background image

                                                                 

Once the required zones have been selected, press the ACK button (Silence alarm
button ).  If any zones were disabled, the disable LED and the relevant zone disable
LED(s)   will  remain  lit.    All   incoming   signals  from  disabled  sense  zones   will  be
ignored.  If the alarm zones are disabled, then the alarms will not be activated even if
the panel detects a fire event on an active sense zone.

 The procedure of to cancel disable is same the using disable.

Using the Evacuate function.

To evacuate the sounder(NAC) output, press the Evacuate Key and keep more than 3
seconds .
To cancel evacuate , press the Silence Key twice. 

4. LED Indicators                                                      

MAINS

When this indicator is green lit, AC power is being provided to the system from the
building's electrical system and not from the backup battery. When the AC power
condition is low or completely gone, the Fault indicator comes on and the Mains LED
become yellow. 

Battery

When   this   indicator   is   green   lit,   the   Battery   is   normal.  When   the   Battery   power
condition is low or completely gone, the Fault indicator comes on and the Battery
LED become yellow. 

Alarm Red LED

This Indicator is lit when an alarm condition exists in the system, initiated by smoke
detectors, heat detectors, sprinkler flow switches, manual pull stations, manual call
points, or other initiating devices. Along with the indicator on the panel, notification
appliances such as horns and strobes are also activated, signaling a need to evacuate
the building occupants. In an alarm condition, the fire alarm control panel indicates
where  the  alarm originated. The alarm panel can be reset once the device  which
initiated the alarm is reset, such as returning the handle of a manual pull station to its
normal position.

Fault Yellow LED

When on steady or flashing, it means that a trouble condition exists on the panel.
Fault conditions are often activated by a contaminated smoke detector or an electrical
problem   within   the   system.   Fault   conditions   are   also   activated   by   a   zone   being
disabled (disconnected from the system), low power on the backup battery, disabled
notification appliance circuits, earth ground faults, shorted circuits or open circuits.

- 15 -

Содержание HP101

Страница 1: ... Fire Alarm Control Panel 4 16 Zones User Installation Manual IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice ...

Страница 2: ...E 7 2 2 MOUNTING THE ENCLOSURE 8 2 3 AC POWER CONNECTION 9 2 4 BATTERY INSTALLATION 9 2 5 ZONE INSTALLATION 10 2 6 NAC SOUNDER OUTPUT CIRCUIT INSTALLATION 10 2 7 RELAY OUTPUTS 10 2 8 RINGING THE ALARMS REMOTELY 11 2 9 SIGNALING FIRE TO ANOTHER PANEL 11 2 10 CONNECT TO REPEATER 12 2 11 MAIN PCB BOARD 12 2 12 INNER DOOR LABEL WIRING DIAGRAM 13 3 CONTROL PANEL OPERATION 14 4 LED INDICATORS 15 5 FAULT...

Страница 3: ...e following key features 4 8 or 16 conventional input zones 2 notification appliance circuits NAC Sounder with built in synchronization for ANSI 3 41and Gentex The panel comes with a 3 amp power supply Dedicated alarm and trouble relays 1 RS485 can be able to connect repeaters Housed in a 383mm W x 295mm H x 87mm D metal enclosure Enclosure supports two 12V 7Ah backup batteries 1 2 Electrical Spec...

Страница 4: ... might not function for a diversity of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a building A second floor detector for example may not sense a first floor or basement fire Particles or combustion or smok...

Страница 5: ...y to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any warning device may fail to alert people with a disability or those who have recently consumed drugs alcohol or medication Please note that Strobes can under certain circumstances cause seizures ...

Страница 6: ...ments To ensure proper system operation this product must be tested in accordance with NFPA 72 after any programming operation or change in site specific software Re acceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions know...

Страница 7: ...ndling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by a...

Страница 8: ...sonnel and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order 2 2 Mounting The Enclosure Install the enclosure as follows 1 Carefully unpack the system components and inspect for any damage due to shipping 2 Mount the enclosure in a clean dry vibration free area where extreme temperatures are not encountered The location s...

Страница 9: ...binet via a knock out hole Attach the brown live wire from the source to the terminal labeled L terminal Attach the blue neutral wire from the source to the terminal labeled N terminal Attach the ground wire from the source to the terminal labeled E terminal Figure 2 2 AC power wiring connection 2 4 Battery Installation The batteries are placed at the bottom of the enclosure The panel is fully pro...

Страница 10: ...it Installation The control panel has 2 built in output notification appliance circuits NAC Figure 2 5 shows output circuit 1 wired as a class B NAC output Observe the polarity of the wiring and the placement of the 10K end of line EOL resistor located at the very end of the class B wiring Figure 2 5 Sounder bell wiring connection 2 7 Relay Outputs Each panel has 2 forms C relays the relays are de...

Страница 11: ...s shown below when panel B closes its auxiliary contacts panel A will go into fire If the zone on panel A is set to non latching it will automatically reset when panel B opens its auxiliary contacts If both panels need to signal fire to each other simply duplicate the circuit substituting panel A for panel B and vice versa 11 Sense Zone Sense Zone Panel A 510R Resistor 4K7 EOL AUXILIARY CONTACTS C...

Страница 12: ...rm control panel can connect 64 repeaters in the same RS485 communication wires The default setting for RS485 JP1 jump is set to position 2 which EOF of RS485 is zero ohm For the end repeater of RS485 the jump JP1 should set to position 1 which the EOF of RS485 is 120 ohm 2 11 Main PCB Board 12 ...

Страница 13: ... e P e r m 2 8 V t e r m i n a l t h e a l a r m s d e v i c e s o n t h e N A C w i l l s o u n d B a t t e r y S i z e 2 x 1 2 V R e q u i r e d Z o n e 1 1 6 c i r c u i t s M a x i m u m N u m b e r o f D e t e c t o r s p e r Z o n e i s 3 0 s m o k e d e t e c t o r m a n u l c a l l p o i n t h e a t d e t e c t o r s m o k e d e t e c t o r E O L R e s is t o r 4 7 K m a x 3 0 d e v i c e ...

Страница 14: ... button Silencing the fault alarm and sounder If a fire or fault is detected the panel will automatically activate the alarm circuits To silence the alarms press the Silence button once In the alarm silenced condition press the Silence button once the sounder will be reset Using the disable function The panel allows the user to selectively disable the sense zones and the alarm zones To enter disab...

Страница 15: ...ry power condition is low or completely gone the Fault indicator comes on and the Battery LED become yellow Alarm Red LED This Indicator is lit when an alarm condition exists in the system initiated by smoke detectors heat detectors sprinkler flow switches manual pull stations manual call points or other initiating devices Along with the indicator on the panel notification appliances such as horns...

Страница 16: ...one wiring Short circuit on the sense zone wiring Detector head removal Check all detectors and call points on the sense zone indicated Check wiring is as in example diagrams and ensure the end of line monitor is a 4K7 resistor or an active end of line device Fault LED and Sounder NAC zone fault LED flashing buzzer sounding Faults monitored are Open circuit on the Sounder NAC zone wiring Short cir...

Страница 17: ...Ensure batteries are connected correctly and battery leads are secure Note Date Time Zone Event Action Required Date Completed Initials 17 ...

Отзывы: