HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
14.11 Cleaning heat exchangers
Be sure the heat exchanger has been isolated, using primary and secondary closing
valves
Only the specially designed, pre-fitted cleaning kit and compatible agents should be
used for cleaning fusion-bonded or soldered plate heat exchangers.
Protective gloves and glasses should always be worn while these operations
.
Open top and bottom clips to
remove insulation.
To process cleaning, use CIP
connections 3/4" (CB60) or
1”1/2 (CB76).
Remove the caps on the
connections and plug in the
cleaning system.
DO NOT USE
hydrochloric acid or any other acid that may corrode stainless steel plates.
DO NOT USE
water containing more than 300 ppm CI for the preparation of cleaning solutions
.
Nitric acid (for calcium carbonate), sulphamic acid (for calcium sulphate) or citric acid (for silt
clay) can be used. The concentration should not exceed 4% at 60 ° C. Gloves and goggles
should always be worn during these operations.
Gently rinse the plates with clean water before cleaning.
14.12 Technical data
Models AMB S & D
Models SS & DS
Electrical data:
230 V/50 Hz, Single Phase + Earth 230 V/50 Hz, Single Phase + Earth
Main measurements:
Max. 485x535x970mm (LxWxH)
Max. 850x505x1315mm (LxWxH)
Weight:
50-100 kg
60-110 kg
Electric consumption, Pmax (W)
Pmax : 312 W*
Pmax : 752 W*
Imax : 3 A*
Imax : 5 A*