Item
Requirements
EMI prevention
Take effective measures to protect the power system from the
power grid system.
Separate the protection ground of the router from the grounding
device or lightning protection grounding device as far as possible.
Keep the router far away from radio stations, radar and high-
frequency devices working in high current.
Use electromagnetic shielding when necessary.
Lightning protection
The PGND cable of the chassis is well grounded.
The grounding terminal of the AC power socket is well grounded.
A power lightning arrester is installed. (Optional)
A port lightning arrester is installed. (Optional)
A signal lightning arrester is installed at the input end of an
external signal cable. (Optional)
Electricity safety
Equip an uninterrupted power supply (UPS).
In case of emergency during operation, switch off the external
power switch.
Workbench
The workbench is stable enough
Well grounding
Cabinet-mounting
requirements
Install the router in an open cabinet if possible. If you install the
router in a closed cabinet, make sure that the cabinet is equipped
with a good ventilation system.
The rack is sturdy enough to support the weight of the router and
installation accessories.
The size of the cabinet is appropriate for the router.
The front and rear of the cabinet are at least 0.8 m (31.5 in.)
away from walls or other devices.
Safety precautions
The router is far away from any moist area and heat source.
The emergency power switch in the equipment room is located.
Tools
Installation accessories supplied with the router
User supplied tools
Reference
Documents shipped with the router
Online documents