HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
12.3 Change Modbus parameters
1.
Press
key to access to Service Menu, go to
“Login Installer”, press the wheel.
2.
Enter the current password, press the wheel to
validate.
3.
Mark
“Next" then press the wheel.
4.
Select “Interface Config”
5.
Select “Modbus”.
6.
Select the variable to change
Press the wheel to validate.
Device ID = Modbus Address of the controller
Baud Rate=Com speed
Parity = None (0) / Even /Odd
No of Stop Bits= 0/1