29
4 214 283 / 00
INSTALLATION
4.8
Minimum value limiting of boiler return
temperature
Hydraulic and technical control measures are to be imple-
mented to ensure that the minimum boiler feed and return
temperatures are not fallen below.
4.9 Setting
the
temperature
controller
Boiler temperature controller, selectable TR 65-85°C
The basic setting is made by the heating installer. Selec-
tion and setting of the different heating programs accor-
ding to operating instructions.
4.10 Boiler safety valve
Heating installations and hot water supply systems are to
be protected against inadmissible overpressure by safety
valves. The blow-off pressure of the heating system safe-
ty valve must correspond to the maximum rated thermal
it's downstream isolating valve.
4.11 Filling
pump
(boiler with separate calorifier)
Speed and output regulation must correspond to the re-
made by the heating specialist.
4.12 Heating
pump
Speed and output regulation must correspond to the re-
made by the heating specialist.
4.13 Heating
connections
In the case of boiler installation in the domestic domain,
-
xible compensators.
4.14 Installing
a
flue
gas
thermometer
(optional
item)
A 3/8” sleeve with a max. length of 25 mm is to be welded
control panel; see Fig. 22.
capillary through the rear wall between the external and
round insulation.
Screw the sensor tube into the sleeve.
STB
Flue gas
temperature sensor
Fig. 22
The capillary must not be kinked.
Important note:
routed on the top, along the boiler insulating mat,
towards the back.
4.15 Gas
Boosters
A booster is required when the gas pressure at the burner
Important
If a critical system is served it is good pra-
ctise to install a duty/standby gas booster
Gas Regulations require that no more than 0.5" WG pres-
sure is lost due to pipe work resistance between the sup-
ply meter and the gas inlet.
4.15.1 Booster Installation
It is usually preferably to locate the boosters as near as
possible to the burner served rather than close to the me-
ter.
• Leave adequate access for servicing drive belts, fan
bearing assemblies, electrical motors and any acoustic
shroud.
• Ensure that the room in which the gas booster is to be
installed is well ventilated and free from dust.
set.
Содержание Max-3 plus Series
Страница 8: ...8 4 214 283 00 ASSEMBLY Fig 03 1 4 3a 3 5 5a 5b 5c 2a 2b 2 1a 6...
Страница 12: ...12 4 214 283 00 ASSEMBLY Fig 10 1a 1 2 2a 2b 3 3a 3b 4 5b 5 6 5c 5a...
Страница 16: ...16 4 214 283 00 ASSEMBLY Fig 17 1a 1 2 2a 2b 3 3a 3b 4 5b 5 6 5c 5a...
Страница 18: ...18 4 214 283 00 ASSEMBLY 24 23 22 21 20 11 12 19b 25b 25a 25 17b 17a 18g 19 17 10 9 8 15 16 14 13 Fig 21...
Страница 59: ...59 4 214 283 00...