29
4 205 503 / 14
PARAMETER LISTS
13.6 40/41 - UG (15-90)
Parameter
Description
Unit
Level
Factory setting
from
gen.
1
1
- UG
(150)
40/41
-
UG
(15)
40/41
-
UG
(20)
40/41
-
UG
(27)
40/41
-
UG
(35)
40/41
-
UG
(50)
41
-
UG
(70)
41
-
UG
(100)
1
2AA
32769 Blocking temperature
°C
OEM
95
90
90
90
90
90
90
90
2
2AC
32770 Maximum reference value
°C
BE
80
3
2AD 32771 Switch-off hysteresis above reference value
°C
OEM
10
5
5
5
5
5
5
5
4
2AE
32772 Switch-on difference relating to tripping
point
°C
HF
10
5
2AF
32773 Proportional part
°C
OEM
40
10
10
10
10
10
10
10
6
2AG
32774 Integral part
sec
OEM
100
180
180
180
180
180
180
180
7
2AH 32775 Differential part
sec
OEM
25
10
10
10
10
10
10
10
8
2AI
32776 Reference value when bus interruption
°C
HF
75
9
2AJ 32777 Max. temperature rise at low flow
temperature
°C/s OEM
1
10
2AK 32778 Max. temperature rise at high flow
temperature
°C/s OEM
0.5
11
2AL 32779 “Low” flow temperature
°C
OEM
60
12
2AM 32780 “High” flow temperature
°C
OEM
80
13
2BC
32781 Lock-out flue gas temperature
°C
OEM
110
14
2BD 32782 Blocking flue gas temperature
°C
OEM
100
15
2CA
32783 Gas pressure switch attached
OEM
ON
16
2DA 32784 Water pressure sensor attached
OEM
ON
17
2DB 32785 Water pressure warning
bar
OEM
1
18
2DC 32786 Water pressure hysteresis
bar
OEM
0.2
19
2DD 32787 Blocking pressure min.
bar
OEM
0.5
20
2DE 32788 Blocking pressure min – hysteresis
bar
OEM
0.2
21
2DF 32789 Blocking pressure max
bar
OEM
4.8
2.8
2.8
2.8
2.8
2.8
3.8
3.8
22
2DG 32790 Blocking pressure max – hysteresis
bar
OEM
0.2
23
2DH 32791 Lock-out pressure max
bar
OEM
5
3
3
3
3
3
4
4
24
2DI 32792 Max. boiler performance at pressure warning
%
OEM
50
25
2EC
32793 Ionisation warning
µA
OEM
3
26
2FA
32794 Number of hall impulses per revolution
OEM
3
2
2
2
2
2
2
2
27
2FF
32795 Fan speed during the first period of pre-
venting
min
–1
OEM
5700 5000
6300
5500 6500 6800 5200
6300
28
2FG
32796 Fan speed at start
min
–1
OEM
1900
3500
2500 2200 2500 2500 2100 2700
29
2FH 32797 Maximum fan speed
min
–1
OEM
5700 5000
6300
5500 6500 6800 5200
6300
30
2FI
32798 Minimum fan speed
min
–1
OEM
1200 1000
1300
1100 1100 1200 1200
1300
31
2FJ 32799 Upward ramp of the fan during venting
min
–1
/s OEM
500
32
2FK 32800 Downward ramp of the fan during venting
min
–1
/s OEM
200
Содержание BIC 960
Страница 41: ...41 4 205 503 14...