background image

                                                                 

DO NOT alter any mechanical or electrical features of the equipment 
supplied

BE FAMILIAR with the building code, fire prevention code, and/or requirements of
the Authority Having Jurisdiction (AHJ) in the locale of the installation.

! Caution !

Under normal and fault conditions, AC line voltages may be present on any terminal.
Touching any component could be hazardous and result in loss of life. A short circuit
can result in arcing that could cause molten metal injuries to testing personal. To
minimize this possibility, only qualified electrical technicians familiar with electrical
hazards should perform these checkout procedures. Safety glasses should be worn by
such personnel, and instruments used for voltage measurement should be designed for
the purpose and should be in good mechanical and working order.

2.2   Mounting The Enclosure

Install the enclosure as follows:

1. Carefully unpack the system components and inspect for any damage due to 

shipping.

2. Mount the enclosure in a clean, dry, vibration-free area where extreme 

temperatures are not encountered. The location should be readily accessible 
with sufficient room for easy installation and maintenance.

3. Mount the cabinet by using the two mounting holes located in the upper back

of the cabinet. After the panel has been properly located using the mounting 
holes, the panel can be secured.

4. Complete all conduit connections to the cabinet. Use the knockouts provided 

in the top and the sides.

Wire   must   NOT  enter   the   bottom   of   the   cabinet,   since   this   area   is   intended   for
batteries only.

- 8 -

Содержание HP101

Страница 1: ... Fire Alarm Control Panel 4 16 Zones User Installation Manual IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice ...

Страница 2: ...E 7 2 2 MOUNTING THE ENCLOSURE 8 2 3 AC POWER CONNECTION 9 2 4 BATTERY INSTALLATION 9 2 5 ZONE INSTALLATION 10 2 6 NAC SOUNDER OUTPUT CIRCUIT INSTALLATION 10 2 7 RELAY OUTPUTS 10 2 8 RINGING THE ALARMS REMOTELY 11 2 9 SIGNALING FIRE TO ANOTHER PANEL 11 2 10 CONNECT TO REPEATER 12 2 11 MAIN PCB BOARD 12 2 12 INNER DOOR LABEL WIRING DIAGRAM 13 3 CONTROL PANEL OPERATION 14 4 LED INDICATORS 15 5 FAULT...

Страница 3: ...e following key features 4 8 or 16 conventional input zones 2 notification appliance circuits NAC Sounder with built in synchronization for ANSI 3 41and Gentex The panel comes with a 3 amp power supply Dedicated alarm and trouble relays 1 RS485 can be able to connect repeaters Housed in a 383mm W x 295mm H x 87mm D metal enclosure Enclosure supports two 12V 7Ah backup batteries 1 2 Electrical Spec...

Страница 4: ... might not function for a diversity of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a building A second floor detector for example may not sense a first floor or basement fire Particles or combustion or smok...

Страница 5: ...y to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any warning device may fail to alert people with a disability or those who have recently consumed drugs alcohol or medication Please note that Strobes can under certain circumstances cause seizures ...

Страница 6: ...ments To ensure proper system operation this product must be tested in accordance with NFPA 72 after any programming operation or change in site specific software Re acceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions know...

Страница 7: ...ndling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by a...

Страница 8: ...sonnel and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order 2 2 Mounting The Enclosure Install the enclosure as follows 1 Carefully unpack the system components and inspect for any damage due to shipping 2 Mount the enclosure in a clean dry vibration free area where extreme temperatures are not encountered The location s...

Страница 9: ...binet via a knock out hole Attach the brown live wire from the source to the terminal labeled L terminal Attach the blue neutral wire from the source to the terminal labeled N terminal Attach the ground wire from the source to the terminal labeled E terminal Figure 2 2 AC power wiring connection 2 4 Battery Installation The batteries are placed at the bottom of the enclosure The panel is fully pro...

Страница 10: ...it Installation The control panel has 2 built in output notification appliance circuits NAC Figure 2 5 shows output circuit 1 wired as a class B NAC output Observe the polarity of the wiring and the placement of the 10K end of line EOL resistor located at the very end of the class B wiring Figure 2 5 Sounder bell wiring connection 2 7 Relay Outputs Each panel has 2 forms C relays the relays are de...

Страница 11: ...s shown below when panel B closes its auxiliary contacts panel A will go into fire If the zone on panel A is set to non latching it will automatically reset when panel B opens its auxiliary contacts If both panels need to signal fire to each other simply duplicate the circuit substituting panel A for panel B and vice versa 11 Sense Zone Sense Zone Panel A 510R Resistor 4K7 EOL AUXILIARY CONTACTS C...

Страница 12: ...rm control panel can connect 64 repeaters in the same RS485 communication wires The default setting for RS485 JP1 jump is set to position 2 which EOF of RS485 is zero ohm For the end repeater of RS485 the jump JP1 should set to position 1 which the EOF of RS485 is 120 ohm 2 11 Main PCB Board 12 ...

Страница 13: ... e P e r m 2 8 V t e r m i n a l t h e a l a r m s d e v i c e s o n t h e N A C w i l l s o u n d B a t t e r y S i z e 2 x 1 2 V R e q u i r e d Z o n e 1 1 6 c i r c u i t s M a x i m u m N u m b e r o f D e t e c t o r s p e r Z o n e i s 3 0 s m o k e d e t e c t o r m a n u l c a l l p o i n t h e a t d e t e c t o r s m o k e d e t e c t o r E O L R e s is t o r 4 7 K m a x 3 0 d e v i c e ...

Страница 14: ... button Silencing the fault alarm and sounder If a fire or fault is detected the panel will automatically activate the alarm circuits To silence the alarms press the Silence button once In the alarm silenced condition press the Silence button once the sounder will be reset Using the disable function The panel allows the user to selectively disable the sense zones and the alarm zones To enter disab...

Страница 15: ...ry power condition is low or completely gone the Fault indicator comes on and the Battery LED become yellow Alarm Red LED This Indicator is lit when an alarm condition exists in the system initiated by smoke detectors heat detectors sprinkler flow switches manual pull stations manual call points or other initiating devices Along with the indicator on the panel notification appliances such as horns...

Страница 16: ...one wiring Short circuit on the sense zone wiring Detector head removal Check all detectors and call points on the sense zone indicated Check wiring is as in example diagrams and ensure the end of line monitor is a 4K7 resistor or an active end of line device Fault LED and Sounder NAC zone fault LED flashing buzzer sounding Faults monitored are Open circuit on the Sounder NAC zone wiring Short cir...

Страница 17: ...Ensure batteries are connected correctly and battery leads are secure Note Date Time Zone Event Action Required Date Completed Initials 17 ...

Отзывы: