet. Use the knockouts provided
in the top and the sides.
Wire must NOT enter the bottom of the cabinet, since this area is intended for
batteries only.
- 8 -