HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
8.4
Operating hours
Operating hours for the following variables can be checked:
x
Therm_Protec_P1/P2/P3/P4
x
AFF_leg_active
x
Cmd_P1/P2/P3/P4
x
Main_Alarm
x
SAFETY_FCT
x
Multi_P
x
High_Temp_Alarm
x
ThTr_Activated
x
ECO
x
Booster
For more information and description see
10 Parameters list
.
1.
Press
key to access to Service Menu, then click on
“Continue”.
2.
Select “Operating Hours” in the menu.
The first time you enter this menu, the list is empty.
3.
To add a variable to trend; choose
.
4.
Mark one variable to follow and press the wheel.
5.
Validate the variable by ticking in the Operating Hours
box. If this box is empty the variable is in the list but it is
not recorded.
When you go back in the menu (
key), you can see the
list with “Cmd_P1” parameter, and on the right side, the
operating hours.
For more details, click on the line to open the sub-menu.
Here you can read that P1 has been operating less than 1
hour, has been switched one time and status is On.
Proceed the same way to add extra variables.