42
4 214 283 / 00
OVERVIEW OF SETTINGS
6.6
Gas Burner Fault Finding Chart
NOTE:
.
Symptom
Possible Cause
Action
A.
Burner will not start
1.
E lectrical supply failure
1.
Check:
a. Main isolator switch is on and
power is available at the control
panel.
b. Overload protective devices of
2.
Air pressure switch on burner not
operating.
2.
Switch contacts must be in the bur-
ner start position. Check switch is
3.
Control thermostat, time, water
pressure switches or other boiler
system controls at fault.
3.
Check:
That all switches are closed
Booster is not locked out due to low
inlet gas pressure and that pressure
switches function correctly.
4.
Reset and check. Also check con-
trol thermostat setting and operati-
on.
B.
Burner starts i.e. burner
motor runs but will not
light and burner goes to
‹lockout›.
1.
No ignition spark.
1.
See action B1.
2.
Gas starvation.
2.
Purge gas pipe, check pilot valve
operation.
3.
Ultra-violet cell fault.
3.
Remove, clean and check connec-
tions and replace if necessary.
C.
Burner motor starts but
stops and re-cycles.
1.
Air pressure switch on the burner.
1.
Check:
c. burner damper is open to usual
extent.
d. air inlet to switch is not blocked.
e. switch is not stuck.
f. electrical
connection.
D.
Burner shuts down du-
ring operation and recy-
cles.
1.
As C1 above.
1.
As C1 above.
E.
Burner shuts down du-
ring operation and goes
to ‹lockout›.
1.
Flame failure.
1.
Check gas supply and pressure.
2.
Ultra-violet cell fault.
2.
As B3 above.
Содержание Max-3 plus Series
Страница 8: ...8 4 214 283 00 ASSEMBLY Fig 03 1 4 3a 3 5 5a 5b 5c 2a 2b 2 1a 6...
Страница 12: ...12 4 214 283 00 ASSEMBLY Fig 10 1a 1 2 2a 2b 3 3a 3b 4 5b 5 6 5c 5a...
Страница 16: ...16 4 214 283 00 ASSEMBLY Fig 17 1a 1 2 2a 2b 3 3a 3b 4 5b 5 6 5c 5a...
Страница 18: ...18 4 214 283 00 ASSEMBLY 24 23 22 21 20 11 12 19b 25b 25a 25 17b 17a 18g 19 17 10 9 8 15 16 14 13 Fig 21...
Страница 59: ...59 4 214 283 00...