This section describes the physical and environmental information.
HPE Superdome X
NOTE:
Site planning and installation included.
System Unit
Dimensions
Height
798 mm / 31.4" (18U)
Width
485 mm / 19.1"
Depth
828 mm / 32.6"
Weight
Minimum
(empty chassis with midplane
assembly and rear chassis
cage)
108 kg / 238 lb (empty chassis with midplane assembly
and rear chassis cage)
Typical
(half populated)
254 kg / 559 lb
Maximum (fully populated)
314 kg / 692 lb
BTU Rating
Maximum Heat dissipation
(fully populated system)
30.93 kBTU//hr (2.5 Tons) , 9065W
Electrical
Characteristics
AC input power: 3-phase
2N Dual Power input modules with two 5-wire cords
each: IEC309 16A or two 4-wire cords each: NEMA
L15-30P 30A. 5 wire: 12.26A per cord. 4wire: 23.3A per
cord
AC input power: Single-Phase
2N Dual Power input modules with 6 Input Receptacles
each: IEC-C19, 16/20A.
Maximum Input Current:
Single Phase (200V)
13.8A per C19 cord
Maximum Input Power total
9,250 VA at PF .98 or greater
Cooling airflow
600 CFM min; 1000 CFM@32 deg. C avg; 1900 CFM
max
Environmental
Characteristics
Acoustics
<= 8.6 bels LwA
d
(Sound Power)
Temperature - Recommended
Operating Range
+18°C to +27°C
Temperature - Allowable
Operating Range
+5°C to +40°C
Maximum rate of temperature
change
20°C/hr
Non-operating temperature
(storage)
-40°C to +80°C
Air quality
Gaseous contaminants must be at the G1 level or less
as defined by ISA Standard ISA-71.04-1985
Humidity - Recommended
Operating Range (non-
condensing)1
+5.5 °C DP to 15°C DP and 65% RH
Humidity - Allowable
Operating Range (non-
-12 °C DP and 8% RH to 24 °C DP and 85% RH