Table 5: Additional component power consumption
Additional component
Power consumption
Processor
130 W
443.6 Btu/h
SAS disk drive (with I/O access)
23 W
78.4 Btu/h
SAS disk (idle)
16 W
54.5 Btu/h
PCIe card
10 to 25 W
34.12 Btu/h to 85.30 Btu/h
Server physical and environmental specifications
Operating temperature and humidity ranges might vary, depending on the installed mass storage devices.
High humidity levels can cause improper disk operation. Low humidity levels can aggravate static
electricity issues and cause excessive wear of the disk surface.
NOTE:
De-rate maximum dry bulb temperature 1°/300 m (1000 ft) above 900 m (3000 ft).
Table 6: Environmental specifications (system processing unit with hard disk)
Parameter
Value
Data Center Server
Office Friendly Server
Operating temperature (up to 1524 m/5000 ft)
+5° C to +35° C (+41° F to +95° F)
Non-operating temperature
- 40° C to +70° C (40° F to 158° F)
Over-temperature shutdown
+38° C (+100° F)
Operating humidity
15% to 80% RH noncondensing
Non-operating humidity
8% to 90% RH at 65° C noncondensing
Acoustic Noise Emission (ISO 9296)
Sound Power
Level
Maximum configuration (disk
active)
LwAd = 7.0 B
LwAd = 6.0 B
Sound Pressure Level
LpAm = 52.7 dB
LpAm = 42.4 dB
Altitude
Operating altitude
0 to 3000 m (10,000 ft) maximum
Non-operating altitude
0 to 4,600 m (15,000 ft) maximum
22
Server physical and environmental specifications
Содержание AH395-9013J
Страница 13: ...Internal components Figure 1 Internal components Fans Processors DIMM expansion boards Internal components 13...
Страница 19: ...21 NIC 3 connector 22 NIC 4 connector 23 NIC link LED 24 NIC activity LED Overview 19...
Страница 186: ...2 Select Add License Key 3 Enter the license key and press Enter 186 Utilities...