Chapter 2
System Specifications
Electrical Specifications
64
NOTE
A qualified electrician must wire the PDCA receptacle to site power using copper wire and in
compliance with all local codes.
All branch circuits used within a complex must be connected together to form a common ground. All power
sources such as transformers, UPSs, and other sources, must be connected together to form a common ground.
When only one PDCA is installed in a system cabinet, it must be installed as PDCA 0. Refer to Figure 2-1 for
the location of PDCA 0.
NOTE
When wiring a PDCA, phase rotation is unimportant. When using two PDCAs, however, the
rotation must be consistent for both.
7
3-phase
Voltage range 200
to 240 V ac,
phase-to-neutral,
50 Hz / 60 Hz
5-wire
24 A maximum
per phase
Connector and plug
provided with a 2.5 meter
(8.2 feet) power cable.
Electrician must hard wire
receptacle to 32 A site
power.
a. A dedicated branch circuit is required for each PDCA installed.
Table 2-7
Option 6 and 7 Specifics
PDCA
Part Number
Attached Power Cord
Attached Plug
Receptacle
Required
A5201-69023
(Option 6)
OLFLEX 190 (PN 600804) is a 2.5 meter (8.2 feet)
multi conductor, 600 V, 90° C, UL and CSA
approved, oil resistant flexible cable (8 AWG 60 A
capacity).
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 460R9
(60 A capacity)
A5201-69024
(Option 7)
H07RN-F (OLFLEX PN 1600130) is a 2.5 meter
(8.2 feet) heavy-duty neoprene-jacketed
harmonized European flexible cable (4 mm
2
32 A
capacity).
Mennekes
ME 532P6-14
(32 A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)
Table 2-6
Available Power Options (Continued)
Option
Source
Type
Source Voltage
(Nominal)
PDCA
Required
Input Current
Per Phase 200
to 240 V ac
a
Power Receptacle
Required
Содержание Integrity Superdome sx2000
Страница 8: ...Contents 8 ...
Страница 10: ...Tables 10 ...
Страница 14: ...Figures 14 ...
Страница 53: ...Chapter 1 Overview New Server Cabling 53 Figure 1 11 Backplane Cables ...
Страница 119: ...Chapter 3 Installing the System Turning On Housekeeping Power 119 Figure 3 37 BPS LEDs BPS LEDs ...
Страница 169: ...Appendix A 169 A sx2000 LEDs ...
Страница 174: ...Appendix A sx2000 LEDs 174 ...
Страница 187: ...Appendix B Management Processor Commands MP Command HE 187 Example B 11 HE Command ...
Страница 199: ...Appendix B Management Processor Commands MP Command PS 199 Example B 20 PS Command ...
Страница 212: ...Appendix B Management Processor Commands MP Command XD 212 ...
Страница 224: ...Appendix C Powering the System On and Off Turning On Housekeeping Power 224 Figure C 14 BPS LEDs BPS LEDs ...
Страница 230: ...Appendix D Templates Templates 230 Figure D 2 SD16 and SD32 Space Requirements ...
Страница 233: ...Appendix D Templates Templates 233 Figure D 4 Computer Floor Template ...
Страница 234: ...Appendix D Templates Templates 234 Figure D 5 Computer Floor Template ...
Страница 235: ...Appendix D Templates Templates 235 Figure D 6 Computer Floor Template ...
Страница 236: ...Appendix D Templates Templates 236 Figure D 7 Computer Floor Template ...
Страница 237: ...Appendix D Templates Templates 237 Figure D 8 Computer Floor Template ...
Страница 238: ...Appendix D Templates Templates 238 Figure D 9 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 239: ...Appendix D Templates Templates 239 Figure D 10 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 240: ...Appendix D Templates Templates 240 Figure D 11 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 241: ...Appendix D Templates Templates 241 Figure D 12 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 242: ...Appendix D Templates Templates 242 Figure D 13 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 243: ...Appendix D Templates Templates 243 Figure D 14 SD32 and SD64 and I O Expansion Cabinet Templates ...
Страница 244: ...Appendix D Templates Templates 244 ...
Страница 247: ...Index 247 W wiring check 101 wrist strap usage 76 ...