Altitude requirements
The following table lists the altitude requirements for the HPE DL20 G9 server.
Specification
Value
Operating
3050 m (10,000 ft). This value can be limited by the type and number
of options installed. Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Server dimensions and clearance requirement
The following table lists the server dimensions and clearance requirement for the HPE DL20 G9
server.
Type
Description
Dimensions
Height: 4.32 cm (1.7 in)
Width: 43.46 cm (17.11 in)
Depth: 38.22 cm (15.05 in)
Weight (all hard drives, power
supplies, and processors installed)
7.88kg (17.37Ib)
Temperature and humidity requirements
The following table lists the temperature and humidity requirements for the HPE DL20 G9 server.
Specification
Value
Temperature range
Operating
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C per
every 305 m (1.8°F per every 1000 ft) above sea level to a maximum of
3050 m (10,000 ft), no direct sustained sunlight. Maximum rate of change is
20°C/hr (36°F/hr).
Non-operating
-30°C to 65°C (-22°F to 149°F)
Relative humidity (non-condensing)
Operating
Minimum to be the higher (more moisture) of -12°C (10.4°F) dew point or 8%
relative humidity. Maximum to be the lower (less moisture) of 24°C (75.2°F)
dew point or 90% relative humidity.
Non-operating
5% to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature