36
4 205 503 / 14
PARAMETER LISTS
Parameter
Description
Unit
Level
Factory setting
from
gen.
1
1
- U
G
(1
50
)
11/20/21/30/41
-
UG
(125)
11/20/21/30/41
-
UG
(200)
11/20/21/30/41
-
UG
(250)
11/20/21/30/41
-
UG
(300)
11/20/21/30/41
-
UG
(350)
11/20/21/30/31/41
-
UG
(400)
35 2FN 32803 Post-venting of the fan after lock-out
sec OEM
180
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/blocking
min
–1
OEM
1200 1100 900 1000 1100 1000 900
37 2FR 32805 Fan afterrun time after operation or blocking
min OEM
3
38 2FU 32806 Fan speed at boiler freeze protection
min
–1
OEM
1500
39
2GA
32807 Waiting time after opening main gas valve or activation of heating
room fan
min OEM
0
40 2GB
32808 External main gas valve/ heating room fan available
OEM
ON
41
2HA 32809 Afterrun heating pump or shut-off valve
min
HF
5
42
2HD 32810 Summer operation (“summer kick”)
sec OEM
10
43
2IA
32811 Ignition (0-> Internal, 1-> In External, 2-> External)
OEM
2
44
2KM 32812 Step modulation (0-> off, 1->increasing, 2-> increasing and
decreasing)
HF
1
45
2LA 32813 Effect of the fault relay
HF
2
46
2NA 32814 ADC/4 value at 0 bar
OEM
25
47
2NB 32815
ADC/4 value at 6 bar and BIC 960 V.2
OEM
145
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225
48 2IB
32816 Extended external ignition time
sec OEM
8
1
1
1
1
1
1
49
2QA 32817 Reserve
%
OEM
70
Adaptations for liquid gas
27 2FF
32795 Fan speed during the first period of pre-venting
min
–1
OEM
5500 4700
3700
4600 5400
5300 3300
28 2FG
32796 Fan speed at start
min
–1
OEM
3300
2800 2200 2700
3200 3100
1600
29
2FH 32797 Maximum fan speed
min
–1
OEM
5500 4700
3700
4600 5400
5300 3300
30
2FI
32798 Minimum fan speed
min
–1
OEM
1600 1400
1300
1400 1400
1300 1300
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/blocking
min
–1
OEM
1600 1400
1300
1400 1400
1300 1300