40
HP ProLiant DL560 Server User Guide
CAUTION:
When using a Compaq branded 7000 Series rack,
you must install the high airflow rack door insert [P/N 327281-B21 (42U)
or P/N 157847-B21 (22U)] to provide proper front-to-back airflow and
cooling.
CAUTION:
If a third-party rack is used, observe the following
additional requirements to ensure adequate airflow and to prevent
damage to the equipment:
•
•
Front and rear doors—If the 42U server rack includes closing front
and rear doors, you must allow 5,350 sq cm (830 square inches) of
holes evenly distributed from top to bottom to permit adequate
airflow (equivalent to the required 64 percent open area for
ventilation).
Side—The clearance between the installed rack component and the
side panels of the rack must be a minimum of 7 cm (2.75 inches).
Temperature Requirements
To ensure continued safe and reliable equipment operation, install or position the
system in a well-ventilated, climate-controlled environment.
The maximum recommended ambient operating temperature (TMRA) for most
server products is 35°C (95°F). The temperature in the room where the rack is
located must not exceed 35°C (95°F).
CAUTION:
To reduce the risk of damage to the equipment
when installing third-party options:
•
•
Do not permit optional equipment to impede airflow around the
server or to increase the internal rack temperature beyond the
maximum allowable limits.
Do not exceed the manufacturer’s TMRA.
HP CONFIDENTIAL
File Name: 303212-1new.doc Last Saved On: 11/4/02 10:51 AM
Содержание ProLiant DL560
Страница 1: ...HP ProLiant DL560 Server User Guide ...
Страница 54: ......
Страница 78: ......
Страница 81: ...Server Cabling 81 HP CONFIDENTIAL File Name 303212 1new doc Last Saved On 11 4 02 10 51 AM ...
Страница 82: ......
Страница 98: ......
Страница 122: ......