HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
14.9 Relay 1 and 2 contacts
Relay 1 can be NO (normally open) or NC (normally closed).
Relay 2 is always NO (normally open).
Connect the relay 1:
Operating mode
Connections on PCB bottom terminal
NO
C-NO (25-24)
NC
C-NF (25-26)
Connect relay 2 to the controller terminal 13(IN6) and 14 (OUT6).
See
4.2 Electrical wiring diagram
.
If using 230V phase through this contact, do not exceed 2A load.
14.10 Remote Control contact
The Aqua
0RGXOH$0%
can be operated by a remote controller.
To enable that connect a volt free contact between BI1 and GND.
Wire terminal name
Wire terminal number
BI1
33
GND
31 or 37
See
4.2 Electrical wiring diagram
.
NOTE
: When the contact is open, the unit operates normally. If it is closed, primary and secondary
pump are stopped and valves get a 0% (0 volt) signal. The unit is in standby but the controller
display remains activated.