Figure 15 Single rack configuration floor space requirements
5. Rear service area depth 300 mm
1. Front door
6. Rack depth 1000 mm
2. Rear door
7. Front service area depth 406 mm
3. Rack width 600 mm
8. Total rack depth 1706 mm
4. Service area width 813 mm
If the feet are not fully raised, complete the following procedure:
1.
Raise one foot by turning the leveler foot hex nut counterclockwise until the weight of the rack
is fully on the caster (see
Figure 16 (page 33)
).
2.
Repeat
Step 1
for the other feet.
Figure 16 Raising a leveler foot
1. Hex nut
2. Leveler foot
3.
Carefully move the rack to the installation area and position it to provide the necessary service
areas (see
Figure 15 (page 33)
).
Moving and stabilizing a rack
33